<br /> MECHANICAL SPECIFICATIONS
<br /> ,n IT IS THE INTENT OF THESE SPECIFICATIONS TO FURNISH A COMPLETE HEATING, VENTILATING, AND AIR T •
<br /> Ip z CONDITIONING SYSTEM, FULLY ADJUSTED, AND READY FOR USE.
<br /> SEE NOTE
<br /> ALL MECHANICAL WORK TO BE DONE IN COMPLIANCE WITH NORTH CAROLINA BUILDING CODE AND ALL LOCAL
<br /> v�i Im CODES. AIR FLOW
<br /> SUPPLY/RETURN DUCT
<br /> g_ THIS CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS AND PAY ALL SALES TAXES, ° SS-1A
<br /> cam, I� Q AND OTHER COSTS, IN CONNECTION WITH HIS WORK. ROUND RUNOUT FLEXIBLE DUCT, 222 cloister court
<br /> Iz - FLEXIBLE DUCT CONNECTION TO METAL DUCT 5' MAX. LENGTH SUSPEND WITH (4)STRAP
<br /> LLJ ALL MATERIAL AND EQUIPMENT THAT CAN BE U.L. LISTED SHALL BE FURNISHED FOR THIS PROJECT. TOP OF DUCT RIGID SHEET HANGERS chapel hill, nc 27514
<br /> METAL BOX. 919.401 .8586
<br /> a FROM STRUCTURE ABOVE
<br /> MATERIAL AND EQUIPMENT HAS BEEN CAREFULLY SELECTED FOR THIS PROJECT AND THE CONTRACTOR IS MANUAL www.cra-ae.com
<br /> I EXPECTED TO PROVIDE ALL ITEMS AS CLOSELY AS POSSIBLE TO THE SPECIFICATIONS AND AS CALLED FOR ON VOLUME TRANSITION
<br /> � o DAMPER LINED WITH
<br /> THE DRAWINGS. ROUND DUCT DUCT LINER.
<br /> 1O BRANCH TAKE-OFF NECK (IF REQUIRED)
<br /> SUBMIT THREE (3) SETS OF EQUIPMENT DATA SHOP DRAWINGS TO ENGINEER FOR ALL ITEMS TO BE TURNING VANE OPEN TO ATTIC
<br /> z FURNISHED AND INSTALLED FOR APPROVAL. COMPLETELY SEE NOTE DAMPER TAG
<br /> INSULATE OR RIBBON
<br /> 1 1 rg
<br /> THIS CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST TO THE OWNER, ANY LABOR, SIDE OF DUCT BACK OF �1 1� SS-1 B
<br /> Q MATERIALS, SERVICES, APPARATUS, DRAWINGS, IN ORDER TO COMPLY WITH ALL APPLICABLE LAWS, DIFFUSER
<br /> — BALANCE DAMPER
<br /> C SPIN TAP WITH MAN_�A= \ UAL 1 _ WHERE SPECIFIED.
<br /> ORDINANCES, RULES AND REGULATIONS, WHETHER OR NOT SHOWN ON DRAWINGS AND/OR SPECIFIED. NO AIR FLOW VOLUME DAMPER CEILING//T 0
<br /> CLAIM FOR EXTRAS WILL BE APPROVED WITHOUT PRIOR COORDINATION FOR CONFLICTS BY CONTRACTOR, AND (MECHANICAL CONTRACTOR SHALL RKa
<br /> XDE'
<br /> w WRITTEN REQUEST AND WRITTEN APPROVAL PRIOR TO PERFORMING WORK.
<br /> c o PERFORATWA
<br /> ED PROVIDE ACCESS DOOR FOR ANY
<br /> ALL WORK AND EQUIPMENT TO BE GUARANTEED BY CONTRACTOR FOR ONE 1 YEAR. AN ADDITIONAL FOUR DOWN TO DIFFUSER VOLUME DAMPER LOCATED ABOVE SUPPLY
<br /> ( ) CEILING. RETURN DIFFUSER.
<br /> (4) YEAR WARRANTY SHALL BE PROVIDED ON ALL COMPRESSORS. _ DIFFUSER HARD CEILING) DIFFUSER MECHANICAL CONTRACTOR REFER TO GRILLE = ENGINEERS
<br /> o MANUAL FLEXIBLE CONNECTION TO SUPPLY DIFFUSER SCHEDULE FOR TYPE AND Reece, Noland & McElrath, Inc.
