Scope of Work Change order <br />Demo of the installed MS/TP wiring for existing Carrier RTU-01, -02, and -08 <br />Siemens to wire the following to new Siemens PXC field panel controller for monitoring and control: <br />Carrier RTU with 2 cooling stages (RTU-01): <br />•AI Point:Duct mounted return temperature sensor.Quantity (1):Siemens 544-343-18 <br />•AI Point:Duct mounted supply temperature sensor.Quantity (1):Siemens 544-343-18 <br />•DI Point:Compressor 1 run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Compressor 2 run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Heating run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Fan run status.Quantity (1):Veris Hawkeye H300 <br />Carrier RTU with 2 cooling stages (RTU-02): <br />•AI Point:Duct mounted return temperature sensor.Quantity (1):Siemens 544-343-18 <br />•AI Point:Duct mounted supply temperature sensor.Quantity (1):Siemens 544-343-18 <br />•DI Point:Compressor 1 run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Compressor 2 run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Heating run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Fan run status.Quantity (1):Veris Hawkeye H300 <br />Carrier RTU with 1 cooling stage (RTU-01L-A): <br />•AI Point:Duct mounted return temperature sensor.Quantity (1):Siemens 544-343-18 <br />•AI Point:Duct mounted supply temperature sensor.Quantity (1):Siemens 544-343-18 <br />•DI Point:Compressor 1 run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Heating run status.Quantity (1):Veris Hawkeye H300 <br />•DI Point:Fan run status.Quantity (1):Veris Hawkeye H300 <br />Exclusions and Clarifications <br />Work to be performed during normal business hours (Monday - Friday from 7:30am to 4pm) <br />The following are not included in project and not in Siemens scope: <br />•Any demo, removal, or relocation of controls associated with equipment not mentioned in this scop <br />•Any additional control end devices including temperature/humidity sensors, DP transmitters, etc. not <br />explicitly mentioned in this SOW. <br />•Cutting, patching, painting, and any building penetrations. <br />•All BACnet integration cards not mentioned in scope <br />•Furnishing/install of any factory-mounted controls <br />•Furnishing dampers <br />•Furnishing or wiring manual/motorized volume dampers, fire dampers, smoke dampers. <br />•Furnishing of smoke detectors <br />Page 4 of 6 <br />Docusign Envelope ID: 5A712C73-3478-4F70-8870-3DA46BC3AE3D