Orange County NC Website
SWITCHES SHALL BE BY EATON, SQUARE-D, GENERAL ELECTRIC, OR <br />APPROVED EQUAL. <br />B. FUSES LESS THAN 60A SHALL BE CLASS RK5, DUAL-ELEMENT, TIME- <br />DELAY WITH INDICATION. <br />C. FUSES GREATER THAN 60A SHALL BE CLASS J, DUAL-ELEMENT, TIME- <br />DELAY WITH INDICATION. <br />D. A SET OF 3 SPARE FUSES OF EACH SIZE AND TYPE SHALL BE PROVIDED. <br />E. FUSES SUPPLYING AC SOURCE LOAD FROM INVERTER SYSTEMS SHALL BE <br />REVERSE FEED CAPABLE. <br /> <br />8. MOUNTING SYSTEMS <br /> <br />A. THE MOUNTING SYSTEM SHALL RESULT IN THE INSTALLATION OF A PV <br />SYSTEM THAT MEETS ALL LOCAL SEISMIC AND WIND REQUIREMENTS. <br />B. BALLASTED SYSTEMS SHALL BE BASED ON PANEL CLAW FR10 RACKING <br />SYSTEM. ALTERNATE RACKING MANUFACTURERS INCLUDE UNIRAC AND <br />PEGASUS. <br />C. PITCHED ROOFTOP SYSTEMS SHALL BE BASED ON IRON-RIDGE XR FLUSH <br />MOUNT. APPROVED ALTERNATE MANUFACTURERS ARE UNIRAC, AND <br />SNAPNRACK. <br />D. CONTRACTOR SHALL ENSURE THE RACKING SYSTEM TO BE USED FOR <br />CONSTRUCTION IS COMPATIBLE WITH THE MOUNTING REQUIREMENTS <br />FOR THE SOLAR PANEL USED FOR CONSTRUCTION. <br />E. RACKING SYSTEM PROVIDED MUST BE FEOC COMPLIANT AND QUALIFY <br />AS DOMESTIC CONTENT. <br />F. RACKING SYSTEM PROVIDED SHOULD HAVE A RECENTLY COMPLETED <br />DNV BANKABILITY REPORT. <br />G. FOR BALLASTED SYSTEMS, DESIGN FOR RACKING SYSTEM PROVIDED <br />MUST HAVE COMPLETED BOUNDARY LAYER WIND TUNNEL TESTING <br />WITHIN THE LAST TWO YEARS. <br />H. FOR BALLASTED SYSTEMS, RACKING SYSTEM PROVIDED MUST BE RAIL <br />BASED AND DESIGNED SUCH THAT THE SOLAR PANEL SHALL NOT BE <br />CONSIDERED AS PART OF THE LOAD PATH THAT REISIST THE <br />INTERCONNECTION FORCE UNLESS THE PANELS HAVE BEEN EVALUATED <br />OR TESTED FOR SUCH LOADING. <br />I. FOR BALLASTED SYSEMS, RACKING SYSTEM PROVIDED SHOULD INCLUDE <br />INTEGRATED PROTECTION PADS WITH FRICTION TESTING REPORTS. <br />J. FOR BALLASTED SYSTEMS, RACKING SYSTEM MAIN FASTENING <br />HARDWARE PROVIDED SHOULD INCLUDE NYLON TOQUE PATCH OR <br />SIMILAR PREVAILING TORQUE LOCKING ELEMENT <br />K. RACKING SYSTEM PROVIDED MUST INCLUDE 4 CONNECTIONS PER <br />MODULE ALL ATTACHING TO THE AIRY POINTS OF THE LONG SIDE OF THE <br />MODULE FLANGE. <br />Docusign Envelope ID: CF064D56-F89A-8651-8229-D168AFF8B909