Orange County NC Website
ORANGE COUNTY 260519-5 <br /> <br />Emergency Management Warehouse Building Dehumidification Secondary Voltage Wires and Cables <br /> <br /> <br /> <br />Terminate spare conductors with electrical tape. 1 <br /> 2 <br /> 3 <br />FIELD QUALITY CONTROL 4 <br /> 5 <br />Prior to energizing circuitry, check installed wires and cables with megohm meter to determine insulation resistance 6 <br />levels to insure requirements are fulfilled. Provide additional testing as directed by the A-E in accordance with 7 <br />Section 260800, TESTING AND PLACING IN SERVICE. 8 <br /> 9 <br />Prior to energizing circuitry, test wires and cables for electrical continuity and for short circuits. Verify proper phasing 10 <br />connections. 11 <br /> 12 <br />Subsequent to wire and cable hook-ups, energize circuitry and demonstrate functioning in accordance with 13 <br />requirements. Where necessary, correct malfunctioning units, and then retest to demonstrate compliance. 14 <br /> 15 <br /> 16 <br />END OF SECTION 260519 17 <br />DocuSign Envelope ID: 7668B866-6C26-485C-9A45-DAAB5D4BD951