Orange County NC Website
114 <br /> a. Doors. The number of entrances to the ADP room will be kept to a minimum as <br /> required by local fire code. Every entrance into an ADP room must be a metal clad <br /> or solid core, lockable door. A managed process will be utilized to control all <br /> access to the room. The process can be electronic or manual (key access, door bell <br /> with escort and sign-in, etc.) and the process must be documented. One key or code <br /> will be assigned to an individual from each customer group. All computer room <br /> doors shall be removed from the master key system of the facility. Exterior doors <br /> must have either interior hinges or exterior hinges with non-removable pins. <br /> b. Windows. There will be NO WINDOWS in the ADP room, even if a portion of the <br /> room has exterior walls. <br /> c. Flooring. The flooring will be anti-static hard surface; no carpet. <br /> d. Walls. Wall construction will be slab to slab with sound transmission class 40 or <br /> better. <br /> e. Temperature and Humidity. The ADP room shall be cooled at all times. The <br /> ambient room temperature shall be maintained between 650 to 78°F (18°to 26°C). <br /> The ambient relative humidity levels shall be maintained between 35% and 55%. <br /> The temperature and humidity controls shall be managed within the room, including <br /> point of contacts for emergency situations. The ADP room shall have access to <br /> temperature readings within the space. Air conditioning must be controlled on the <br /> weekends as needed to maintain the minimum temperature in the room. <br /> f. Shared Space. The ADP room shall NOT be designed as a multi-use room. Only <br /> ADP and telephone equipment shall be in this room. Mail machines, printers <br /> (unless specifically for the ADP equipment), faxes, file cabinets, shared storage, <br /> copiers,plotters, etc. shall be located outside the ADP room. ITS storage will NOT <br /> be in the ADP room. <br /> g. Plumbing. Because of the danger of water damage, the ADP room shall not be <br /> located in areas where water bearing pipes would be overhead. <br /> h. Fire Suppressant Systems. A sprinkler system will be installed when local building <br /> codes require it. A dry-pipe system is preferred. Sprinkler heads shall be placed so <br /> that they are not directly above any equipment. Each ADP room shall be equipped <br /> with a clean agent fire extinguisher. An annual inspection must be performed on <br /> the fire extinguisher. <br /> i. Telephone S.. sem. The telephone demarcation must be inside the building, not on <br /> the exterior. While this is preferred at all sites, it is mandatory in new construction. <br /> The building contractor shall attach to one wall a sheet of 3/4 inch 4 x 8 plywood, <br /> painted with fire retardant paint. This will be the extended demarcation point and <br /> for the installation of phone equipment, etc. <br /> Page 10 Lessor Gov't FPAC V1 1.13.202020 <br />