DocuSign Envelope ID: B94F2D40-3B3C-47A7-86C2-6F1 B4F92C62C <br /> Orange County Emergency Services Building Construction Documents <br /> 3.04 SCHEDULES <br /> A. Hanger Spacing for Copper Tubing. <br /> 1. 1/2 inch, 5/8 inch, and 7/8 inch OD: Maximum span, 5 feet; minimum rod size, 1/4 inch. <br /> 2. 1-1/8 inch OD: Maximum span, 6 feet; minimum rod size, 1/4 inch. <br /> 3. 1-3/8 inch OD: Maximum span, 7 feet; minimum rod size, 3/8 inch. <br /> 4. 1-5/8 inch OD: Maximum span, 8 feet; minimum rod size, 3/8 inch. <br /> 5. 2-1/8 inch OD: Maximum span, 8 feet; minimum rod size, 3/8 inch. <br /> END OF SECTION 23 23 00 <br /> PDC Project 18102 REFRIGERANT PIPING 23 23 00-5 <br /> 12/17/2018 <br />