ORANGE COUNTY 230923-2
<br />
<br />Emergency Management Warehouse Building Dehumidification Extension of Existing Direct Digital
<br /> Control System for HVAC
<br />
<br />Product Data: Include manufacturer's technical literature for each control device. Indicate dimensions, 1
<br />capacities, performance characteristics, electrical characteristics, finishes for materials, and installation and 2
<br />startup instructions for each type of product indicated. 3
<br /> 4
<br />DDC System Hardware: Bill of materials of equipment indicating quantity, manufacturer, model number, and 5
<br />other relevant technical data. Include technical data for operator workstation equipment, interface equipment, 6
<br />control units, communicating thermostats, transducers/ transmitters, sensors, actuators, valves, relays/switches, 7
<br />control panels, operator interface equipment, etc. 8
<br /> 9
<br />DDC System Software: 10
<br /> 11
<br />Include technical data for operating system software, operator interface, color graphics, and other third-12
<br />party applications. 13
<br /> 14
<br />List of graphics indicating monitored systems, data (connected and calculated) point addresses, output 15
<br />schedule, and operator notations. 16
<br /> 17
<br />Controlled Systems: 18
<br /> 19
<br />Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of 20
<br />field assembly, components, and location and size of each field connection. 21
<br /> 22
<br />Bill of materials of equipment indicating quantity, manufacturer, and model number for each controlled 23
<br />system 24
<br /> 25
<br />Schematic diagrams of each controlled system with control points labeled and control elements 26
<br />graphically shown, with wiring and termination labels. 27
<br /> 28
<br />Details of control panel faces, including controls, instruments, and labeling. 29
<br /> 30
<br />Written sequences of operation. The sequence shall include reference to schematic diagram(s) that 31
<br />is/are applicable. Include "on/off" and "occupied/unoccupied" schedules, as applicable for each 32
<br />controlled system. 33
<br /> 34
<br />Schedule of software interlocks between HVAC equipment or components. Include any "groupings" of 35
<br />controlled systems that may be used to initiate on/off control of any other controlled system. 36
<br /> 37
<br />Schedule of dampers including size, leakage, and flow characteristics. 38
<br /> 39
<br />Schedule of valves including flow characteristics. 40
<br /> 41
<br />DDC System Hardware: 42
<br /> 43
<br />Wiring diagrams for control units and communicating thermostats, with termination numbers. 44
<br /> 45
<br />Schematic diagrams and floor plans for field sensors and control hardware. 46
<br /> 47
<br />Schematic diagrams for control, communication, and power wiring, showing trunk data 48
<br />conductors and wiring between operator workstation and control unit locations. 49
<br /> 50
<br />Scaled drawings showing mounting, routing, and wiring of elements including bases and 51
<br />special construction. 52
<br /> 53
<br />Graphic Displays: Include color prints or "screen shots" of each proposed graphic display proposed, complete 54
<br />with clear indication of (1) static components and dynamic components and (2) "on"/"off"/"alarm" condition 55
<br />designation convention. 56
<br /> 57
<br />Samples for Initial Selection: For each color available for each type of thermostat, sensor, etc. cover exposed to 58
<br />view with factory-applied color finishes. 59
<br /> 60