Orange County NC Website
1 OF 2 <br />H-PANEL CONTROL INTERCONNECTIONS <br />Part No. 0191120SSD <br /> Rev. G 08/15/23 GENERATOR CONTROLSNotes: <br />1. Spare Outputs are Standard on Industrial <br />Product Only. GenLink® Required for <br />Programming. Contacts Rated at 5A <br />at 30VAC/30VDC <br />2. TB4 Max Wire Size: #10 AWG, <br />Recommended Tightening Torque: 14 LB-IN <br />3. TB1, TB2, TB9 & RB3 Max Wire Size: #14 AWG, <br />Recommended Tightening Torque: 12 LB-IN <br />4. Refer to H-Panel Manual for Instructions on <br />Enabling HTS Transfer Switch. Refer to HTS <br />Transfer Switch Manual for Dip Switch Settings <br />for Multiple HTS Application <br />5. Connect the RS-485 Overall Shield at Genset <br />Connection Terminal Only <br />Note 5 <br />High Voltage Connection Panel <br />RB3 <br />TB1 TB2 <br />TB4 Note 2 <br />120/240 VAC <br />Utility Supply <br />(by Customer) <br />125A Load Center <br />Verify Component <br />Ratings for Proper <br />Supply Voltage to <br />Be Provided <br />Low Voltage Connection Panel <br />Note 5 <br />Spare Outputs Notes 1 & 3 Note 3 <br />Note 3 <br />GTS Transfer Switch <br />RAP/RRP <br />HTS Transfer Switch <br />Note 4 <br />GTS or HTS Transfer Switch <br />Docusign Envelope ID: 2F58BEE5-DDBE-42EB-8DFA-5E2508488B04