Orange County Emergency Services -Generator <br />PDC Project 24030 Conduit for Electrical Systems 26 05 33.13 - 4 <br />2.04 INTERMEDIATE METAL CONDUIT (IMC) <br />A.Description: NFPA 70,Type IMC galvanized steel intermediate metal conduit complying with ANSI <br />C80.6 and listed and labeled as complying with UL 1242. <br />B.Fittings: <br />1.Non-Hazardous Locations: Use fittings complying with NEMA FB 1 and listed and labeled as <br />complying with UL 514B. <br />2.Material: Use steel or malleable iron. <br />3.Connectors and Couplings: Use threaded type fittings only.Threadless set screw and <br />compression (gland)type fittings are not permitted. <br />2.05 FLEXIBLE METAL CONDUIT AND LIQUIDTIGHT FLEXIBLE METAL CONDUIT (FMC LFMC) <br />A.Manufacturers: <br />1.Allied Tube &Conduit. <br />2.Republic Conduit. <br />3.Wheatland Tube Company. <br />4.or approved equal. <br />B.Description: NFPA 70,Type FMC standard wall steel flexible metal conduit listed and labeled as <br />complying with UL 1,and listed for use in classified firestop systems to be used. <br />C.Description: NFPA 70,Type LFMC polyvinyl chloride (PVC)jacketed steel flexible metal conduit <br />listed and labeled as complying with UL 360. <br />D.Spiral strip construction shall allow the conduit to bend up to four times its internal radius. <br />E.Fittings shall be compression type with insulated throats and listed for use with conduit specified. <br />2.06 ELECTRICAL METALLIC TUBING (EMT) <br />A.Manufacturers: <br />1.Allied Tube &Conduit. <br />2.Republic Conduit. <br />3.Wheatland Tube Company. <br />4.or approved equal. <br />B.Description: NFPA 70,Type EMT cold-rolled steel electrical metallic tubing with zinc coating on <br />the inside and protected on the inside by a zinc,enamel or equivalent corrosion-resistant coating <br />complying with ANSI C80.3 and listed and labeled as complying with UL 797. <br />C.Fittings: <br />1.Description: Fittings complying with NEMA FB 1 and listed and labeled as complying with UL <br />514B. <br />2.Material: Use steel or malleable iron. <br />3.Connectors and Couplings: Use hexagonal compression (gland)type. <br />a.Do not use indenter type connectors and couplings. <br />b.Do not use set-screw type connectors and couplings. <br />2.07 RIGID POLYVINYL CHLORIDE (PVC)CONDUIT <br />A.Manufacturers: <br />1.Allied Tube &Conduit. <br />2.Republic Conduit. <br />3.Wheatland Tube Company. <br />4.or approved equal. <br />B.Description: NFPA 70,Type PVC rigid polyvinyl chloride conduit complying with NEMA TC 2 and <br />listed and labeled as complying with UL 651;Schedule 40 or Schedule 80 as indicated;rated for <br />use with conductors rated 90 degrees C. <br />C.Fittings: <br />1.Manufacturer: Same as manufacturer of conduit to be connected. <br />Docusign Envelope ID: DEDB83DA-7916-8AE5-81B0-AA1EA4D56AE9