Orange County NC Website
DocuSign Envelope ID: 9826C043- 4C32- 49CD- A4CC- DC28ABAB7CE7 <br />SECTION 238000 — TEST AND BALANCE <br />8. Actual airflows measured at each grille /diff user. <br />9. Inlet and outlet static pressures measured at each air handling unit. <br />10. Pump inlet and outlet pressures and flow rates. <br />11. Identification on system diagrams to be cross - referenced to tabulated data. <br />3.21 ADDITIONAL TESTS <br />A. Within 90 days of completing TAB, perform additional testing and balancing to verify that balanced <br />conditions are being maintained throughout and to correct unusual conditions. <br />B. Seasonal Periods: If initial TAB procedures were not performed during near -peak summer and <br />winter conditions, perform additional testing, inspecting, and adjusting during near -peak summer and <br />winter conditions. <br />C. Opposite season testing: Perform additional testing, inspecting, and adjusting during the opposite <br />season in which initial TAB procedures were performed. <br />D. In all cases, notify Designer in advance of performing additional tests. <br />END OF SECTION 238000 <br />Reece, Noland & McElrath, Inc. 238000-9 Orange County Board of Elections <br />Orange Co., NC 05/04/18 <br />