Orange County NC Website
<br />808 Aviation Parkway, Suite 1100, Morrisville, NC 27560 – Tel: 866.328.2764 – bradyservices.com <br />Page 4 of 5 <br /> (2) Chilled Water Differential Pressure <br /> BACnet MS/TP integration to Chiller Control Panel (Chiller to be <br />provided with BACnet communications enabled) <br /> BACnet MS/TP integration to (3) Pump VFD Interface (Siemens <br />shall provide VFDs with BACnet communications enabled) <br /> <br />Implement control sequences: <br /> Enable/disable based on system demand <br /> Chilled water temperature reset logic <br /> Lead/lag if multiple chillers exist <br />o Test all alarms and interlocks. <br /> <br /> <br />Scope of Work – Chilled Water Pump Replacement <br />1. Mechanical <br /> Remove existing chilled water pumps. <br /> Install new pumps with VFDs, suction diffusers, triple-duty valves, and flexible <br />connectors. <br /> Grout pump bases and align shafts. <br /> Insulate piping and provide heat trace if required. <br /> Label piping per ANSI standards. <br /> <br />2. Electrical <br /> Provide power to new pump motors and VFDs. <br /> Install disconnect switches and verify grounding. <br /> Test voltage and rotation before start-up. <br /> <br />3. Controls <br /> Integrate pumps into BAS for: <br />o Start/stop, speed control, DP reset logic. <br /> Configure lead/lag sequencing. <br /> Install pressure sensors for differential pressure control. <br /> Test alarms and interlocks. <br />Docusign Envelope ID: 8E7F8A38-088B-4CBD-BB93-D9B5A5272522