Browse
Search
2024-390-E-AMS-Brady Services-WCOB Server Room HVAC
OrangeCountyNC
>
Board of County Commissioners
>
Contracts and Agreements
>
General Contracts and Agreements
>
2020's
>
2024
>
2024-390-E-AMS-Brady Services-WCOB Server Room HVAC
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
7/30/2024 1:56:17 PM
Creation date
7/30/2024 1:54:37 PM
Metadata
Fields
Template:
Contract
Date
7/10/2024
Contract Starting Date
7/10/2024
Contract Ending Date
7/15/2024
Contract Document Type
Contract
Amount
$146,290.00
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
271
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Orange County West Campus Office Building -HVAC <br />PDC Project 23020 Identification for Electrical Systems 26 05 53 - 1 <br />SECTION 26 05 53 <br />IDENTIFICATION FOR ELECTRICAL SYSTEMS <br />PART 1 GENERAL <br />1.01 SECTION INCLUDES <br />A.Electrical identification requirements. <br />B.Identification nameplates and labels. <br />C.Wire and cable markers. <br />D.Warning signs and labels. <br />1.02 ADMINISTRATIVE REQUIREMENTS <br />A.Coordination: <br />1.Verify final designations for equipment,systems,and components to be identified prior to <br />fabrication of identification products. <br />B.Sequencing: <br />1.Do not conceal items to be identified,in locations such as above suspended ceilings,until <br />identification products have been installed. <br />2.Do not install identification products until final surface finishes and painting are complete. <br />1.03 SUBMITTALS <br />A.Product Data: Provide manufacturer's standard catalog pages and data sheets for each product. <br />B.Shop Drawings: Provide schedule of items to be identified indicating proposed designations, <br />materials,legends,and formats. <br />1.04 FIELD CONDITIONS <br />A.Do not install adhesive products when ambient temperature is lower than recommended by <br />manufacturer. <br />PART 2 PRODUCTS <br />2.01 IDENTIFICATION REQUIREMENTS <br />A.Identification for Equipment: <br />1.Use identification nameplate to identify each piece of electrical distribution and control <br />equipment and associated sections,compartments,and components. <br />a.Panelboards: <br />1)Identify ampere rating. <br />2)Identify voltage and phase. <br />3)Identify power source and circuit number.Include location. <br />4)Use typewritten circuit directory to identify load(s)served. <br />b.Enclosed switches,circuit breakers,and motor controllers: <br />1)Identify voltage and phase. <br />2)Identify power source and circuit number.Include location. <br />3)Identify load(s)served.Include location. <br />c.Enclosed Contactors: <br />1)Identify ampere rating. <br />2)Identify voltage and phase. <br />3)Identify coil voltage. <br />4)Identify load(s)and associated circuits controlled.Include location. <br />2.Use identification nameplate to identify disconnect location for equipment with remote <br />disconnecting means. <br />3.Available Fault Current Documentation: Use identification label to identify the available fault <br />current and date calculations were performed at locations requiring documentation by NFPA <br />70 including but not limited to the following. <br />a.Service equipment. <br />B.Identification for Conductors and Cables: <br />Docusign Envelope ID: 8DED1454-68D2-4E36-9FC6-E56FF2124E5D
The URL can be used to link to this page
Your browser does not support the video tag.