Browse
Search
2022-315-E-AMS-Siemens Industry-Efland EMS Station Building Automation System
OrangeCountyNC
>
Board of County Commissioners
>
Contracts and Agreements
>
General Contracts and Agreements
>
2020's
>
2022
>
2022-315-E-AMS-Siemens Industry-Efland EMS Station Building Automation System
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
7/28/2022 11:20:22 AM
Creation date
7/28/2022 11:20:03 AM
Metadata
Fields
Template:
Contract
Date
7/27/2022
Contract Starting Date
7/27/2022
Contract Ending Date
7/28/2022
Contract Document Type
Contract
Amount
$165,540.00
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
17
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
<br />Unrestricted Siemens Industry, Inc. <br />215 Southport Drive - Suite 900 <br />Morrisville, NC 27560 <br />Tel: 919.469-5095 <br />Fax: 919.469-9846 <br />3 of 4 <br />o (3) Toilet/Shower Fans (F-5, 6, 7) <br />§ Interlock with room light switch <br /> <br />o (2) Service Bay Fans (BAF-1, 2) <br />§ Siemens to install and wire Local BAF Touchscreen control panel (Stand Alone) that is to be <br />furnished with the fans from the factory. <br /> <br />o (1) Infrared Heater (IFH-1) <br />§ Provide integration to field provided BACnet Thermostat for monitoring and control of unit <br />through BAS. Siemens RDY2000 w/ humidity monitoring <br /> <br />o (1) Electric Unit Heater (EWH-1) <br />§ Provide standalone control of unit through factory furnished 7-day programable thermostat. <br />Provide space temp sensor for monitoring through BAS. <br /> <br />o (1) Morgue Cooler <br />§ Provide space temperature and humidity monitoring for alarming <br /> <br />o Integrations and Monitoring <br />§ Fire Alarm System Integration (40 integration points) <br />• Provide integration of Siemens Fire Alarm system to provide viewing of addressable <br />information from fire alarm control panels and for representation on BAS graphics. <br />§ Generator Monitoring (Status, Low Fuel Alarm) (10 integration points) <br />• Provide integration to Generator via BACnet interface provided by electrical contractor <br />§ Solar PV Controls (integration to BAS for monitoring) (40 integration points) <br />• Provide integration to Solar PV DAS system via BACnet interface provided by PV <br />contractor. <br />§ ATS System (integration to BAS for monitoring) (10 integration points) <br />• Provide integration to ATS via BACnet/Modbus interface provided by electrical <br />contractor <br />§ Switch Gear (integration to BAS for monitoring) (10 integration points) <br />• Provide integration to switch gear via BACnet/Modbus interface provided by electrical <br />contractor <br />§ Metering – <br />• Provide pulse inputs from the following meters for monitoring and trending purposes: <br />Main Water Supply Metering (pulse input from Utility meter) <br />Main Electrical Supply Metering (pulse input from Utility meter) <br />Main Gas Metering (pulse input from Utility meter) <br />Automatic Transfer Switch Metering (from factory) <br />Solar PV Metering (meter included in PV DAS) <br /> <br />6. All instrumentation to be Siemens standard products. <br />7. Labor to support Test & Balance contractor. (up to 24 hours) <br />8. Labor to support Commissioning contractor. (up to 24 hours) <br />9. A total of (16) hours Owner training. <br />10. All work to be completed during normal business hours. <br />11. One-year warranty. <br /> <br />DocuSign Envelope ID: FE7B6577-D8C8-4F5E-A6E1-82EE5E4625B7
The URL can be used to link to this page
Your browser does not support the video tag.