Orange County NC Website
2 OF 2 <br />Doc. No 0187980SBY <br />Rev. D 06/13/19 <br />Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53187 <br />P: (262) 544-4811 © 2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.GENERATOR CONTROLSThe above Figure shows the Generac GENprotect thermal protection curve for use in protection and coordination studies. The alternator <br />Thermal Damage Curve is shown just to the right of the GENprotect protection curve. If the alternator load is greater than the thermal damage <br />protection curve for the alternator, the generator set will trip off-line. For example, an overload current of 110% for 75 seconds causes an <br />overload alarm and will trip the generator off-line, shutting down the engine. GENprotect will provide generator protection over a full range of <br />time and current, from instantaneous faults to overloads lasting several minutes. An advantage of GENprotect over a MCCB is that GENprotect <br />allows for downstream breakers to clear faults without tripping the generator off-line, providing selective coordination with the first level of <br />downstream breakers. <br />GENprotect ™ <br />Seamless Protection for Industrial Power Generators <br />Docusign Envelope ID: 2F58BEE5-DDBE-42EB-8DFA-5E2508488B04