Orange County NC Website
Construction Documents <br />20033 <br />Orange County Europa Center <br />23 3600 - 2 AIR TERMINAL UNITS <br />E.Controls: <br />1.Electric: <br />a.Wall-mounted electric thermostat including 24 volt damper actuator and mounting <br />hardware. <br />b.See Section 25 3516. <br />2.Control Sequence: See Section 23 0993. <br />PART 3 EXECUTION <br />3.01 EXAMINATION <br />A.Verify that conditions are suitable for installation. <br />B.Verify that field measurements are as indicated on drawings. <br />3.02 INSTALLATION <br />A.Install in accordance with manufacturer's instructions. <br />B.Install the inlets of air terminal units and air flow sensors a minimum of four duct diameters from <br />elbows, transitions, and duct takeoffs. <br />C.Provide ceiling access doors or locate units above easily removable ceiling components. <br />D.Support units individually from structure with wire rope complying with ASTM A492 and ASTM <br />A603 in accordance with SMACNA (SRM). See Section 23 0548. <br />E.Do not support from ductwork. <br />F.Connect to ductwork in accordance with Section 23 3100. <br />END OF SECTION 23 3600 <br />DocuSign Envelope ID: ECCAC5A0-6CC8-4B37-8AD3-89D69F0AE1AE