Orange County NC Website
Construction Documents <br />20052 / Orange County - Court Street <br />Annex <br />23 3700 - 2 AIR OUTLETS AND INLETS <br />2.06 WALL SUPPLY REGISTERS/GRILLES <br />A.Type: Streamlined and individually adjustable blades, 3/4 inch (19 mm) minimum depth, 3/4 <br />inch (19 mm) maximum spacing with spring or other device to set blades, vertical face, single <br />deflection. <br />B.Fabrication: Steel with 20 gage, 0.0359 inch (0.91 mm) minimum frames and 22 gage, 0.0299 <br />inch (0.76 mm) minimum blades, steel and aluminum with 20 gage, 0.0359 inch (0.91 mm) <br />minimum frame, or aluminum extrusions, with factory baked enamel finish. <br />C.Color: As indicated. <br />2.07 DOOR GRILLES <br />A.Frame: 20 gage, 0.0359 inch (0.91 mm) steel with auxiliary frame to give finished appearance <br />on both sides of door, with factory prime coat finish. <br />PART 3 EXECUTION <br />3.01 INSTALLATION <br />A.Install in accordance with manufacturer's instructions. <br />B.Check location of outlets and inlets and make necessary adjustments in position to comply with <br />architectural features, symmetry, and lighting arrangement. <br />C.Install diffusers to ductwork with air tight connection. <br />END OF SECTION 23 3700 <br />DocuSign Envelope ID: 09980A3B-0691-41B4-854D-3865F2287392