Orange County NC Website
Asbestos Abatement Guidelines and Policies <br />Page 01560-2 <br />F. Contractor shall install a negative pressure system as outlined by section 01513. <br /> <br />G. No water or ACBM may be left standing on the floor at the end of the workday. <br /> <br />H. The contractor shall establish and mark emergency and fire exit from the work area. <br />Emergency procedures shall have priority over established decontamination entry and <br />exit procedures. Audible and visible fire and emergency evacuation alarms shall be <br />installed to be heard and seen throughout the entire work area. <br /> <br />I. Integrity of these seals shall be regularly checked and maintained by the contractor. <br /> <br />J. After work area preparation, the contractor shall notify the air monitor verbally with <br />written follow-up that he is ready for a pre-work inspection. <br />DocuSign Envelope ID: 09980A3B-0691-41B4-854D-3865F2287392