Orange County NC Website
ORANGE COUNTY 260534-4 <br /> <br />Emergency Management Warehouse Building Dehumidification Raceways <br /> <br /> <br />Fasten heavy wall conduit terminations in sheet metal enclosures by two locknuts, one inside and one outside of 1 <br />enclosure, and terminate with insulated bushing; terminate other conduit systems with connectors listed for the 2 <br />purpose and as described above. 3 <br /> 4 <br />Conduit couplers shall be steel threaded type in all locations where such use is possible. Otherwise use 3-piece 5 <br />union. 6 <br /> 7 <br />Conduits are not to cross pipe shafts or ventilating duct openings. Conduit is not to be routed in elevator shafts 8 <br />unless necessary to serve items within the shaft. 9 <br /> 10 <br />Keep conduits a minimum distance of 6" from parallel runs of hot water pipes or other sources of heat. Wherever 11 <br />possible, install horizontal raceway runs above water piping. 12 <br /> 13 <br />Support riser conduit at each floor level with clamp hangers. 14 <br /> 15 <br />Use of running threads at conduit joints and terminations is prohibited. Where required, use threaded nipples and 16 <br />3-piece unions. 17 <br /> 18 <br />Support exposed conduit by use of hangers, clamps or clips Listed for the purpose. Support conduit on each side of 19 <br />bends and on spacing not to exceed following: 20 <br /> 21 <br />• Rigid Metal Conduits Up to 1": 8'-0". 22 <br />• Rigid Metal Conduits 1-1/4" and Over: 10'-0". 23 <br />• EMT Up to 1": 8'-0". 24 <br />• EMT 1-1/4" and Over: 10'-0". 25 <br /> 26 <br />Arrange conduit supports to prevent distortion of alignment by wire pulling operations. Fasten conduit using 27 <br />galvanized straps, lay-in adjustable hangers, clevis hangers, or bolted split stamped galvanized hangers Listed for 28 <br />the purpose. Requirements for exposed conduits also apply to conduits installed in space above hung ceilings. 29 <br /> 30 <br />Concealed Conduits: 31 <br /> 32 <br />• Metallic raceways installed underground, in floors below grade (where permitted), or outside are to 33 <br />have conduit threads painted with corrosion inhibiting compound before couplings are assembled. 34 <br />Draw up coupling and conduit sufficiently tight to ensure a water tight joint. 35 <br />• For floors-on-grade (where permitted), install conduits under crushed rock and concrete slabs. 36 <br />• Install underground conduits 24" below finished grade (24" cover) as a minimum or as otherwise 37 <br />indicated on the Drawings if a greater depth is shown. 38 <br /> 39 <br />Exposed Conduits: 40 <br /> 41 <br />• Install conduits in a manner so as not to damage or run through structural members. Avoid 42 <br />horizontal or cross runs in building partitions or side walls. 43 <br />• Install exposed conduits and extensions from concealed conduit systems neatly, parallel with, or at 44 <br />right angles to walls of building. 45 <br />• Install exposed conduit work as not to interfere with ceiling inserts, lights or ventilation ducts or 46 <br />outlets. Coordinate conduit installation with other trades as required. 47 <br />• Install exposed conduit directly on structure using two hole straps. Provide offsets at all boxes and 48 <br />as required to avoid exiting utilities. 49 <br />• Conduits installed on interior of exterior walls shall be spaced off the wall surface a minimum of ¼ 50 <br />inch with appropriate straps. 51 <br /> 52 <br />Run conduits for outlets on waterproof walls exposed where indicated on the Drawings. Set anchors for 53 <br />supporting conduit on waterproof wall in waterproof cement. Requirements for exposed conduit also apply to 54 <br />conduits installed in space above hung ceilings. 55 <br /> 56 <br />Raceway Fittings: Install connectors, couplers, and related fittings as required for a complete raceway system. 57 <br /> 58 <br />Install insulated bushings for terminating all types of raceway where termination is not made with an 59 <br />insulated throat connector. 60 <br />61 <br />DocuSign Envelope ID: 7668B866-6C26-485C-9A45-DAAB5D4BD951