ORANGE COUNTY 262816-3 <br /> <br />Emergency Management Warehouse Building Dehumidification Enclosed Switches and Circuit Breakers <br /> <br /> <br /> <br />Coordinate electrical switches and circuit breakers installation work with electrical raceway and cable work, as 1 <br />necessary for proper interface. Coordinate exact location of switches with equipment electrical connection point. 2 <br /> 3 <br />Locate electrical switches and circuit breakers so that they are accessible after all project elements are 4 <br />installed. Location selected for switches must permit complete opening of the disconnect door or cover to 5 <br />the maximum amount permitted by the design of the switch enclosure. 6 <br /> 7 <br />Install electrical switches and circuit breakers for use with motor-driven appliances, and motors and controllers within 8 <br />sight of controller position unless otherwise indicated. 9 <br /> 10 <br /> 11 <br />GROUNDING 12 <br /> 13 <br />Provide equipment grounding connections, sufficiently tight to assure a permanent and effective ground, for electrical 14 <br />switches and circuit breakers. All electrical switches and circuit breakers shall be grounded by means of a separate 15 <br />insulated grounding conductor, run with the ungrounded conductors, and bonded to the disconnect enclosure by 16 <br />means of a dedicated grounding screw terminal or bus. 17 <br /> 18 <br /> 19 <br />FIELD QUALITY CONTROL 20 <br /> 21 <br />Subsequent to completion of installation of electrical switches and circuit breakers, energize circuitry and 22 <br />demonstrate capability and compliance with requirements. Where possible, correct malfunctioning units at project 23 <br />site, then retest to demonstrate compliance; otherwise remove and replace with new units and retest. 24 <br /> 25 <br /> 26 <br />END OF SECTION 262816 27 <br />DocuSign Envelope ID: 7668B866-6C26-485C-9A45-DAAB5D4BD951