2 OF 2 <br />ALTERNATOR DATA SHEET <br />K0130124Y21 <br />Part No. 0182610SSD <br />Rev. G 03/16/20 <br />Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53187 <br />P: (262) 544-4811 © 2020 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.60Hz ALTERNATOR DATAskVA <br />10%15%20%25%30%35% <br />480 V @ 0.3PF 77 120 169 223 292 361 <br />480 V @ 0.6PF 94 139 192 251 327 403 <br />208/240 V @ 0.3PF 78 120 169 223 294 365 <br />208/240 V @ 0.6PF 89 137 192 250 327 404 <br />Efficiencies <br /> Rated Power*480 @ 0.8PF 480 @ 1.0PF 208/240 @ 0.8PF 208/240 @ 1.0PF <br />20%86.8 88.0 86.9 88.1 <br />40%89.9 92.0 90.1 92.0 <br />60%90.0 92.8 90.1 92.8 <br />80%89.3 92.6 89.1 92.5 <br />100%88.1 92.1 88.0 92.0 <br />*Rated Power value is rating kW at 120 °C Winding Temperature Rise and 0.8PF <br />LOG LOG Decrement Curve <br />10 <br />100 <br />1000 <br />10000 <br />100000 <br />0.001 0.010 0.100 1.000 10.000Output Current (A)Time (s) <br />Balanced 3-Phase Short Circuit Decrement & Thermal Damage Current <br />Limit Curves <br />208V Decrement Curve <br />480V Decrement Curve <br />240V Decrement Curve <br />208V Thermal Damage Curve <br />480V Thermal Damage Curve <br />240V Thermal Damage Curve <br />208V Control System Shutdown <br />480V Control System Shutdown <br />240V Control System Shutdown <br />Balanced 3Ø Short Circuit Decrement and Thermal Damage Current Limit Curves <br />Docusign Envelope ID: 2F58BEE5-DDBE-42EB-8DFA-5E2508488B04