Orange County NC Website
OC Motor Pool and Maintenance Shop <br />PDC Project 23017 Conduit for Electrical Systems 26 05 33.13 - 8 <br />A.Repair cuts and abrasions in galvanized finishes using zinc-rich paint recommended by <br />manufacturer.Replace components that exhibit signs of corrosion. <br />B.Where coating of PVC-coated galvanized steel rigid metal conduit (RMC)contains cuts or <br />abrasions,repair in accordance with manufacturer's instructions. <br />C.Correct deficiencies and replace damaged or defective conduits. <br />3.04 CLEANING <br />A.Clean interior of conduits to remove moisture and foreign matter. <br />3.05 PROTECTION <br />A.Immediately after installation of conduit,use suitable manufactured plugs to provide protection <br />from entry of moisture and foreign material and do not remove until ready for installation of <br />conductors. <br />END OF SECTION 26 05 33.13 <br />Docusign Envelope ID: EF9C08D2-5B75-438B-8D6D-8473F81BD7C4