Orange County Health Department Improvements Smith Sinnett /2024008 <br />Hillsborough,NC Orange County Asset Management Services <br />ELECTRICAL WORK 23 05 12 - 1 <br />SECTION 23 05 12 <br />ELECTRICAL WORK <br />PART 1 GENERAL <br />1.01 DIVISION OF WORK <br />A This Contractor shall be responsible for the final electrical and the entire control connections and wiring to <br />all equipment installed as part of his contract. <br />B Contractor shall review the electrical plans,where applicable,to establish points of connection and the extent <br />of his electrical work to be provided in his contract. <br />C Unless otherwise noted,this Contractor shall wire from his equipment to disconnect switches,junction <br />boxes,or panelboard circuit breakers as provided by the Electrical Contractor or as required by the existing <br />conditions. <br />D All power and control wiring shall be in conduits. Refer to electrical specifications for conduit and conduit <br />fittings. <br />E All electrical work shall be performed by a licensed electrician. <br />F All electrical work shall be in accordance with the State Building Code and all its supplements,the latest <br />edition of the National Electrical Code and the electrical specifications. <br />PART 2 PRODUCT <br />2.01 GENERAL REQUIREMENTS <br />A All motor starters,disconnects,switches,relays,conduits,conductors,etc.that are required for a complete <br />electrical power and/or control system shall conform to the requirements set forth by NEC. <br />B Refer to the plans for the type,size and electrical characteristics of the starters,disconnects,switches,relays, <br />conductor and conduits. <br />C All conductors and conduits shall be sized as noted on the plans or As required per NEC. <br />D All individual motor starters for mechanical equipment (i.e.,fans,pumps,etc.)shall be furnished and <br />installed under Division 23. <br />E All relays,actuators,timers,seven-day clocks,alternators,pressure,vacuum,float,flow,pneumatic-electric, <br />and electric-pneumatic switches,aquastats,freezestats,line and low voltage thermostats,thermals,remote <br />selector switches,remote push-button stations,emergency break-glass stations,interlocking,disconnect <br />switches beyond termination point,and other appurtenances associated with equipment under Division 23 <br />shall be furnished,installed and wired under Division 23. <br />PART 3 EXECUTION <br />3.01 GENERAL REQUIREMENTS <br />A All motor starters,disconnects,and switches shall be installed on or as close to the equipment they are <br />serving as possible,or where shown on the plans. <br />B Electrical connection to equipment subject to vibration which develops objectionable noises shall be made <br />from the conduit system with short lengths of flexible "Liquid-Tite"conduit.Connection to other equipment <br />shall be made with rigid conduit. <br />C Conduits shall be run in a concealed space such as wall cavities,ceiling cavities,etc.except in the <br />mechanical rooms where conduit may be run exposed. <br />END OF SECTION 23 05 12 23 05 12 <br />Docusign Envelope ID: 2D852F9B-A7CF-462A-9536-444A53AA848A