<br /> ALL MATERIALS AND EQUIPMENT TO BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS AND GOOD VOLUME ELECTRICAL CONTRACTOR I NECK SIZE 94 Main Street
<br /> DAMPER
<br /> N o RECOMMENDED PRACTICES. NOTE: I Canton, North Carolina 28716
<br /> c� z
<br /> PHONE:828-492-0677 NC CERT.N0.C-0149 FAX:828492-1054
<br /> = 10 00 1. ALL MANUAL VOLUME DAMPERS (FOR INSULATED DUCTWORK)SHALL I MAIL@RNM-ENGENEERS.COM p2018 WWW.RNM-ENGINEERS.COM
<br /> ALL WORK AND MATERIALS SHALL MEET APPROVAL OF ARCHITECT/ENGINEER. SINGLE DROP
<br /> 1,� o BE PROVIDED WITH AN ELEVATED REGULATOR(STAND-OFF) EQUAL TO
<br /> THIS CONTRACTOR SHALL GIVE FULL COOPERATION TO OTHER TRADES. WHERE THE WORK OF THIS NOTE: NOTE : DURO DYNE SRST SERIES. STAND SHALL EXTEND A MINIMUM OF 2
<br /> 1� o CONTRACTOR WILL BE INSTALLED IN CLOSE PROXIMITY TO, OR WILL INTERFERE WITH WORK OF OTHER TRADES,
<br /> 1. MANUAL VOLUME DAMPERS SHALL BE PROVIDED FOR ALL FLEXIBLE DUCT CONNECTIONS TO SHEET METAL SHALL BE BEYOND DUCTWORK WITH EXTENDED TAB/SHAFT. NOTE:
<br /> 1� U HE SHALL ASSIST IN WORKING OUT SPACE CONDITIONS TO MAKE SATISFACTORY ADJUSTMENTS. IF THIS ALL SUPPLY AND RETURN SINGLE DROP DUCT RUNS. SECURED WITH NYLON STRAP AND 2 SHEET METAL SCREWS (MIN.). 2. MANUAL VOLUME DAMPERS SHALL BE PROVIDED FOR ALL SUPPLY THE SPIT SYSTEM A/C UNIT SPECIFIED ONLY REQUIRES A SINGLE BREAKER SPACE.
<br /> No m CONTRACTOR INSTALLS HIS WORK BEFORE COORDINATING WITH OTHER TRADES, HE SHALL MAKE THE AND RETURN RUNOUTS. THE INSIDE UNIT IS SUB FED FROM THE OUTSIDE UNIT. ELECTRICAL CONTRACTOR IS
<br /> o NECESSARY CHANGES IN HIS WORK TO CORRECT THE CONDITION WITHOUT EXTRA CHARGE. RESPONSIBLE FOR WIRING TO OUTSIDE UNIT. MECHANICAL CONTRACTOR IS
<br /> RESPONSIBLE FOR WIRING FROM OUTSIDE UNIT TO INDOOR UNIT. M.C.TO FURNISH
<br /> o DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENTS OF SYSTEMS AND WORK INCLUDED BOTH DISCONNECTS.
<br /> IN THE CONTRACT. DRAWINGS ARE NOT TO BE SCALED. DUCTWORK DETAILS FLEX. CONNECTION DETAIL ROUND NECK DIFFUSER SPLIT SYSTEM WIRING DETAIL PLENUM CEILING RETURN GRILL
<br /> z NO SCALE
<br /> Cot = ALL DUCTWORK TO BE FABRICATED FROM GALVANIZED SHEET METAL AND INSTALLED ACCORDING TO NO SCALE NO SCALE NO SCALE NO SCALE
<br /> o
<br /> REQUIREMENTS OF NFPA 90A, SMACNA, AND ASHRAE GUIDE AND DATA BOOKS.
