Orange County NC Website
ORANGE COUNTY 230913-4 <br /> <br />Emergency Management Warehouse Building Dehumidification Instrumentation and Control <br /> Devices for HVAC <br /> <br />Temperature Sensors: 1 <br /> 2 <br />Install all sensors and instrumentation according to manufacturer’s written instructions. Temperature sensor 3 <br />locations shall be readily accessible, permitting quick replacement and servicing of them without special 4 <br />skills and tools. 5 <br /> 6 <br />All wires attached to sensors shall be air sealed in their conduits or in the wall to stop air transmitted from 7 <br />other areas affecting sensor reading. 8 <br /> 9 <br />Actuators: 10 <br /> 11 <br />Mount damper and valve actuators according to manufacturer’s written instructions. 12 <br /> 13 <br />Damper actuators shall be located outside of the airstream. 14 <br /> 15 <br />Check operation of damper/actuator combination to confirm that actuator modulates damper smoothly 16 <br />throughout stroke to both open and closed position. 17 <br /> 18 <br />Check operation of valve/actuator combination to confirm that actuator modulates valve smoothly in both 19 <br />open and closed position. 20 <br /> 21 <br /> 22 <br />FIELD TEST AND INSPECTIONS 23 <br /> 24 <br />Upon completion of installation of each sensor or final control element, field inspect and mechanically and electrically 25 <br />test for proper function. 26 <br /> 27 <br /> 28 <br />OWNER INSTRUCTION AND TRAINING 29 <br /> 30 <br />Provide Owner instruction and training in accordance with Section 019926. 31 <br /> 32 <br /> 33 <br />END OF SECTION 230913 34 <br />DocuSign Envelope ID: 7668B866-6C26-485C-9A45-DAAB5D4BD951