ELECTRICAL GENERAL NOTES <br />1.ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH AND SHALL CONFORM IN ALL <br />ASPECTS TO THE 2020 NATIONAL ELECTRICAL CODE (NFPA CODES & LOCAL BUILDING CODES). <br />2.ALL WORK TO BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, AND MECHANICAL <br />CONTRACTOR. WORK SHALL BE PLANNED OUT CAREFULLY BEFORE PROJECT COMMENCES TO AVOID <br />CONFLICTS BETWEEN TRADES. <br />3.DRAWINGS ARE DIAGRAMMATIC IN NATURE. ACTUAL FIELD CONDITIONS MAY REQUIRE THE <br />CONTRACTOR TO MAKE FIELD MODIFICATIONS. <br />4.ENGINEER UNDERSTANDS THAT THERE MAY BE HIDDEN EXISTING CONDITIONS. IF A HIDDEN <br />CONDITION WHICH MAY BE DEEMED DANGEROUS OR MAY COST EXCESSIVE TIME AND MONEY, <br />CONTRACTOR IS TO STOP WORK AND CONTACT ENGINEER AS SOON AS POSSIBLE. <br />5.MINIMUM CONDUIT SHALL BE 1/2”. <br />6.UNLESS OTHERWISE NOTED, ALL POWER WIRING SHOWN IS COPPER THW OR THHN/THWN CABLING <br />WITH A MINIMUM RATING OF 75C. CONDUCTORS TO BE ROUTED WITHIN PVC CONDUIT. MINIMUM WIRE <br />SIZE SHALL BE 12 AWG. <br />7.ALL CABLING WHETHER SHOWN OR NOT SHALL BE GROUNDED PER ARTICLE 250 OF THE NEC. <br />8.PROVIDE JUNCTION BOXES AT ALL JOINTS AND TURNS OF THE CONDUIT. <br />9.PROVIDE A TYPEWRITTEN CIRCUIT BREAKER SCHEDULE MOUNTED ON THE DOOR OF EACH PANEL. <br />10.ALL NEWLY INSTALLED PANELS OR DISCONNECTS SHALL BE MARKED WITH THE TAG SHOWN ON THE <br />PANEL SCHEDULES, THE SOURCE INFORMATION (PANEL NAME AND CIRCUIT FROM WHICH THEY ARE <br />FED), AS WELL AS VOLTAGE. <br />11.ALL SERVICE EQUIPMENT SHALL BE MARKED TO INDICATE THE AVAILABLE FAULT CURRENT PER NEC <br />110.24. CONTRACTOR TO COORDINATE WITH UTILITY COMPANY AND CHANGE AIC RATINGS AS <br />NECESSARY. <br />12.ALL PANELBOARDS SHALL BE CLEARLY MARKED PER NEC 110.16 FOR ARC FLASH HAZARD. <br />13.THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE POWER DISCONNECTING MEANS, <br />SUCH AS DISCONNECT, HAND-OFF-AUTO, AND MOTOR STARTERS (AS REQUIRED), FOR ALL EQUIPMENT <br />SHOWN ON THE PLUMBING, MECHANICAL, AND ELECTRICAL CONTRACTORS; HERETO GENERICALLY <br />REFERRED TO AS "DISCONNECTS". ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER <br />CONTRACTORS AS TO EXACT DISCONNECTING MEANS REQUIRED. DISCONNECT SIZES MAY BE <br />INCLUDED AS PART OF THE DESIGN. IF NOT INCLUDED WITH DESIGN, CONTRACTOR IS TO TAKE THE <br />EQUIPMENT MAXIMUM OPERATING POWER (MOP) MULTIPLIED BY 110%, AND PROVIDE THE <br />DISCONNECTING MEANS ACCORDINGLY. EC IS RELIEVED OF THIS RESPONSIBILITY ONLY IF OTHER <br />CONTRACTORS SHALL PROVIDE AS PART OF FACTORY MOUNTED EQUIPMENT. <br />14.ALL ELECTRICAL DEVICES, MATERIALS, APPLIANCES, AND EQUIPMENT SHALL BE LISTED AND LABELED <br />BY A THIRD PARTY TESTING AGENCY APPROVED BY THE STATE OF NC. <br />15.COORDINATE UTILITY METER LOCATION AND CONDUIT REQUIREMENTS WITH UTILITY COMPANY. <br />ADJUST AS NECESSARY. <br />16.PRIOR TO BUILDING OUT PANELBOARD STANDS AND METERS, COORDINATE WITH LOCAL UTILITY TO <br />CONFIRM DESIRED SERVICE ENTRANCE LOCATION. <br />ELECTRICAL DRAWINGS INDEX <br />E1.1 ELECTRICAL NOTES, SCHEDULES AND DETAILS. <br />E2.1 PARTIAL POWER PLAN. <br />2'x4' LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE. <br />1'x4' OR 1'x8' LIGHT FIXTURE. SEE LIGHTING <br />FIXTURE SCHEDULE. <br />WALL MOUNTED EXTERIOR LIGHT FIXTURE. UL LABEL <br />FOR WET LOCATION. <br />LED EXIT SIGN WITH BATTERY BACKUP PACK AND REMOTE <br />EXTERIOR EGRESS LAMP. <br />EMERGENCY LIGHT FIXTURE W/ ADJUSTABLE HEADS <br />SINGLE POLE TOGGLE SWITCH <br />THREE SWITCH TOGGLE SWITCH <br />DISCONNECT SWITCH. RATING, VOLTAGE AND AMPACITY AS <br />INDICATED ON DRAWINGS. <br />3 <br />PANELBOARD <br />BRANCH CIRCUIT <br />HOMERUN (TWO ARROWHEADS FOR TWO CIRCUITS). <br />DUPLEX RECEPTACLE OUTLET, 20 AMP, 125 VOLT (UNLESS <br />OTHERWISE NOTED). <br />DUPLEX RECEPTACLE OUTLET, 20 AMP, 125 VOLT. <br />GFI: GROUND FAULT CIRCUIT INTERRUPTER. <br />WP: WEATHER PROOF IN WEATHERPROOF ENCLOSURE <br />AND IN-USE COVER. <br />EQUIPMENT GROUNDING GREEN CONDUCTOR. <br />NEUTRAL CONDUCTOR. <br />MOTOR OUTLET <br />CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, <br />120/277 V, 1200 W AT 277 V. <br />4" SQUARE OUTLET BOX RECESSED IN WALL. ROUTE 1" EMT <br />CONDUIT IN WALL AND TERMINATE CONDUIT ABOVE CEILING <br />WITH BUSHINGS. INSTALL OUTLET BOX 18" ABOVE FLOOR. <br />EXISTING 240/1PH. RECEPTACLE TO BE REMOVED WITH <br />WIRING BACK TO SOURCE. <br />OC <br />2'x2' LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE. <br />LED UNIVERSAL MOUNT EXIT SIGN WITH BATTERY BACKUP <br />EMERGENCY LIGHT FIXTURE/EXIT SIGN COMBO W/ <br />ADJUSTABLE HEADS <br />TWO LAMP OUTDOOR RATED EMG EGRESS LT W/ <br />PHOTOCELL AND BATTERY PACK <br />WP <br />DIMMABLE TOGGLE SWITCHd <br />SYMBOL DESCRIPTION <br />ELECTRICAL SYMBOLS & ABBREVIATIONS <br />4 <br />DUPLEX RECEPTACLE. TOP HALF SWITCHED. <br />220 VAC RECEPTACLES <br />QUAD RECEPTACLE OUTLET, 20 AMP 125V. <br />FOUR