GENERAL NOTES: <br />A. CONTROLS PROVIDED BY CONTROLS CONTRACTOR AND SHALL BE FACTORY INSTALLED <br />BY THE VAV BOX MANUFACTURER. PROVIDE SHEET METAL ENCLOSURE FOR CONTROLS. <br />B. THERMOSTATS SHALL HAVE ADJUSTMENT AND A TIMED OVERRIDE BUTTON - TWO(2) <br />HOUR MAX. <br />C. DIVISION 23 SHALL COORDINATE LOCATION OF VAV BOXES WITH ALL OTHER DISCIPLINES <br />TO ENSURE THAT VAV BOXES CAN BE EASILY SERVICED. DIVISION 23 SHALL BE <br />RESPONSIBLE FOR REROUTING OR RELOCATING THE BOXES. <br />D. EQUIVALENTS LISTED IN SPECIFICATIONS. <br />E. BOXES SHALL BE 120 VOLT. COORDINATE WITH DIVISION 26. PROVIDE A 24/120V <br />TRANSFORMER TO POWER CONTROLS. MANUFACTURER SHALL PROVIDE A MOTOR- <br />RATED DISCONNECT SWITCH FOR EACH VAV BOX. <br />F. PIPING CONNECTIONS AND CONTROLS ENCLOSURE SHALL BE ON SAME SIDE. HOT <br />WATER SUPPLY CONNECTION SHALL BE AT BOTTOM INLET POSITION (COUNTERFLOW <br />CONFIGURATION). <br />GENERAL NOTES: <br />A. EQUALS BY TUTTLE AND BAILEY, NAILOR, OR AS LISTED IN SPECIFICATIONS. <br />B. PROVIDE VOLUME DAMPERS AT TAKE-OFF FOR EACH GRILLE. <br />C. THE PRICE MODELS SCHEDULED HERE ARE BASIS OF DESIGN. INCLUDING <br />GENERATED NOISE. PROPOSED SUBSTITUTIONS WILL BE JUDGED BY THOSE <br />CRITERIA ALSO. <br />REMARKS: <br />1. SUPPLY WITH OFF-WHITE ENAMEL FINISH. <br />2. SUPPLY WITH TRIM TO MATCH CEILING TYPE. <br />3. PROVIDE GRILLE WITH ROUND NECK OR SUPPLY SQUARE-TO-ROUND TRANSITION. <br />4. ALL CEILING MOUNTED RETURN GRILLES SHALL BE FULL-FACED. NO LAY IN PANELS ALLOWED. <br />REINFORCEMENT MAY BE USED FOR ATTACHMENT <br />IF IT QUALIFIES FOR BOTH DUTIES. <br />DO NOT EXCEED LOAD RATINGS FOR METHOD USED. <br />FROM SMACNA DUCT STANDARDS <br />TRAPEZE HANGERS <br />1. <br />2. <br />NOTES: <br />ROUND DUCT SUPPORTSTRAP HANGERS <br />HANGERS FOR <br />STACKED DUCT <br />3" <br />12" <br />1" MINIMUM <br />MAXIMUM <br />SPACING <br />ROD <br />NUTS <br />ANGLES <br />ALTERNATE <br />LOCATION <br />HANGER STRAP <br />SLING - AVOID <br />DISRUPTION <br />OF INSULATION <br />LOAD RATED <br />FASTENERS <br />(TYPICAL) <br />BAND OF SAME SIZE <br />AS HANGER STRAP <br />HANGER RODS <br />OR STRAPS <br />BAND <br />SCREWS <br />(TYPICAL) <br />HANGER STRAPROD <br />STRAP OR ANGLE <br />SIZE BOLT(S) <br />FOR LOAD <br />* A COMBINATION STARTER SHALL BE USED IN LIEU OF A SEPARATE <br /> DISCONNECT SWITCH AND STARTER, WHERE AVAILABLE. <br />PANELBOARD <br />J <br />BRANCH CIRCUIT AND CONDUIT IN ELECTRICAL WORK. <br />SEE PANELBOARD SCHEDULES FOR WIRE AND BREAKER <br />SIZES TO HVAC AND PLUMBING EQUIPMENT <br />JUNCTION BOX MAY BE SHOWN ON <br />ELECTRICAL PLANS FOR SOME <br />EQUIPMENT (NOT NECESSARY <br />IF WIRING IS CONNECTED DIRECTLY <br />TO STARTER OR DISCONNECT SWITCH) <br />WIRING IN ELECTRICAL WORK <br />EXTERNALLY OR INTERNALLY MOUNTED <br />DISCONNECT SWITCH FURNISHED BY <br />HVAC OR PLUMBING CONTRACTOR, <br />OR OTHER TRADES AND INSTALLED <br />BY THE ELECTRICAL CONTRACTOR. <br />CONTROL CONNECTIONS BY OTHERS. <br />EXTERNALLY MOUNTED STARTER <br />FURNISHED BY HVAC OR PLUMBING <br />CONTRACTOR OR OTHER TRADES, <br />INSTALLED BY THE ELECTRICAL <br />CONT. LINE AND LOAD CONNECTIONS <br />BY THE ELECTRICAL CONTRACTOR. <br />CONTROL CONNECTIONS BY OTHERS <br />WIRING IN ELECTRICAL WORK <br />EQUIPMENT IN HVAC OR PLUMBING WORK <br />OR WORK OF OTHER TRADES. SEE HVAC, <br />PLUMBING, AND ARCHITECTURAL PLANS <br />FOR LOCATION OF ALL EQUIPMENT <br />* <br />FINAL CONNECTIONS