Orange County NC Website
Construction Documents <br />20052.02 / Orange County - Justice <br />Facility <br />26 2726 - 6 WIRING DEVICES <br />K. Install wall dimmers to achieve full rating specified and indicated after derating for ganging as <br />instructed by manufacturer. <br />L. Do not share neutral conductor on branch circuits utilizing wall dimmers. <br />M. Install vertically mounted receptacles with grounding pole on top and horizontally mounted <br />receptacles with grounding pole on left. <br />N. Where receptacles are indicated to be mounted above counters they shall be mounted <br />horizontally. <br />O. Install wall plates to fit completely flush to wall with no gaps and rough opening completely <br />covered without strain on wall plate. Repair or reinstall improperly installed outlet boxes or <br />improperly sized rough openings. <br />P. Install blank wall plates on junction boxes and on outlet boxes with no wiring devices installed or <br />designated for future use. <br />Q. Install poke-through closure plugs in each unused core holes to maintain fire rating of floor. <br />3.04 FIELD QUALITY CONTROL <br />A. Inspect each wiring device for damage and defects. <br />B. Operate each wall switch and wall dimmer with circuit energized to verify proper operation. <br />C. Test each receptacle to verify operation and proper polarity. <br />D. Test each GFCI receptacle for proper tripping operation according to manufacturer's <br />instructions. <br />E. Correct wiring deficiencies and replace damaged or defective wiring devices. <br />3.05 ADJUSTING <br />A. Adjust devices and wall plates to be flush and level. <br />B. Adjust presets for wall dimmers according to manufacturer's instructions as directed by <br />Architect. <br />3.06 CLEANING <br />A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match <br />original factory finish. <br />END OF SECTION 26 2726 <br />DocuSign Envelope ID: 09980A3B-0691-41B4-854D-3865F2287392