Orange County NC Website
Construction Documents <br />20052.02 / Orange County - Justice <br />Facility <br />27 1000 - 2 STRUCTURED CABLING <br />B.Correct defective Work within a 2 year period after Date of Substantial Completion. <br />PART 2 PRODUCTS <br />2.01 SYSTEM DESIGN <br />A.Provide a system of cabling and pathways for voice and data communications, including cables, <br />conduits and wireways, pull wires, support structures, and outlets. <br />1.Provide fixed cables and pathways that comply with NFPA 70 and TIA-607 and are UL <br />listed or third party independent testing laboratory certified. <br />2.Provide connection devices that are rated for operation under conditions of 32 to 140 <br />degrees F (0 to 60 degrees C) at relative humidity of 0 to 95 percent, noncondensing. <br />3.In this project, the term plenum is defined as return air spaces above ceilings, inside ducts, <br />under raised floors, and other air-handling spaces. <br />B.Cabling to Outlets: Specified horizontal cabling, wired in star topology to distribution frame <br />located at center hub of star; also referred to as "links". <br />2.02 COPPER CABLE AND TERMINATIONS <br />A.Manufacturers: <br />1.CommScope; ________: www.commscope.com/#sle. <br />2.General Cable Technologies Corporation; ________: www.generalcable.com/#sle. <br />3.Siemon Company; ________: www.siemon.com/#sle. <br />4.Or approved equal. <br />B.Copper Horizontal Cable: <br />1.Description: 100 ohm, balanced twisted pair cable complying with TIA-568.2 and listed <br />and labeled as complying with UL 444. <br />2.Cable Type - Voice and Data: TIA-568.2 Category 6 UTP (unshielded twisted pair); 23 <br />AWG. <br />3.Cable Capacity: 4-pair. <br />C.Copper Cable Terminations: Insulation displacement connection (IDC) type using appropriate <br />tool; use screw connections only where specifically indicated. <br />D.Jacks and Connectors: Modular RJ-45, non-keyed, terminated with 110-style insulation <br />displacement connectors (IDC); high impact thermoplastic housing; suitable for and complying <br />with same standard as specified horizontal cable; UL 1863 listed. <br />1.Performance: 500 mating cycles. <br />2.Voice and Data Jacks: 8-position modular jack, color-coded for both T568A and T568B <br />wiring configurations. <br />3.Product(s): <br />a.CommScope; SYSTIMAX RJ45 Jacks; MGS400 Series Category 6 U/UTP Modular <br />Jacks: www.commscope.com/#sle. <br />b.CommScope; Uniprise RJ45 Jacks; UNJ600 Series Category 6 U/UTP Modular <br />Jacks: www.commscope.com/#sle. <br />c.Or approved equal. <br />2.03 COMMUNICATIONS OUTLETS <br />A.Manufacturers: <br />1.CommScope; ________: www.commscope.com/#sle. <br />2.Siemon Company; ________: www.siemon.com/#sle. <br />3.Orapproved equal. <br />B.Outlet Boxes: Comply with Section 26 0533.16. <br />1.Provide depth as required to accommodate cable manufacturer's recommended minimum <br />conductor bend radius. <br />2.Minimum Size, Unless Otherwise Indicated: <br />a.Voice Only Outlets: 4 inch by 2 inch by 2-1/8 inch deep (100 by 50 by 54 mm) trade <br />size. <br />DocuSign Envelope ID: 09980A3B-0691-41B4-854D-3865F2287392