Orange County NC Website
OC Sportsplex Pool HVAC Unit Replacement <br />PDC Project 23022 Testing,Adjusting,and Balancing for <br />HVAC 23 05 93 - 10 <br />8.Suction pressure. <br />9.Total operating head pressure. <br />10.Shut off,discharge and suction pressures. <br />11.Shut off,total head pressure. <br />D.Combustion Equipment: <br />1.Boiler manufacturer. <br />2.Model number. <br />3.Firing rate. <br />4.Gas pressure at meter outlet. <br />5.Gas flow rate. <br />6.Heat input. <br />7.Flue gas temperature at outlet. <br />8.Ambient temperature. <br />9.Net stack temperature. <br />10.Heat output. <br />E.Air Cooled Condensers: <br />1.Identification/number. <br />2.Location. <br />3.Manufacturer. <br />4.Model number. <br />5.Entering DB air temperature,design and actual. <br />6.Leaving DB air temperature,design and actual. <br />F.Cooling Coils: <br />1.Identification/number. <br />2.Location. <br />3.Manufacturer. <br />4.Air flow,design and actual. <br />5.Entering air DB temperature,design and actual. <br />6.Entering air WB temperature,design and actual. <br />7.Leaving air DB temperature,design and actual. <br />8.Leaving air WB temperature,design and actual. <br />9.Water flow,design and actual. <br />10.Water pressure drop,design and actual. <br />11.Entering water temperature,design and actual. <br />12.Leaving water temperature,design and actual. <br />13.Air pressure drop,design and actual. <br />G.Heating Coils: <br />1.Identification/number. <br />2.Location. <br />3.Manufacturer. <br />4.Air flow,design and actual. <br />5.Water flow,design and actual. <br />6.Water pressure drop,design and actual. <br />7.Entering water temperature,design and actual. <br />8.Leaving water temperature,design and actual. <br />9.Entering air temperature,design and actual. <br />10.Leaving air temperature,design and actual. <br />11.Air pressure drop,design and actual. <br />H.Air Moving Equipment: <br />1.Location. <br />2.Manufacturer. <br />Docusign Envelope ID: D4F3B98E-0756-4A0C-A3AD-05AA32D39F1C