Orange County NC Website
16 <br /> + BRADY <br /> ■ (2) Chilled Water Differential Pressure <br /> • BACnet MS/TP integration to Chiller Control Panel (Chiller to be <br /> provided with BACnet communications enabled) <br /> • BACnet MS/TP integration to (3) Pump VFD Interface (Siemens <br /> shall provide VFDs with BACnet communications enabled) <br /> Implement control sequences: <br /> • Enable/disable based on system demand <br /> ■ Chilled water temperature reset logic <br /> ■ Lead/lag if multiple chillers exist <br /> o Test all alarms and interlocks. <br /> Scope of Work — Chilled Water Pump Replacement <br /> 1. Mechanical <br /> • Remove existing chilled water pumps. <br /> • Install new pumps with VFDs, suction diffusers, triple-duty valves, and flexible <br /> connectors. <br /> • Grout pump bases and align shafts. <br /> • Insulate piping and provide heat trace if required. <br /> • Label piping per ANSI standards. <br /> 2. Electrical <br /> • Provide power to new pump motors and VFDs. <br /> • Install disconnect switches and verify grounding. <br /> • Test voltage and rotation before start-up. <br /> 3. Controls <br /> • Integrate pumps into BAS for: <br /> o Start/stop, speed control, DP reset logic. <br /> • Configure lead/lag sequencing. <br /> • Install pressure sensors for differential pressure control. <br /> • Test alarms and interlocks. <br /> 808 Aviation Parkway, Suite 1100, Morrisville, NC 27560 — Tel: 866.328.2764 — bradyservices.com <br /> Page 4 of 5 <br />