Browse
Search
2024-575-E-AMS-Hamlett Associates-RFP5417 -Motor Pool, Maintenance Shop, OPT ATS & Generator Work
OrangeCountyNC
>
Board of County Commissioners
>
Contracts and Agreements
>
General Contracts and Agreements
>
2020's
>
2024
>
2024-575-E-AMS-Hamlett Associates-RFP5417 -Motor Pool, Maintenance Shop, OPT ATS & Generator Work
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/19/2024 9:31:08 AM
Creation date
11/19/2024 9:28:16 AM
Metadata
Fields
Template:
Contract
Date
10/4/2024
Contract Starting Date
10/4/2024
Contract Ending Date
10/8/2024
Contract Document Type
Contract
Amount
$430,100.00
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
288
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
OC Motor Pool and Maintenance Shop <br />PDC Project 23017 Power Conductors and Cables 26 05 19 - 5 <br />F.Secure and support conductors and cables in accordance with NFPA 70 using suitable supports <br />and methods approved by the authority having jurisdiction. Provide independent support from <br />building structure. Do not provide support from raceways,piping,ductwork,or other systems. <br />G.Install conductors with a minimum of 12 inches of slack at each outlet. <br />H.Neatly train conductors inside boxes,wireways,panelboards and other equipment enclosures. <br />Condcutors shall not be laced or bundled to avoid overheating. <br />I.Group or otherwise identify neutral/grounded conductors with associated ungrounded conductors <br />inside enclosures in accordance with NFPA 70. <br />J.Make wiring connections using specified wiring connectors. <br />1.Remove appropriate amount of conductor insulation for making connections without cutting, <br />nicking or damaging conductors. <br />2.Do not remove conductor strands to facilitate insertion into connector. <br />3.Clean contact surfaces on conductors and connectors to suitable remove corrosion,oxides, <br />and other contaminates.Do not use wire brush on plated connector surfaces. <br />K.Insulate ends of spare conductors using vinyl insulating electrical tape. <br />L.Unless specifically indicated to be excluded,provide final connections to all equipment and <br />devices,including those furnished by others,as required for a complete operating system. <br />3.04 FIELD QUALITY CONTROL <br />A.All tests shall be completely documented indicating time of day,date,temperature and all pertinent <br />test information.All required documentation shall be submitted to the Engineer prior to,and as a <br />prerequisite for,final acceptance of the project.All test results shall be included in the Owner's <br />operation and maintenance manual. <br />B.Inspect and test in accordance with NETA ATS,Section 7.3.2. <br />1.Perform each of the following visual and electrical tests: <br />a.Compare cable data with drawings and specifications to ensure compliance with contract <br />documents. <br />b.Inspect exposed sections of conductor and cable for physical damage and correct <br />connection according to the single-line diagram. <br />c.Test bolted connections for high resistance using one of the following: <br />1)A low-resistance ohmmeter. <br />2)Calibrated torque wrench. <br />d.Inspect compression-applied connectors for correct cable match and indentation. <br />e.Inspect for correct identification. <br />f.Inspect cable jacket and condition. <br />g.Continuity test on each conductor and cable. <br />h.Uniform resistance of parallel conductors. <br />C.Insulation resistance test is required for all feeder conductors prior to energizing feeders,sub- <br />feeders,or service entrance conductors. <br />1.All current carrying feeder phase conductors and neutrals shall be tested as installed,and <br />before connections are made,for insulation resistance and accidental grounds. This shall be <br />done with a 500 volt insulation resistance tester. In the procedures listed below shall be <br />followed: <br />a.Minimum readings shall be one million (1,000,000)or more ohms for #6 AWG wire and <br />smaller,250,000 ohms or more for #4 AWG wire or larger,between conducts and <br />between conductor and the grounding conductor. <br />b.After all fixtures,devices and equipment are installed and all connections completed to <br />each panel,the Contractor shall disconnect the neutral feeder conductor from the neutral <br />bar and take a insulation resistance reading between the neutral bar and the grounded <br />enclosure. If this reading is less than 250,000 ohms,the Contractor shall disconnect the <br />branch circuit neutral wires from this neutral bar. He shall then test each one separately <br />to the panel and until the low readings are found. The Contractor shall correct troubles, <br />reconnect and retest until at 250,000 ohms from the neutral bar to the grounded panel <br />Docusign Envelope ID: EF9C08D2-5B75-438B-8D6D-8473F81BD7C4
The URL can be used to link to this page
Your browser does not support the video tag.