Southern Human Services Center Smith Sinnett /2020072 <br />HVAC and Roof Renovations Orange County,North Carolina <br />VAV PACKAGED DX RTU 23 74 00 - 5 <br />8.Lead refrigeration circuit shall be provided with hot gas reheat coil,modulating valves, <br />electronic controller,supply air temperature sensor and a control signal terminal which allow <br />the unit to have a dehumidification mode of operation,which includes supply air temperature <br />control to prevent supply air temperature swings and overcooling of the space. <br />9.Unit shall be configured as an air-source heat pump.Each refrigeration circuit shall be <br />equipped with a factory installed liquid line filter drier with check valve,reversing valve, <br />accumulator,and expansion valves on both the indoor and outdoor coils.Reversing valve <br />shall energize during the heat pump cooling mode of operation. <br />L.Condensers <br />1.Air-Cooled Condenser <br />a.Condenser fans shall be a vertical discharge,axial flow,direct drive fans. <br />b.Coils shall be designed for use with R-410A refrigerant.Coils shall be multi-pass and <br />fabricated from aluminum microchannel tubes. <br />c.Heat pump outdoor coil shall be constructed of copper tubes with aluminum fins <br />mechanically bonded to the tubes and aluminum end casings.Fin design shall be sine <br />wave rippled. <br />d.Coils shall be designed for a minimum of 10°F of refrigerant sub-cooling. <br />e.Coils shall be hydrogen or helium leak tested. <br />f.Condenser coils shall include corrosion-resistant,electrostatically-applied coating rated <br />for 5,000 hours in accordance with ASTM B117. <br />g.Condenser fans shall be high efficiency electrically commutated motor driven with factory <br />installed head pressure control module.Condenser airflow shall continuously modulate <br />based on head pressure and cooling operation shall be allowed down to 35°F with <br />adjustable compressor lockout. <br />h.Condenser fans shall be VFD driven variable speed for condenser head pressure <br />control. Factory provided and factory programmed VFDs shall continuously modulate <br />the fan air flow to maintain head pressure at acceptable levels.Cooling operation shall <br />be allowed down to 35°F with adjustable compressor lockouts. <br />M.Filters <br />1.Outdoor air hood shall have a aluminum mesh filter section. <br />2.Unit shall include 2 inch thick,pleated panel filters with an ASHRAE efficiency of 30%and <br />MERV rating of 13,upstream of the cooling coil. <br />3.Unit shall include 0-100%economizer consisting of a motor operated outside air damper and <br />return air damper assembly constructed of extruded aluminum,hollow core,airfoil blades with <br />rubber edge seals and aluminum end seals.Damper blades shall be gear driven and <br />designed to have no more than 20 cfm of leakage per sq ft.at 4 in.w.g.air pressure <br />differential across the damper.Low leakage dampers shall be Class 2 AMCA certified,in <br />accordance with AMCA Standard 511.Damper assembly shall be controlled by spring return <br />enthalpy activated fully modulating actuator.Unit shall include outside air opening bird <br />screen,outside air hood,and barometric relief dampers. <br />4.Economizer shall be furnished with return air CO2 override. <br />N.Controls <br />1.Factory Installed Controller <br />a.The unit shall come with a factory programmed and supplied controller that provide all <br />programming and functionality for the unit to operate,including internal safeties. <br />b.All sensors required for the operation of the unit shall be factory furnished.This includes <br />outside air temperature and humidity sensors,supply air temperature and humidity <br />sensors,coil suction pressure and temperature sensors,space temperature and <br />humidity sensors,preheat discharge temperature sensor,and other sensors as required <br />to implement the sequence of operations.Refer to sequence on Drawings. <br />O.Accessories <br />1.Unit shall be provided with a smoke detector in the supply of the unit,wired to shut off the <br />unit’s control circuit. <br />2.03 CURBS <br />A.Refer to Vibration and Isolation Section. <br />DocuSign Envelope ID: 94E7997D-4F29-42F6-A9B4-0A160438D2A6