Orange County NC Website
Construction Documents <br />20052.02 / Orange County - Justice <br />Facility <br />28 4600 - 7 FIRE DETECTION AND ALARM <br />b. Door hold open magnets shall be furnished with keepers, door chains, and other <br />accessories as required to properly hold open doors as indicated on the Drawings. <br />c. Wall mounted magnetic door holders and separate heavy duty closers shall be used <br />instead of combination door control units. <br />d. Holding force of the magnet shall be appropriate for the door to be held open. Door <br />hold open magnets shall operate in a fail safe manner, i.e., the door shall release in <br />event of a failure of voltage to the device. <br />e. Power Source: Door hold open magnets shall be configured to operate from a <br />nominal 24 VDC system as supplied by the FACP or other power supply listed for the <br />purpose. <br />f. All hold open magnet supply sources, whether a part of the FACP or whether derived <br />from a separate power supply, shall be supervised. <br />g. Door hold open magnet circuits which use step-down transformers, 120 VAC, or local <br />relays are not permitted. <br />h. Door shall close after 60 seconds of the power loss. <br />9. Battery Power Supply (BPS) &/or Supplementary Notification Appliance Circuit (SNAC): <br />These types of panels shall be completely maintenance free, shall not require liquids, fluid <br />level checks or refilling, and shall not be capable of producing spills and/or leaks. Batteries <br />shall be sealed gel-cell type with expected life of 10 years. Battery voltage shall be as <br />required by the FACP and related equipment. Battery shall have sufficient capacity to <br />power the fire alarm system for not less than 60 hours plus 15 minutes of alarm upon a <br />normal AC power failure. Battery cabinet shall be twice the size of the batteries it will <br />contain. NAC circuits shall not exceed 75% of maximum current load allowed. <br />a. The voltage drop at EOL must not exceed 14% of the expected battery voltage after <br />the required standby and alarm times. Determine worst case voltage at far end of <br />each NAC circuit. The results must not be than the minimum listed rating on the <br />device. <br />b. Where voltage drop or capacity limits are exceeded provide additional NAC panels as <br />required for a fully functional system. <br />c. All power supplies shall be capable of withstanding prolonged short circuits in the field <br />wiring, either line-to-line or line-to-ground, without damage. <br />d. All power supplies shall be equipped with battery charging using dual-rate charging <br />techniques for fast battery recharge. <br />10. Enclosure: All equipment enclosures shall be third party listed suitable for surface or <br />semi-flush mounting. Cabinet and front shall be corrosion resistant, given a rust-resistant <br />prime coat, and manufacturer's standard finish. The door shall provide a key lock and a <br />glass opening for viewing indicators. Door hinge shall be field selectable (left or right). <br />E. Wiring <br />1. Addressable loop (signaling line) circuits shall be wired with type FPL/FPLR/FPLP fire <br />alarm cable, AWG 18 minimum, low capacitance, twisted shielded copper pair. Cable <br />shield drain wires are to be connected at each device on the loop to maintain continuity, <br />taped to insulate from ground, and terminated at the FACP. Acceptable cables include <br />Atlas 228-18-1-1STP, BSCC S1802s19 (same as EEC 7806LC), West Penn D975, D991 <br />(AWG 16), D995 (AWG 14), or equal wire having capacitance of 30pf/ft. maximum <br />between conductors. Belden 5320FJ acceptable if only FPL rating needed. <br />a. Unshielded cable, otherwise equal to the above, is permitted to be used if the <br />manufacturer’s installation manual requires, or states preference for, unshielded <br />cable. <br />b. In underground conduit, use Type TC or PLTC cable (PE insulated) to avoid problems <br />from moisture. <br />c. The following conductor color coding shall be maintained throughout the system: <br />1) Initiating Circuits: Red (+)/White (-) <br />2) Initiating Circuits, Smoke Only: Violet (+)/Grey (-) <br />3) Signal Line Circuits: Red jacket with Red (+)/Black(-) <br />4) Alarm Indicating Appliance Circuits: Blue (+)/Black(-) <br />DocuSign Envelope ID: 09980A3B-0691-41B4-854D-3865F2287392