Orange County NC Website
6 1/2 <br />FOOT <br />MIN. <br />FRONT VIEWSIDE VIEW <br />OK <br />OK <br />PANELPANEL <br />6 FT <br />OR <br />LESS <br /> N.E.C ARTICLE 110-26(F)(1) <br />FIXTURE FIXTURE <br />STRUCTURAL <br />CEILING <br />SUSPENDED <br />CEILING <br />DEDICATED <br />ELECTRICAL <br />SPACE <br />DEDICATED <br />ELECTRICAL <br />SPACE <br />30" <br />MIN <br />3'-0" <br />MIN <br />SECTION <br />110-26 <br />WORKING <br />SPACE <br />SECTION <br />110-26 <br />WORKIN <br />G <br />SPACE <br />FRONT VIEWSIDE VIEW <br />OK <br />OK <br />PANELPANEL <br />6 1/2 FT <br />MINIMUM <br /> N.E.C ARTICLE 110-26 <br />FIXTURE FIXTURE <br />STRUCTURAL <br />CEILING <br />SUSPENDED <br />CEILING <br />DRAIN PAN <br />APPROVEDAIR GAPHEIGHTTOTALHEIGHTOF TRAPH <br />X <br />FULL SIZE VENT; EXTEND <br />TWO(2) PIPE DIAMETERS <br />ABOVE RIM OF DRAIN PAN <br />UNION <br />(TYPICAL) <br />REMOVABLE CAP <br />FULL SIZE <br />DRAIN <br />CLEANOUT <br />FULL SIZE OF <br />DRAIN CONNECTION <br />LOCAL <br />FLOOR DRAIN <br />BLOW THROUGH <br />X = MINIMUM 1" PLUS <br />CASING STATIC PRESSURE <br />H = MINIMUM 1" <br />X = 1/2 "H" <br />H = MINIMUM 1" PLUS <br />CASING STATIC PRESSURE <br />DRAW THROUGH <br />SWIVEL RING <br />PIPE <br />ALL <br />THREAD <br />ROD WITH <br />TWO NUTS <br />& FENDER <br />WASHERS <br />BOTTOM CHORD OF <br />BAR JOIST <br />TOP OF BAR <br />JOIST TO <br />CENTER LINE OF <br />PIPE <br />(DIM. "B") <br />MINIMUM <br />DISTANCE <br />ROUNDED TO <br />NEAREST <br />INCH AND <br />NOTED ON <br />PLAN <br />SWIVEL <br />RING TAKE <br />OUT "C""A""B""D"TOP OF BAR JOIST <br />NOTE ON PLAN: HANGER NUMBER AND "A" DIMENSION <br />3/4" <br />PIPE <br />SIZE <br />ROD <br />SIZE <br />'B' <br />DIM. <br />MIN 'C' <br />DIM. <br />MAX 'C' <br />DIM. <br />1" <br />1-1/4" <br />1-1/2" <br />2" <br />2-1/2" <br />3" <br />3-1/2" <br />4" <br />5" <br />6" <br />8" <br />3/8" <br />1/2" <br />SIZE OF ANGLE <br />IRON ON BOTTOM <br />CHORD OF BAR <br />JOIST PLUS 1-1/2" <br />1/2" <br />5/8 <br />"13/16" <br />15/16" <br />1-3/16 <br />"1-7/16" <br />1-3/4" <br />2" <br />2-1/4" <br />2-3/4" <br />3-5/16" <br />4-5/16" <br />1-5/8" <br />1-3/4" <br />1-7/8" <br />2" <br />2-3/8 <br />"2-3/4" <br />3-1/4" <br />3-5/8" <br />3-7/8" <br />4-3/4" <br />5-1/2" <br />6-3/4" <br />BAR JOIST HANGER <br />WITH NUTS AND WASHERS <br />PIPE SADDLE, 12" IN LENGTH <br />PROVIDE WITH RIGID INSERTS, <br />SAME LENGTH AS THE SADDLE <br />NOTE: <br />PIPE HANGERS, HARDWARE, ETC. SHALL BE <br />COMPLETELY GALVANIZED. <br />CONCRETE INSERT- <br />SEE SPECIFICATIONS <br />CONCRETE STRUCTURE- <br />SEE SPECIFICATIONS <br />THREADED ROD- <br />SEE SPECIFICATIONS <br />THREADED ROD- <br />SEE SPECIFICATIONS <br />STEEL STRUCTURE <br />OFFSET CLAMP- <br />SEE SPECIFICATIONS <br />PIPE HANGER- <br />SEE SPECIFICATIONS <br />PIPE <br />PIPE INSULATION <br />COUNTERFLASHING <br />CANT <br />FLASHING <br />PATE ROOF CURB - <br />COMPANY MODEL #PC-2A <br />OR APPROVED EQUIVALENT <br />INSULATION <br />ROOF <br />1. <br />NOTE: <br />REFER TO ROOFING DRAWINGS <br />FOR COORDINATION WITH <br />INSTALLING ROOF CURBS. <br />EQUIPMENT MANUFACTURER SHALL PROVIDE <br />ALL REQUIRED VALVES. REFRIGERANT PIPE <br />SIZES SHALL BE AS RECOMMENDED BY <br />EQUIPMENT MANUFACTURER. <br />NOTE: <br />AIR COOLED <br />CONDENSING <br />UNIT <br />SOLENOID VALVE <br />SIGHT <br />GLASS <br />FILTER <br />DRIER <br />EXPANSION VALVE <br />AIR <br />HANDLING <br />UNIT <br />U BEND FLOOR <br />ROOF RAIL, <br />PROVIDE THYBAR TEMS-3 <br />RAILS OR EQUIVALENT. <br />ROOF PENETRATION HOUSING <br />FOR REFRIGERANT LINES, <br />POWER, AND CONTROLS <br />EXISTING ROOF <br />LIQUID <br />SUCTION <br />NEOPRENE <br />VIBRATION <br />ISOLATOR <br />NUMBER OF CIRCUITS DEPENDENT <br />ON SIZE OF UNIT. REFER TO <br />SCHEDULE AND MANUFACTURER. <br />NOT TO SCALE <br />DETAIL -DEDICATED SPACE FOR ELECTRICAL EQUIPMENT1 <br />NOT TO SCALE <br />DETAIL -WORKING CLEARANCE FOR ELECTRICAL EQUIPMENT12 <br />NOT TO SCALE <br />DETAIL -CONDENSATE DRAIN DETAIL5 <br />NOT TO SCALE <br />HANGERS6 <br />DRAWN BY:CHECKED <br />BY: <br />REVISIONS <br />SCAMPBELL@PDCENGINEERS.COM <br />ORANGE COUNTY WEST OFFICE BUILDINGHVAC UPGRADEDETAILS <br />M5.01 <br />BID/PERMIT <br />ORANGE COUNTYJAV SWC <br />PDC 23020 02/20/2024 <br />NOT TO SCALE <br />HANGERS4 <br />NUMBER DATE DESCRIPTION <br />NOT TO SCALE <br />DETAIL -ROOF CURB3 <br />NOT TO SCALE <br />TYPICAL SPLIT SYSTEM DX UNIT7 <br />02/20/2024 <br />Docusign Envelope ID: 8DED1454-68D2-4E36-9FC6-E56FF2124E5D