ANSI/UL1479 (ASTM E814)CAN/ULC S115 <br />F Ratings —1 and 2 Hr (See Items 1 and <br />3) <br />F Ratings — 1 and 2 Hr (See Items 1 and <br />3) <br />T Rating — 0 Hr FT Rating — 0 Hr <br />L Rating at Ambient — Less Than 1 <br />CFM/sq ft <br />FH Ratings —1 and 2 Hr (See Items 1 <br />and 3) <br />L Rating at 400 F — Less Than 1 CFM/sq <br />ft FTH Rating — 0 Hr <br />L Rating at Ambient — Less Than 1 <br />CFM/sq ft <br />L Rating at 400 F — Less Than 1 CFM/sq <br />ft <br />System No. W-L-1054 <br />C R <br />Classified by <br />Underwriters Laboratories, Inc. <br />to UL 1479 and CAN/ULC-S115 <br />US <br />1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified <br />in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction <br />features: <br />A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) <br />lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are <br />used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed <br />between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152 <br />mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the <br />opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides. <br />B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of <br />layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance <br />Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls. <br />The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly. <br />2. Through-Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. <br />The annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tubing to be <br />rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe. <br />C.Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) . diam steel conduit. <br />D.Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. <br />E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) regular (or heavier) copper pipe. <br />3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces <br />of wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the <br />pipe wall interface on both surfaces of wall. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant <br />*Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as <br />Canada), respectively. <br />SECTION A-A <br />A <br />A <br />1A <br />3 <br />2 1B <br />JUNCTION BOX <br />ATTACHED <br />TO STRUCTURE <br />BRANCH CIRCUIT <br />CONDUIT (1/2" EMT) <br />FOR EACH FIXTURE, PROVIDE TWO STEEL <br />WIRE SUPPORTS TO STRUCTURE, ONE <br />WIRE AT EACH CORNER OF THE FIXTURE, <br />THEN SCREW FIXTURE TO THE MAIN <br />RUNNERS OF THE LAY-IN CEILING TRACK, <br />AT THE FOUR CORNERS, WITH SHEET <br />METAL SCREWS. <br />A. <br />6 FEET LENGTH OF FLEXIBLE <br />CONDUIT TO ALLOW FOR <br />RELOCATION. INCLUDE GROUND <br />WIRE. ALL CONDUCTORS #12 AWG <br />COPPER, MAXIMUM OF THREE(3) <br />FLEXIBLE RUNS PER JUNCTION BOX. <br />LAY-IN TYPE <br />TROFFER <br />GRID TYPE <br />INVERTED <br />"T" CEILING <br />ACOUSTICAL PANEL <br />BRANCH <br />CIRCUIT <br />CONDUIT <br />4" SQUARE <br />DEVICE <br />BOX <br />BOX DEVICE COVER <br />WITH RAISED RING OF <br />PROPER DEPTH AND <br />TYPE FOR WALL <br />CONSTRUCTION. RING <br />TO FINISH FLUSH <br />WITH WALL. <br />DEVICE <br />TRIM <br />PLATE <br />1 #12 AWG SOLID COPPER <br />GREEN INSULATED JUMPER <br />TO DEVICE GROUNDING <br />SCREW <br />1 #12 AWG SOLID COPPER <br />GREEN INSULATED <br />JUMPER <br />TO BOX BONDING SCREW <br />MAKE CIRCUIT JOINT <br />WITH TWIST-ON <br />CONNECTOR AND <br />CONNECT TO <br />DEVICE <br />WITH SINGLE LEADS <br />ANY 24VDC <br />CEILING/WALL <br />SENSOR <br />WATTSTOPPER WT1105 <br />ULTRASONIC OCCUPANCY SENSOR <br />1100 SQ. FT. 360°, TWO SIDED COVERAGE <br />LIGHTING <br />CIRCUIT <br />Wall <br />Hot <br />N White <br />Black <br />Switch <br />Red <br />White (Neutral) <br />Red <br />BlueBlackRedPOWER PACK <br />LIGHTING <br />LOAD <br />OCCUPANCY SENSORS WITHOUT ISOLATED RELAY WIRING DIAGRAM <br />(EQUALS: HUBBELL, SENSOR SWITCH) <br />GENERAL NOTES: <br />OCCUPANCY SENSOR SINGLE LEVEL WIRING DIAGRAM <br />(EQUALS: WATTSTOPPER, HUBBELL, SENSOR SWITCH) <br />ANY 24VDC <br />WALL <br />SWITCH/SENSOR <br />Ground Green <br />Green/YellowGround <br />Line Black Red (Load) <br />Neutral <br />LIGHTING <br />LOAD <br />DSW-100 <br />DUAL TECHNOLOGY WALL SWITCH SENSOR <br />35' x 30' PIR MAJOR MOTION ULTRASONIC 20' x 20' <br />20' x 15' PIR MINOR MOTION ULTRASONIC 15' x 15' <br />( )OS <br />WATTSTOPPER WT2255 <br />ULTRASONIC OCCUPANCY SENSOR <br />90 LINEAR FT. 360°, TWO SIDED COVERAGE <br />WATTSTOPPER WT605 <br />ULTRASONIC OCCUPANCY SENSOR <br />600 SQ. FT. 180°, ONE SIDED COVERAGE <br />WATTSTOPPER DT305 <br />DUAL TECHNOLOGY OCCUPANCY SENSOR <br />1100 SQ. FT. 360°, TWO SIDED COVERAGE <br />WATTSTOPPER WPIR <br />PASSIVE IFRARED OCCUPANCY SENSOR <br />300 SQ. FT. 360° COVERAGE <br />A. ALL SENSOR LOCATIONS ARE APPROXIMATE. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS PRIOR TO INSTALLATION. <br />B. ULTRASONIC CEILING MOUNTED SENSORS SHALL NOT BE LOCATED WITHIN 6'-0" OF SUPPLY/RETURN GRILLES. <br />C. CONTRACTOR IS RESPONSIBLE FOR PROPER SENSITIVITY AND TIME DELAY SETTINGS, VERIFICATION OF MANUFACTURER'S RECOMMENDED PLACEMENT AND FIELD <br />VERIFICATION OF CIRCUITS WITH RESPECT TO POWER PACK PLACEMENT. <br />D. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF REQUIRED NUMBER OF POWER PACKS. POWER PACKS SHALL BE INSTALLED IN A 4" SQUARE JUNCTION BOX. <br />E. ONE POWER PACK IS REQUIRED FOR EACH CIRCUIT THAT IS TO BE CONTROLLED. <br />F. MAXIMUM NUMBER OF SENSORS THAT CAN BE WIRED IN PARALLEL TO A SINGLE POWER PACK IS DEPENDENT ON SENSOR MODEL. (SEE INDIVIDUAL DATA SHEETS FOR mA <br />CONSUMPTION.) <br />G. SENSOR LAYOUT DRAWINGS AND PRODUCT DATA SHEETS ARE REQUIRED AS PART OF SHOP DRAWING SUBMITTALS. <br />H. ALL OCCUPANCY SENSOR WIRING SHALL BE WIRED IN ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS. <br />I. REFER TO SPECIFICATION 260923. <br />J. ALL EXPOSED WIRING SHALL BE PLENUM RATED. <br />K. ALL WALL MOUNT STYLE SENSORS SHALL BE THE SWIVEL TYPE SO THAT IT ALLOWS FOR ADJUSTMENT. NON-SWIVEL SENSORS SHALL NOT BE ACCEPTABLE. <br />LP-2 <br />LP-2 <br />NEATLY HAND WRITTEN <br />CIRCUIT IDENTIFIER OR SYSTEM <br />CONDUCTORS CONTAINED <br />WITHIN <br />COLOR CODE JUNCTION BOX <br />COVER WITH PAINT COLORS <br />AS INDICATED IN <br />SPECIFICATIONS <br />FOR SYSTEM CONTAINED <br />WITHINNOTE: <br />CONTRACTOR SHALL IDENTIFY JUNCTION BOX COVERS WITH ONE OF THE TWO METHODS <br />SHOWN ABOVE, BUT NOT BOTH. ALL JUNCTION BOX COVERS SHALL BE CONSISTENTLY <br />IDENTIFIED ACROSS THE ENTIRE PROJECT. <br />JUNCTION BOX LABELING