<br /> =II V) 1`X111111itfill/,
<br /> t° ALL FLEXIBLE DUCTWORK, FOR CONNECTIONS BETWEEN DIFFUSERS AND BRANCH DUCTS WHERE INDICATED, TO
<br /> GALV. ALL-THREADED "All
<br /> BE THERMAFLEX TYPE MKE . TO ANGLES ROD (TYP)
<br /> „ CONTINUE UP TO 1/2 0 THREADED � om e
<br /> v, 10 ALL DUCT SEAMS TO BE TAPED WITH FASSON �AFTS-100/3 SMACNA TAPE, OR EQUAL. 7' 1 STRAP STRUCTURAL ROOF SUPPORT. ROD. (TYP) P a� o
<br /> `—' � SEE DETAIL " " SHEET �$e,�
<br /> VOLUME CONTROL DAMPERS (BALANCING) SHALL BE INSTALLED IN EACH BRANCH OR ZONE DUCT. 1"STRAP fy,��a �aj•�
<br /> r vgvvvpg4q
<br /> .o BAND A INSULATION 1/0)y M0��`�`ti,
<br /> DAMPERS WHICH ARE PART OF A MANUFACTURED AIR GRILL DO NOT MEET THIS REQUIREMENT. W17ititillo
<br /> ALL SQUARE ELBOWS SHALL HAVE TURNING VANES INSTALLED. TURNING VANES SHALL BE APPLIED EQUALLY DUCT DUCT SPRING VIBRATION ISOLATORS. _ _ DUCT
<br /> TO THE RETURN AIR SIDE.
<br /> DUCTWORK SIZES INDICATED ON DRAWINGS ARE AS REQUIRED FOR FREE INSIDE AREAS. P W _� GALV.ANGLE NUT & LOCK WASHER.
<br /> SCREW(TYP) TOP AND BOTTOM
<br /> ALL DUCTWORK TO BE INSULATED WITH 2" BLANKET TYPE INSULATION 1 LB. DENSITY (MIN. R=6.5) WITH DUCTS UP TO DUCTS ABOVE ROUND
<br /> lo
<br /> VAPOR BARRIER JACKET OF .002 INCH THICK ALUMINUM FOIL LAMINATED. 48"WIDTH 48"WIDTH o GASKET
<br /> ALL PIPING AND DUCTWORK TO BE SUSPENDED WITH APPROPRIATE HANGERS, INSTALLED AND SPACED PER NC LOW PRESSURE DUCTWORK SUPPORT LUGS.
<br /> lo
<br /> MECHANICAL CODE.
<br /> 1"STRAP (IF PROVIDED) NUT & LOCK
<br /> ALL SUPPLY GRILLES AND DIFFUSERS TO BE EQUIPPED WITH VOLUME CONTROLS. TO ANGLES WASHER. TOP
<br /> <>- <?
<br /> 1" HANGER AND BOTTOM.
<br /> AIR HANDLING EQUIPMENT SHALL BE ISOLATED FROM DIRECT CONTACT WITH SUPPLY OR RETURN AIR RECTANGULAR OR STRAP
<br /> DUCTWORK. FLEXIBLE CONNECTIONS SHALL BE INSTALLED BETWEEN THE EQUIPMENT AND DUCT. FLEXIBLE FLAT-OVAL DUCT
<br /> CONNECTIONS SHALL BE MADE OF APPROVED FLAMEPROOFED FABRIC OR OTHER APPROVED NON—COMBUSTIBLE DUCT
<br /> ll
<br /> MATERIAL. � \ EQUIPMENT
<br /> SECTION "A-A"
<br /> X v,
<br /> INDEPENDENT T&B AGENCY (AABC OR NEBB CERTIFIED) TO PERFORM ALL ADJUSTMENTS AND BALANCING OF o � 0) C
<br /> SYSTEMS, EQUIPMENT, CONTROLS, ETC., NECESSARY FOR THE SYSTEM TO PROVIDE THE REQUIRED BAND if
<br /> _
<br /> PERFORMANCE AND TO OPERATE SAFELY. SUBMIT CERTIFIED T&B REPORT, AND "AS—BUILT" DRAWINGS TO O
<br /> ENGINEER SHOWING ACTUAL AIR FLOWS AT EACH GRILL INSTALLED UNDER THIS CONTRACT. REPORT GALV.ANGLE E CHANNEL •
<br /> GALV.ALL-THREADED -_ ACCESS PANEL
<br /> PROCEDURES TO BE PER AABC/NEBB GOOD PRACTICES AND RECOMENDATIONS. T&B TO BE PALMETTO OR ROD (TYP) ROUND C3X6
<br /> APPROVED EQUAL. T&B TO BE UNDER MECHANICAL CONTRACT.
