Orange County NC Website
3 OF 4 <br />REMOTE EMERGENCY STOP SWITCH <br />Break Glass, H-Panel & PM-DCP <br />Part No. A0001726816 <br /> Rev. C 08/03/23 GENERATOR CONTROLSWiring - PM-DCP <br />Note: <br />1.Factory to provide jumper on TB2 as shown below to perform normal factory testing which will remain installed on unit when <br />shipped to customer. <br />2.Default input is “D12” (digital input #28) but can be changed, if needed, to another psotion. See programming instructions for <br />changing configuration. <br />3.Factory to test functionality of remote e-stop programming by temporarily removing one side of installed jumper to see if unit will <br />shut down. Reattached when testing is complete. <br />4.Customer to remove jumper when remote e-stop wiring is completed. Recommended at least 300V 18AWG wire. <br />5.Remote e-stop shipped loose with unit. <br />Docusign Envelope ID: 2F58BEE5-DDBE-42EB-8DFA-5E2508488B04