FIRE ALARM DEVICE MOUNTING <br />COORDINATE WITH LOCAL AHJ <br />PRIOR TO ROUGH-IN <br />HORN/STROBE <br />NFPA 72 AND ADA DEVICE <br />INSTALLATION REQUIREMENTS <br />3'-0" MINIMUM <br />ANNUNCIATOR <br />MANUAL PULL STATION <br />5'-0" MAXIMUM <br />0'-4" MINIMUM <br />SMOKE/ HEAT <br />MOUNT ON A <br />BOX <br />APPROVED <br />DETECTOR <br />96" MAXIMUM <br />TOP OF DEVICE <br />80" MINIMUM <br />BOTTOM OF DEVICE <br />5'-6" <br />FLOOR <br />FINISHED <br />CONTROL <br />PANEL <br />HORN/ STROBE <br />AIR SUPPLY DIFFUSER OR <br />RETURN AIR OPENING <br />GRAPHIC <br />CONDUIT <br />& VISUAL DEVICES <br />MOUNT AUDIBLE <br />0'-4" MINIMUM, <br />SMOKE/ HEAT <br />DETECTOR <br />HORN <br />BOXES. <br />ON APPROVED <br />3'-8" <br />(3'-6" MINIMUM, <br />4'-0" MAXIMUM) <br />HINGED SIDE <br />1'-0" MAXIMUMSTROBEDATA OUTLET <br />DATA OUTLET <br />18" <br />FINISHED CEILING <br />A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING CONDUIT SLEEVES AS <br />NEEDED TO ACCOMMODATE NEW WIRING. <br />CABLING SHALL <br />HAVE <br />2' OF SERVICE LOOP <br />ABOVE CEILINGS. <br />RJ-45 <br />GENERAL NOTES: <br />SINGLE GANG OUTLET BOX <br />U.O.N. <br />3/4" CONDUIT STUBBED <br />12" ABOVE FINISHED CEILING. <br />CAT-6 CABLE TO NEAREST PATCH PANEL <br />A 24"'W X <br />1.9"D X 48"L RECESSED UNV LITHONIA # STAK-2X4-4000LM-80CRI-35K- <br />COL-MIN10-ZT-MVOLT COOPER, EATON RECESSED 2' X 4' LED, 0-10V, 10% DIMMING, 80 CRI 3500K LED <br />4028 LUMENS 33.3W <br />AE 24"'W X <br />1.9"D X 48"L RECESSED UNV <br />LITHONIA # STAK-2X4-4000LM-80CRI-35K- <br />COL-MIN10-ZT-MVOLT-E10W COOPER, EATON RECESSED 2' X 4' LED, 0-10V, 10% DIMMING, 80 CRI, WITH 10 WATT, 90 MINUTE <br />EMERGENCY BATTERY <br />3500K LED <br />4028 LUMENS 33.3W <br />MARK SIZE MOUNTING VOLT MANUFACTURER AND MODEL NO.EQUALS DESCRIPTION LAMP WATTS MTG. <br />HGT. <br />LIGHTING FIXTURE SCHEDULE <br />This drawing and the design shown is the property of Smith Sinnett Architecture, P.A. the reproduction or use of this property without the written consent of the Architect is prohibited. Any infringement of the ownership rights will be subject to legal action. All copies of this drawing must be returned to the Architect at the completion of the contract.Smith Sinnett Architecture, P.A. 2025THIS DRAWING IS FORMATTED TO BE PRINTED ON A 30" X 42" SHEETDRAWN BY: <br />CHECKED BY: <br />DESCRIPTIONDATEID <br />T 919 781 8582 <br />4600 Lake Boone Trail <br />Suite 205 <br />Raleigh, NC 27607 <br />info@smithsinnett.com <br />ITB 367-OC5452C:\Users\dlowry\OneDrive - Progressive Design Collaborative, Ltd\Documents\25027 Orange County Southern Health_MEP_R24_dlowryPDCBIM.rvt10/3/2025 9:00:03 AME1.02ORANGE COUNTY HELATH DEPARTMENT IMPROVEMENTSSCHEDULES & <br />DETAILSSOUTHERN HUMAN SERVICES HEALTH CLINIC2024008 03 OCT 20252501 Homestead Rd, Chapel Hill, NC. 27516CONSTRUCTION DOCUMENTTMC <br />JTB <br />NOT TO SCALE <br />1 OR 2 HR PENETRATION1NOT TO SCALE <br />LAY-IN FIXTURE MOUNTING3 <br />NOT TO SCALE <br />RECEPTACLE GROUNDING4 <br />NOT TO SCALE <br />OCCUPANCY SENSOR WIRING DIAGRAMS2 <br />NOT TO SCALE <br />JUNCTION BOX LABELING5 NOT TO SCALE <br />F/A DEVICE MOUNTING6 <br />NOT TO SCALE <br />DETAIL -DATA DISPLAY OUTLET7 <br />10/03/2025 <br />Docusign Envelope ID: 2D852F9B-A7CF-462A-9536-444A53AA848A