Orange County NC Website
8/28/2020 Print : Quotebuilder : ServiceTrade <br />https://app.servicetrade.com/quotebuilder/print/id/1252752 2/4 <br />[Sprinkler] Main Drain Valve - A Bldg. 2nd Floor <br />PAINTED FIRE SPRINKLER HEADS: (2) <br />(2) Painted Sidewall at left and right entrance room 235 conference <br />1/2” 155* White K=5.6 <br />[Sprinkler] Location - Building <br />MISSING SPARE FIRE SPRINKLER HEADS IN THE SPARE HEADBOX: (4) <br />MISSING FIRE SPRINKLER HEAD WRENCH IN THE SPARE HEADBOX: (3) <br />The spare headbox is missing wrenches for spare heads - 1/2" Tyco TY3131 upright, 3/4" TFP pendant, and Victaulic V 2708 <br />Missing (4) Spare heads in the spare headbox <br />(3) Victaulic V2708 white pendant <br />(1) Tyco TY3131 brass upright <br />[Sprinkler] Dry Sprinkler - RISER ROOM - UNDER STAIRCASE - DRY SYSTEM <br />AIR COMPRESSOR SWITCH IS NOR WORKING PROPERLY: <br />Updated 6.29.20 - Tankless Air Compressor Switch is not working properly. Had to tap it to cut off. <br />Need to replace. It controls the Dry System Air. <br />Condor MDR 11/6 <br />PAT NO 198 08 559 <br />[Sprinkler] Main Drain Valve - A Bldg. 1st Floor <br />NO HYDRAULIC NAME-PLATES ATTACHED TO RISERS <br />NOTE: No hydraulic data plate on the fire sprinkler system. (Customer will need an engineer survey of the building and a complete drawing with <br />calculations to replace the data plates. Let us know if you would like a quote.) <br />Missing Hydraulic Calibration Plates on riser manifolds for the 1st, 2nd, and 3rd Floor Stairwell. <br />[Sprinkler] Location - Building <br />NO HYDRAULIC NAME-PLATES ATTACHED TO RISERS <br />NOTE: No hydraulic data plate on the fire sprinkler system. (Customer will need an engineer survey of the building and a complete drawing with <br />calculations to replace the data plates. Let us know if you would like a quote.) <br />Updated 6.29.20 - No hydraulic nameplates attached to the riser <br />Engineer to survey <br />[Sprinkler] Dry Sprinkler - RISER ROOM - UNDER STAIRCASE - DRY SYSTEM <br />NO HYDRAULIC NAME-PLATES ATTACHED TO RISERS <br />NOTE: No hydraulic data plate on the fire sprinkler system. (Customer will need an engineer survey of the building and a complete drawing with <br />calculations to replace the data plates. Let us know if you would like a quote.) <br />Updated 6.29.20 - No hydraulic nameplates attached to the riser <br />Engineer to survey <br />Parts, labor, and fees Quantity Unit Price Tax Total <br />SUB TOTAL $7191.00 <br />TAX @ 7.5%$539.33 <br />GRAND TOTAL $7730.33 <br />Perform NFPA-25 code required 5-Year internal wet pipe and alarm valve obstruction investigation 5 $775.00 $290.63 $3875.00 <br />Perform NFPA-25 code required 5-Year internal dry pipe and dry valve obstruction investigation 1 $775.00 $58.13 $775.00 <br />DocuSign Envelope ID: F3A3E126-E516-42D3-A7D4-020878A9D80B