DocuSign Envelope ID: 9826C043- 4C32- 49CD- A4CC- DC28ABAB7CE7
<br />SECTION 239500 - MULTI - INDOOR VRV SYSTEM
<br />i. The Daikin wall mounted, hard wired remote sensor kit is recom-
<br />mended for ceiling- embedded type fan coils, which often result in a
<br />difference between set temperature and actual temperature. The sen-
<br />sor for detecting the temperature can be placed away from the indoor
<br />unit (branch wiring is included in the kit).
<br />4.04 FXMQ_PA - CONCEALED CEILING DUCTED UNIT (Med. Static)
<br />A. General: Daikin indoor unit FXMQ_PA shall be a built -in ceiling concealed
<br />fan coil unit, operable with refrigerant R -410A, equipped with an electronic
<br />expansion valve, direct -drive DC (ECM) type fan with auto CFM adjustment
<br />at commissioning, for installation into the ceiling cavity. It is constructed of a
<br />galvanized steel casing. It shall be available in capacities from 7,500 Btu /h to
<br />48,000 Btu /h. Model numbers are FXMQ07PAVJU, FXMQ09PAVJU,
<br />FXMQ12PAVJU, FXMQ15PAVJU, FXMQ18PAVJU, FXMQ24PAVJU,
<br />FXMQ30PAVJU, FXMQ36PAVJU, FXMQ48PAVJU, and FXMQ54PAVJU to
<br />be connected to outdoor unit model RXYQ / RXYMQ / RWEYQ heat pump
<br />and REYQ / RWEYQ heat recovery model. It shall be a horizontal discharge
<br />air with horizontal return air configuration. All models feature a low height
<br />cabinet making them applicable to ceiling pockets that tend to be shallow.
<br />Computerized PID control shall be used to control superheat to deliver a
<br />comfortable room temperature condition. The unit shall be equipped with a
<br />programmed drying mechanism that dehumidifies while limiting changes in
<br />room temperature when used with Daikin remote control BRC1 E72,
<br />BRC1 E73 and BRC2A71. Included as standard equipment, a condensate
<br />drain pan and drain pump kit that pumps to 18 -3/8" from the drain pipe open-
<br />ing. The indoor units sound pressure shall range from 29 dB(A) to 43 dB(A)
<br />at low speed measured 5 feet below the ducted unit.
<br />B. Performance: Each unit's performance is based on nominal operating condi-
<br />tions:
<br />Model Number
<br />Cooling
<br />(Indoor 80 °F DB / 67 °F WB,
<br />Outdoor 95 °F DB, 25 ft pipe length)
<br />Heating
<br />(Indoor 47 °F DB / 43 °F W B,
<br />Outdoor 70 °F DB, 25 ft pipe length)
<br />FXMQ07PAVJU
<br />7,500
<br />8,500
<br />FXMQ09PAVJU
<br />9,500
<br />10.500
<br />FXMQ12PAVJU
<br />12,000
<br />13,500
<br />FXMQ15PAVJU
<br />15,000
<br />16,500
<br />FXMQ18PAVJU
<br />18,000
<br />20,000
<br />FXMQ24PAVJU
<br />24,000
<br />27,000
<br />FXMQ30PAVJU
<br />30,000
<br />34,000
<br />FXMQ36PAVJU
<br />36,000
<br />40,000
<br />FXMQ48PAVJU
<br />48,000
<br />54,000
<br />FXMQ54PAVJU
<br />54,000
<br />60,000
<br />C. Indoor Unit:
<br />1. The Daikin indoor unit FXMQ_PA shall be completely factory assembled
<br />and tested. Included in the unit is factory wiring, piping, electronic propor-
<br />tional expansion valve, control circuit board, fan motor thermal protector,
<br />flare connections, condensate drain pan, condensate drain pump, con-
<br />densate safety shutoff and alarm, self- diagnostics, auto - restart function,
<br />3- minute fused time delay, and test run switch. The unit shall be equip-
<br />ment with automatically adjusting external static pressure logic that is se-
<br />Reece, Noland & McElrath, Inc. 239500-43 Orange County Board of Elections
<br />Orange Co., NC 05/04/18
<br />
|