POLE SWITCH SWITCH <br />PHOTOCELLPC <br />COMBO SMOKE/CARBON MONOXIDE DETECTORS/C <br />CEILING MOUNTED DUPLEX, RECEPTACLE 20 AM, 125 VOLT <br />M <br />N <br />EGC <br />220 <br />1/2 <br />WP <br />GFI <br />CEILING <br />MULTI-PURPOSE OUTLET FOR TV, CAT-6 <br />SINGLE POLE TOGGLE SWITCH WITH OCC SENSORo <br />CEILING MOUNTED EXIT SIGN WITH EGRESS LIGHTING AND <br />BATTERY BACKUP <br />FLOOR MOUNTED 20A, 125 VAC QUAD RECEPTACLE OUTLET WITH <br />CAT 6 CONNECTOR <br />DUPLEX 20A, FLOOR RECEPTACLE <br />CHARGER BASE DETAIL <br />SCALE: NOT TO SCALE <br />PNL-A <br />4000A <br />MCB <br />SERVICE <br />RATED <br />120/208 <br />VAC <br />3P,4W <br />320A, 120/208 VAC, 3Ø <br />SELF-CONTAINED METER <br />120/208 VAC 3Ø <br />PAD MOUNTED <br />UTIL TX <br />2X3#3/0,#3/0N,#1/0G,2"C <br />#6 GEC TO (2) 5/8", 10' LONG, <br />COPPER-CLAD GROUND <br />RODS.2X3#3/0,#3/0N,2"C (BY EC) <br />RISER <br />SCALE: NOT TO SCALE <br />SERVICE RECEPTACLE <br />2"X2"X3/16" STEEL ANGLE. <br />WELDED OR BOLTED TO UPRIGHTS. <br />METER PANEL <br />3" SQUARE STEEL TUBING UPRIGHTS <br />54" MIN. <br />GRADE <br />36" MIN. <br />STAND DETAIL <br />SCALE: NOT TO SCALE <br />3/4"Ø <br />PVC <br />CONDUIT <br />18"X18"X18" POURED <br />CONCRETE BASE <br />18" MIN. <br />GRADE <br />FACTORY SUPPLIED CONCRETE ANCHORS <br />STUB CONDUIT UP 36" INSIDE PEDESTAL. <br />CENTER CONDUIT PENETRATION IN <br />18"X18" PAD. <br />POWERCHARGE PEDESTAL <br />SCALE: <br />36" MIN. <br />42" MAX. <br />3'-0" <br />ENTIRELY SURROUND PIPE <br />WITH 6" OF 3000PSI CONCRETE. <br />6" SCH40 PIPE FILLED WITH <br />CONCRETE PAINT BOLLARD YELLOW <br />GRADE <br />1/2" BITUMINOUS <br />EXPANSION JOINT <br />SLOPE AWAY FROM BOLLARD <br />SLOPE CONCRETE FOR <br />POSSIBLE WATER RUN OFF <br />6" <br />PIPE BOLLARD DETAIL <br />NOT TO SCALE <br />SURROUNDED ENTIERLY WITH <br />6" OF 3000 PSI CONCRETE. <br />COORDINATE WITH UTILITY <br />ON REQUIRED PIT PAD.ELECTRICAL DESIGN FOR:ELECTRICAL NOTES, <br />SCHEDULES AND DETAILS. <br />E1.1 <br />Project <br />Name <br />Rev. #Date <br />Date 08-05-2025 <br />Drawn by LHP <br />Checked By STP <br />Scale <br />Project <br />Number <br />Sheet Name <br />Revision/Issue <br />Sheet Number <br />AS NOTED ON PLANSHILLSBOROUGH COMMONSCHARGERSHILLSBOROUGH 113 MAYO STREET, HILLSBOROUGH NC210 N. MAIN ST. SUITE 340 <br />KERNERSVILLE, NC <br />LC# P-0504 <br />AE20250617 <br />Docusign Envelope ID: 0F194B0D-BE2E-41E2-82AB-106860594B84