INSIDE EQUIPMENT TO <br />BE MADE BY THE HVAC OR PLUMBING <br />CONTRACTOR OR OTHER TRADES <br />LOW PRESSURE <br />SHEET METAL <br />FAN POWERED <br />TERMINAL UNIT <br />MEDIUM PRESSURE DUCTWORK. MINIMUM OF <br />THREE(3) FEET STRAIGHT DUCT PRIOR TO BOX. <br />THREADED RODS <br />TO STRUCTURE <br />NOTES: <br />MEDIUM PRESSURE <br />DUCTWORK <br />SUPPORT UNIT FROM THE STRUCTURE. <br />DO NOT MOUNT BOX OVER A LIGHT. <br />1. <br />2. <br />PROVIDE TAPERED TAKE-OFF WITH ADJUSTABLE VOLUME <br />DAMPER, AIR DISTRIBUTING GRID, OR RADIUS TAKE-OFF <br />WITH STRAIGHTENING VANES AT TAKE-OFF. <br />NOTE: <br />TAPERED TAKE-OFF <br />BUTTERFLY DAMPER <br />WITH LOCKING <br />QUADRANT <br />TAPERED TAKE-OFF <br />WITH ADJUSTABLE VOLUME <br />CONTROL DAMPER <br />CEILING GRID <br />SUPPLY AIR DIFFUSER <br />FLEXIBLE RUNOUT <br />(5 LINEAR FT. MAX., UNLESS <br />OTHERWISE NOTED.) <br />BRANCH <br />DUCT <br />EXTERNALLY INSULATE ROUND <br />SHEET METAL RUNOUT RECTANGULAR <br />DUCT <br />SUPPLY AND INSTALL <br />AN INSULATED METAL <br />ELBOW WHERE DUCT <br />CONNECTS TO DIFFUSER. <br />CUSHION HEAD <br />CUSHION HEAD = 1.5 x BRANCH DUCT WIDTH (MAXIMUM LENGTH 2'-0") <br />CUSHION HEAD <br />WIDTH OF <br />BRANCH <br />WIDTH OF <br />BRANCH <br />MANUAL BALANCING <br />DAMPER <br />WITH LOCKING DEVICE <br />(TYPICAL) <br />T 919 781 8582 <br />F 919 781 3979 <br />4600 Lake Boone Trail <br />Suite 205 <br />Raleigh, NC 27607 <br />info@smithsinnett.com <br />DRAWN BY: <br />CHECKED BY: <br />DESCRIPTIONDATEIDThis drawing and the design shown is the property of Smith Sinnett Architecture, P.A. the reproduction or use of this property without the written consent of the Architect is prohibited. Any infringement of the ownership rights will be subject to legal action. All copies of this drawing must be returned to the Architect at the completion of the contract.Smith Sinnett Architecture, P.A. 2020THIS DRAWING IS FORMATTED TO BE PRINTED ON A 24" X 36" SHEETPDC #20033 <br />C:\Users\chris.pdc\Documents\20033_OCC Europa_MEP_Central_Model_chrishoo.rvt5/20/2020 3:17:01 PMM2-01 <br />MECHANICAL <br />DETAILS AND <br />SCHEDULES <br />2020045 21 MAY 2020CONSTRUCTION DOCUMENTSAuthor <br />CheckerORANGE COUNTY, NCDSS SKILLS DEVELOPMENT CENTER100 Europa Dr Ste 190, Chapel Hill, NC 27517AIR DISTRIBUTION SCHEDULE <br />MARK MANUFACTURER MODEL PURPOSE MIN CFM MAX CFM FACE SIZE INLET SIZE REMARKS <br />B PRICE SCD SUPPLY 105 230 24x24 8" 1-4 <br />C PRICE SCD SUPPLY 235 375 24x24 10" 1-4 <br />R PRICE PDDR RETURN 0 1100 24x24 22x22 1-4 <br />FAN POWERED BOX SCHEDULE <br />MARK MANUFACTURER MODEL <br />INLET <br />SIZE MAX CFM <br />AIRFLOW HEATING COIL ELECTRIC COIL SOUND POWER <br />ELECTRICAL <br />REMARKS <br />MIN <br />CFM <br />MAX <br />HTG <br />APD IN. <br />WG CAPACITY (MBH) EAT (°F) LAT (°F) KW V PH <br />STAG <br />ES DISC RAD <br />FPB1-13 TITUS DTQP 10 1050 300 637 0.22 37.5 70 90 11 480 3 1 24 28 0.5 HP / 21.7 MCA / 25 MOCP <br />FPB1-14 TITUS DTQP 08 540 300 435 0.14 18.8 70 90 5.5 480 3 1 21 32 0.5 HP / 13.4 MCA / 15 MOCP <br />NOT TO SCALE <br />DETAIL -TYPICAL DUCT HANGERS5 <br />NOT TO SCALE <br />DETAIL -TYPICAL EQUIPMENT CONNECTIONS4 <br />NOT TO SCALE <br />DETAIL -FAN POWERED TERMINAL UNIT3 <br />NOT TO SCALE <br />DETAIL -SUPPLY, RETURN & EXHAUST AIR TAKE-OFF2 <br />NOT TO SCALE <br />DETAIL -CUSHION HEAD DETAIL1 <br />05/20/2020 <br />DocuSign Envelope ID: ECCAC5A0-6CC8-4B37-8AD3-89D69F0AE1AE