Part No. 0172520SBY <br />Rev. G 11/10/21 <br />CIRCUIT BREAKER 40-600 AMP <br />CIRCUIT BREAKERS1 OF 2 <br />GENERAC CIRCUIT BREAKER INFORMATION <br />Circuit <br />Breaker <br />Amps <br />Generac C.B. <br />Lug Part Number Lug Description Wire Size Per 310-16*Frame Interrupt <br />Rating <br />Rating <br />Temperature Type <br />40 <br />0F8451 <br />Single Hole 0.656 Diameter <br /># 6 to 300 MCM Cu/Al <br />Single Conductor Only <br />Mounting Bolt 70 in lbs. Wire <br />Lug is 375 in lbs. <br />#8 <br />200 Amp Frame 18,000 <br />40 °C <br />Thermal Magnetic50 #8 <br />60 #6 <br />70 #4 <br />80 #4 <br />90 #3 <br />100 #3 <br />125 #1 <br />150 1/0 <br />175 2/0 <br />200 3/0 <br />225 <br />0A7822 <br />(1) - 600 MCM to # 4 Cu/Al <br />or (2) - 250 MCM to (2) - 1/0 <br />Mounting 70 in lb. Wire Lug <br />is 375 in lb <br />4/0 <br />400 Amp Frame 25,000 <br />250 250MCM <br />300 350MCM <br />350 500MCM <br />400 600MCM <br />450 0F9721 Standard <br />Lug <br />0F8452 Optional <br />Lug - 450-600A <br />(3) - 2/0 - 400 MCM Cu/Al <br />480 in lb. <br />(2) - 500-750 mcm Cu/Al <br />Optional Lug <br />700MCM or 2 - 4/0 <br />600 Amp UL Rated Frame 35,0005002 - 250 MCM <br />600 2 - 350MCM or 3-3/0 <br />All circuit breakers are CUL 489 listed for 120, 208, 240, 480 Volts. <br />Wire size is based on Amp Ratings at 75 °C from Table 310.16, 2008 <br />NEC. All Lugs Are Rated 75 °C. <br />Derate by Temperature <br />Temperature °C Rated Trip Current % <br />20 110 <br />30 105 <br />40 100 <br />50 95 <br />Docusign Envelope ID: 2F58BEE5-DDBE-42EB-8DFA-5E2508488B04