WARREN - HAY
<br />Mechanical Contractors Inc.
<br />Heating and Air Conditioning
<br />P.O. Box 818 • Hillsborough, NC 27278
<br />919-732-4362
<br />NC License number 07211 H-1; H-2; H3
<br />
<br /> August 18, 2020
<br />Orange County Public Works
<br />
<br />Re: Southern Human Service – Boiler
<br />PROPOSAL
<br /> We hereby submit specifications and estimates for: As requested:
<br />Option #1
<br />• Provide & install (1) Hot water condensing boiler option M#FBN1251 - Lochnivar Crest Condensing Boiler
<br />natural gas fired with 1,250,000 Btu/Hr input, 1,203,000 Btu/Hr output. Condensing design with 96.2% AHRI
<br />Thermal Efficiency, 20:1, Turndown, ASME Stainless Steel HX, 316L SS Fire Tubes, ASME relief valve 1648,
<br />Condensate Neutralization Kit, Step Down Gas Regulator.
<br />• Reconnecting to existing piping, pumps, power wiring, & controls.
<br />• Secure permit and required Orange county Inspections.
<br />We propose hereby to furnish material and labor: $54,575.00
<br />Option #2
<br />• Provide & install (1) Hot water Non condensing boiler option CHN1442-M9 - Lochnivar Copper-Fin II natural
<br />gas Boiler with 1,440,000 Btu/Hr input, 1,224,000 Btu/Hr output. ASME Copper Finned Heat Exchanger
<br />rated for 160 psi. Fan assisted combustion, 85% thermal efficiency, 50 psi ASME pressure relief valve Step
<br />down Gas Regulator, Low Temperature Protection Valve, Automatic.
<br />• Reconnecting to existing piping, pumps, power wiring, & controls.
<br />• Secure permit and required Orange county Inspections.
<br />We propose hereby to furnish material and labor: $48,289.00
<br />Option #3
<br />• Provide & install Centrifugal Pumps Tag: P-1-2, E1510-1.5BC-184T-S - B&G Base Mounted Pump Series e-
<br />1510, Model 1.5 BC, SS, 5 HP, 1800 RPM, 184T Frame, with 8.375" Impeller, STD-
<br />Buna/Carbon/Ceramic/SS/Bronze Seal, Galvanized Steel Drip Pan, BG Choice, ODP, Nema Premium Efficient,
<br />208-230/460/3/60 Motor, 106 GPM, 70 FT TDH 436 2 115114 - B&G BB-3X Suction Diffuser Plus 2 IN. NPT x
<br />2 IN. NPT 28 2 B&G 3DS-2S Triple Duty Valve Straight Pattern 2 In. 48 non-fused combo starter, 2hp-5hp
<br />460/3 3-9AMP, W/120V TX HOA & Pilot lights, Nema 1
<br />• Reconnecting to existing piping, pumps, power wiring, & controls.
<br />• Secure permit and required Orange county Inspections.
<br />We propose hereby to furnish material and labor: $21,480.00
<br />Payment to be made upon completion.
<br />Exclusions / Clarifications:
<br />• Any control work or upgrade to controls system by 3rd party. We will remove and reinstall existing
<br />controls to new options only. Any updating, etc, commissioning or verification by others.
<br />• After hour, overtime premium labor, expedited shipment:
<br />Option #1 Current lead time 6-8 weeks.
<br />Option #2 Current lead time 10 – 14 days.
<br />Option #3 Current lead time 3-4 weeks.
<br />Respectfully submitted by: Ron LaPann Commercial Division ron.lapann@warren-hay.com Quote valid for 20 days.
<br />DocuSign Envelope ID: 4614BE98-529B-4741-9D3D-96E7B76C2F30
|