<br /> UPON COMPLETION OF ALL WORK AND ALL TESTS, INSTRUCT THE OWNER OR HIS REPRESENTATIVE FULLY IN CASING • W 1—
<br /> THE OPERATIONS, ADJUSTMENTS, AND MAINTENANCE OF ALL EQUIPMENT FURNISHED. MED. AND HIGH PRESSURE DUCTWORK ' 4
<br /> GASKET Ca < E
<br /> PROVIDE OWNER MAINTENANCE INSTRUCTIONS AND SCHEDULE FOR THE PRINCIPAL ITEMS OF EQUIPMENT EQUIPMENT SUPPORT DETAIL
<br /> FURNISHED. MANUFACTURE DUCTWORK HANGER DETAILS MANUFACTURER'S ADVERTISING LITERATURE OR CATALOGS WILL NOT BE ACCEPTABLE. HANDLE INSIDE N
<br /> � � � o
<br /> NO SCALE NO SCALE
<br /> > 0C=:= 0
<br /> V
<br /> F_
<br /> 0
<br /> s 0
<br /> O o � =
<br /> o =
<br /> INSULATION FLEXIBLE
<br /> R R R 1/2" [15mm] FACTORY FABRICATED LATCH WASHER
<br /> SHALL SHALL co SHALL ROUND ROD PIN
<br /> STIFFEN INSULATION no. revisions
<br /> EQUAL �i�� EQUAL J��GI� EQUAL BLADE AS DUCT OUTSIDE END BEARING SECTION "B-B"
<br /> RFQ1 IIRFn 7
<br /> OR BE OR BE TOR BE Tuuumf
<br /> \-- GREATER GREATER VANE GREATER INSULATION
<br /> STAND-OFF ACCESS DOOR
<br /> + THAN W. VANE THAN THAN
<br /> 1/3W. 1/6W. o DAMPER BLADE NOTES:
<br /> 1/6W
<br /> HANDLE WITH
<br /> LOCKING 1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
<br /> STANDARD RADIUS QUAy INSIDE END BEARING 2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
<br /> ELBOW W W
<br /> NOTE: 1/8" [6mm]
<br /> CLEARANCE
<br /> SHORT RADIUS ELBOW SHORT RADIUS ELBOW 1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SIDE ELEVATION ALL AROUND SECTION DESIGNERS NOTES. The oriuseginal
<br /> site
<br /> purposens
<br /> f specifications shall11 e prepare to and
<br /> original site purpose for which they were prepared and
<br /> publication thereof is expressly limited to such use. Re-use,
<br /> WITH ONE VANE WITH TWO VANES SMACNA. reproduction, modification, or publication by any method, in
<br /> 1. USE ACCESS DOORS ON AIR HANDLING UNITS AND DUCTWORK INSTALLED IN EQUIPMENT ROOMS. whole or in part, is prohibited and the recipient shall defend,
<br /> 2. WHEN W1 DOES NOT EQUAL W2 VANE SHALL BE SINGLE VANE TYPE indemnify and hold The architect harmless from and against any
<br /> NOTE: , claims and losses arising therefrom.Title and all ownership rights
<br /> REGARDLESS OF W DIMENSION. NOTE: 2. USE ACCESS PANELS ON ALL EQUIPMENT AND DUCTWORK INSTALLED ABOVE FINISHED CEILINGS. to the plans and specifications remain in the architect without
<br /> 1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND. use,inclue.ding
<br /> It is i be returned upon request to the architect.Any
<br /> use,including visual contact,with these plans and specifications
<br /> 3. ALL SINGLE VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] 1 DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
<br /> . shall constitute prima facie evidence of the acceptance of the
<br /> 2. ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE. foregoing.
<br /> RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL 4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL 2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR drawn checked
<br /> BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA. FOR MULTI-BLADE DAMPERS & ROUND DAMPERS. ACCESS DOOR DETAIL
<br /> BE DOUBLE VANE TYPE. KDs MRM
<br /> NO SCALE MECHANICAL
<br /> U
<br /> rn
<br /> w
<br /> MITERED ELBOW TURNING VANE DETAILS &
<br /> Q
<br /> RADIUS ELBOW VANE DETAIL DETAIL BALANCE DAMPER DETAIL SPECIFICATIONS