Southern Human Services Center Smith Sinnett /2020072 <br />HVAC and Roof Renovations Orange County,North Carolina <br />Air Terminal Units 23 36 00 - 1 <br />SECTION 23 36 00 <br />AIR TERMINAL UNITS <br />PART 1 GENERAL <br />1.01 SECTION INCLUDES <br />A.Single-duct terminal units. <br />1.02 REFERENCE STANDARDS <br />A.AHRI 410 -Forced-Circulation Air-Cooling and Air-Heating Coils 2001,with Addendum (2011). <br />B.AHRI 880 (I-P)-Performance Rating of Air Terminals 2017. <br />C.ASHRAE Std 130 -Methods of Testing Air Terminal Units 2016. <br />D.ASTM C1071 -Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and <br />Sound Absorbing Material)2019. <br />E.NFPA 70 -National Electrical Code Most Recent Edition Adopted by Authority Having Jurisdiction, <br />Including All Applicable Amendments and Supplements. <br />F.NFPA 90A -Standard for the Installation of Air-Conditioning and Ventilating Systems 2018. <br />G.SMACNA (SRM)-Seismic Restraint Manual Guidelines for Mechanical Systems 2008. <br />H.UL 181 -Standard for Factory-Made Air Ducts and Air Connectors current edition,including all <br />revisions. <br />1.03 SUBMITTALS <br />A.Product Data: Provide data indicating configuration,general assembly,and materials used in <br />fabrication. Include catalog performance ratings that indicate air flow,static pressure,and NC <br />designation. Include electrical characteristics and connection requirements. <br />B.Shop Drawings: Indicate configuration,general assembly,and materials used in fabrication,and <br />electrical characteristics and connection requirements. <br />1.Include schedules listing discharge and radiated sound power level for each of second <br />through sixth octave bands at inlet static pressures of 1 to 4 inch wg. <br />C.Project Record Documents: Record actual locations of units and locations of access doors <br />required for access of valving. <br />D.Operation and Maintenance Data: Include manufacturer's descriptive literature,operating <br />instructions,maintenance and repair data,and parts lists. Include directions for resetting constant- <br />volume regulators. <br />E.Warranty: Submit manufacturer warranty and ensure forms have been completed in Owner's <br />name and registered with manufacturer. <br />1.04 QUALITY ASSURANCE <br />A.Manufacturer Qualifications: Company specializing in manufacturing the type of products specified <br />in this section,with minimum eight years of documented experience. <br />B.Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally <br />Recognized Testing Laboratory (NRTL)and acceptable to authorities having jurisdiction. <br />1.05 WARRANTY <br />A.See Section 01 78 00 -Closeout Submittals,for additional warranty requirements. <br />PART 2 PRODUCTS <br />2.01 SINGLE-DUCT,VARIABLE-VOLUME UNITS <br />A.Manufacturers: <br />1.Carrier,a part of UTC Building and Industrial Systems,a unit of United Technologies Corp. <br />2.Johnson Controls,Inc <br />3.Krueger-HVAC <br />4.Metalaire,a brand of Metal Industries Inc <br />5.Nailor <br />DocuSign Envelope ID: 94E7997D-4F29-42F6-A9B4-0A160438D2A6