Orange County NC Website
OC Sportsplex Pool HVAC Unit Replacement <br />PDC Project 23022 Wiring Devices 26 27 26 - 4 <br />K.Install vertically mounted receptacles with grounding pole on top and horizontally mounted <br />receptacles with grounding pole on left. <br />L.Where receptacles are indicated to be mounted above counters they shall be mounted <br />horizontally. <br />M.Install wall plates to fit completely flush to wall with no gaps and rough opening completely covered <br />without strain on wall plate.Repair or reinstall improperly installed outlet boxes or improperly sized <br />rough openings. <br />N.Install blank wall plates on junction boxes and on outlet boxes with no wiring devices installed or <br />designated for future use. <br />3.04 FIELD QUALITY CONTROL <br />A.Inspect each wiring device for damage and defects. <br />B.Test each receptacle to verify operation and proper polarity. <br />C.Test each GFCI receptacle for proper tripping operation according to manufacturer's instructions. <br />D.Correct wiring deficiencies and replace damaged or defective wiring devices. <br />3.05 ADJUSTING <br />A.Adjust devices and wall plates to be flush and level. <br />3.06 CLEANING <br />A.Clean exposed surfaces to remove dirt,paint,or other foreign material and restore to match <br />original factory finish. <br />END OF SECTION 26 27 26 <br />Docusign Envelope ID: D4F3B98E-0756-4A0C-A3AD-05AA32D39F1C