Orange County NC Website
DRAWN BY:CHECKED BY:REVISIONSSCAMPBELL@PDCENGINEERS.COMORANGE COUNTY SPORTPLEX HVACREPLACEMENTMECHANICALSCHEDULESM7.01BID/PERMIT SETORANGE COUNTYJAV SWCPDC 2302205/17/2024GENERAL NOTES:A. PROVIDE SINGLE POINT POWER CONNECTIONB. PROVIDE CURB ADAPTER TO MATCH UP TO EXISTING ROOF CURB. MINIMUM 2" INSULATION THICKNESS (R-8).C. EQUIVALENTS BY DESERT AIRE, DECTRON, OR SERESCO.D. PERFORMANCE LISTED IS AT 105°F AMBIENT OUTSIDE CONDITIONS.E. PROVIDE A SEPARATE COMPARTMENT OUTSIDE THE AIR STREAM FOR THE COMPRESSORS, TXV, AND CONTROLS.F. UNIT SHALL HAVE MINIMUM TWO INCH CLOSED CELL FOAM INJECTED DOUBLE WALL PANEL CONSTRUCTION.G. UNIT STRUCTURAL MEMBERS SHALL BE EXTRUDED ALUMINUM.H. INTERIOR WALL PANELS SHALL BE ALUMINUM CONSTRUCTION.I. UNIT FLOORING SHALL BE DIAMOND TREAD PLATE TYPE.J. AUXILIARY HEAT SHALL BE HOT WATER.K. SIZING ASSUMES THE FOLLOWING PARAMETERS:a. COMPETITION POOL AREA: 6,370 SF (80 DEG F)b. RECREATION POOL AREA: 4,352 SF (86 DEG F)c. CHILDRENS POOL / SPA AREA: 234 SF (102 DEG F)d. WET DECK AREA: 7499 SFe. ACTIVITY LEVEL FACTORY: 1.0 FOR ALLL. OUTSIDE AIR SUMMER DESIGN CONDITIONS: 94.8°F DB/77.3°F WBM. OUTSIDE AIR WINTER DESIGN CONDITIONS: 16.2°F DBN. COILS SHALL BE FULLY DIPPED AND COATED WITH A POLYESTER/ENAMEL COATING FOR MAXIMUM CORROSION PROTECTION. COATING SHALL COMPLY WITH ASTM B117/D1654 AND ASTM D2126 FOR CORROSION RESISTANCE AGAINST COMMON ACIDS, SALT, AND GASES.O. SUPPLY FAN MOTOR SHALL HAVE FACTORY VFD.P. PROVIDE HEAT RECOVERY COILS BETWEEN EXHAUST AND OUTSIDE AIR FLOW STREAMS. FACTORY GLYCOL PUMP AND HEAT RECOVERY RUNAROUND COILS WITH 33% PROPYLENE BETWEEN OUTSIDE AIR AND EXHAUST AIRSTREAMS. COILS SHALL BE FULLY COATED WITH EPOXY COATING FOR CORROSION PROTECTION.Q. PROVIDE FACTORY DISCONNECT SWITCH AND MINIMUM 35 kA SCCRR. PROVIDE BACNET INTERFACES. PROVIDE HOT WATER AUXILIARY HEATING COIL. 180/160 EWT/LWT. MAX 6 FT PRESSURE DROP.T. PROVIDE POOL HEATING OPTION.U. PROVIDE REMOTE CONDENSING UNITV. PROVIDE MERV 13 RETURN AIR, OUTSIDE AIR, AND EXHAUST AIR FILTERSW. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL GLYCOL SYSTEM FILLINGPOOL DEHUMIDIFICATION UNITTAG MAKE MODELSUPPLY FAN EXHAUST FANOUTSIDEAIR(CFM)PURGE FAN COMPRESSORS POOL PARAMETERSMOISTURECAPACITY(LBS/HR)TOTALCAPACITY(MBH)SENSIBLECAPACITY(MBH)POOL HEATINGREHEAT(MBH)HEAT RECOVERY HOT WATER COILUNITMCA/MOCPVOLT/PHWEIGHT(LBS)REMARKSAIRFLOW(CFM)ESP(in)FANNO/HPAIRFLOW(CFM)ESP(in)FANNO/HPAIRFLOW(CFM)NOMOTORS/HPTYPE NO REFRIGERANT RLAPOOL AIRTEMP. °FPOOLAIR RH%POOL 1WATERTEMP. °FPOOL 2WATERTEMP °FCAPACITY(MBH)GPMPD(PSI)GLYCOLPUMPNO/HPRUNAROUNDCOIL ROWSGLYCOLEDB(°F)LDB(°F)GPMHEATING(MBH)VALVETYPEAHU-1 POOL PAK PPK-190-GB-X 22,000 1.50 2/15.0 5,500 0.50 2/4.8 5,000 N/A N/A SCROLL 2 R410A 32.1 83 60 80 85 243.8 576.3 313.0 390.0 70 10 720.4 1/1.75 4 33% 83.0 114.4 58 GPM 580.0 3-WAY 128/150 480/3 12,700REMOTE OUTDOOR AIR DRY COOLERMARK MANUFACTURER MODELTOTALCOOLING(MBH)FLUID FAN ELECTRICALWEIGHT(LBS)DIMENSIONS(LxWxH)REMARKSGPMCONN(IN)VOL(GAL)QTY FLA MCA MFS V PHCU-1 POOL PAK NG-V-32 720.4 100 3 57.2 6 4.7 30 30 480 3 3600 148x101x80GENERAL NOTES:A. PROVIDE SINGLE POINT POWER CONNECTIONB. CONTRACTOR RESPONSIBLE FOR INITIAL GLYCOL FILLC. EQUIVALENTS BY DESERT AIRE, DECTRON, OR SERESCO.NUMBER DATE DESCRIPTION11/18/2024 <br />Docusign Envelope ID: D4F3B98E-0756-4A0C-A3AD-05AA32D39F1C