Orange County NC Website
ORANGE COUNTY 230517 - 2 <br /> <br />Emergency Management Warehouse Building Dehumidification Sleeves and Sleeve Seals for HVAC Piping <br /> <br /> <br />PART 3 - EXECUTION 1 <br /> 2 <br /> 3 <br />SLEEVE AND SLEEVE-SEAL APPLICATIONS 4 <br /> 5 <br />Use sleeves and sleeve seals for the following piping-penetration applications: 6 <br /> 7 <br />Penetration <br />Application <br />Sleeve <br />Type <br />Sleeve Seal <br />Required <br />Exterior walls above grade Cast Iron Yes <br />Exterior walls below grade Cast Iron Yes <br />Concrete slab on grade Cast Iron Yes <br />Concrete slab above grade Black Steel Pipe No <br />Interior partitions, fire-rated Black Steel Pipe No <br />Interior partitions, non-fire-rated Black Steel Pipe or <br />Galvanized Sheet <br />Metal Sleeve <br />No <br /> 8 <br /> 9 <br />SLEEVE INSTALLATION 10 <br /> 11 <br />Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls. 12 <br /> 13 <br />Sleeves are not required for core-drilled holes. Install sleeves in concrete floors, concrete roof slabs, and concrete 14 <br />walls as new slabs and walls are constructed. 15 <br /> 16 <br />Cut sleeves to length for mounting flush with both surfaces. 17 <br /> 18 <br />Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches 19 <br />above finished floor level. 20 <br /> 21 <br />Using grout, seal the space outside of sleeves in slabs and walls without sleeve-seal system. 22 <br /> 23 <br />Install sleeves for pipes passing through interior partitions. Cut sleeves to length for mounting flush with both surfaces 24 <br />and install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe 25 <br />insulation. 26 <br /> 27 <br />For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide 1-inch annular 28 <br />clear space between piping and concrete slabs and walls. 29 <br /> 30 <br />Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with 31 <br />firestop materials. Comply with requirements for firestopping specified in Section 019913. 32 <br /> 33 <br /> 34 <br />SLEEVE-SEAL-SYSTEM INSTALLATION 35 <br /> 36 <br />Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into 37 <br />building. 38 <br /> 39 <br />Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. 40 <br />Position piping in center of sleeve. Center piping in penetration, assemble sleeve-seal system components, and in-41 <br />stall in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements 42 <br />to expand and make a watertight seal. 43 <br /> 44 <br /> 45 <br />46 <br />DocuSign Envelope ID: 7668B866-6C26-485C-9A45-DAAB5D4BD951