DocuSign Envelope ID: 46EAC4FA- 7089- 45C4- ADA1- 480BF2799823 <br />1 2 3 1 4 5 <br />ELECTRICAL SPECIFICATIONS_ <br />IT IS THE INTENT OF THESE SPECIFICATIONS FOR THE ELECTRICAL CONTRACTOR TO FURNISH A COMPLETE ELECTRICAL SYSTEM, FULLY <br />ADJUSTED, & READY FOR USE. <br />° ALL ELECTRICAL WORK TO BE DONE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE OBSERVING <br />A =n I ALL STATE & LOCAL CODES. <br />ELECTRICAL CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS & PAY ALL SALES TAXES, UTILITY COMPANY <br />CHARGES FOR SERVICE, PERMITS, FEES, & OTHER COSTS IN CONNECTION WITH HIS WORK. <br />N Im <br />s ELECTRICAL CONTRACTOR TO ENSURE THAT ALL MATERIAL & EQUIPMENT FURNISHED FOR THIS PROJECT WHICH CAN BE U.L. LISTED SHALL <br />It BE. <br />IN MATERIAL & EQUIPMENT HAS BEEN CAREFULLY SELECTED FOR THIS PROJECT & THE ELECTRICAL CONTRACTOR IS EXPECTED TO <br />N PROVIDE ALL ITEMS AS CLOSELY AS POSSIBLE TO THE SPECIFICATIONS & AS CALLED FOR ON THE DRAWINGS. <br />I ELECTRICAL CONTRACTOR SHALL SUBMIT THREE (3) SETS OF EQUIPMENT DATA SHOP DRAWINGS TO THE ENGINEER FOR ALL ITEMS TO BE <br />O <br />FURNISHED & INSTALLED FOR APPROVAL. <br />WHERE ALUMINUM CONDUCTORS ARE UTILIZED THEY SHALL BE TERMINATED WITH BURNDY HY -PLUG, HYDRAULIC COMPRESSION <br />TERMINATORS. <br />D ALL CONDUCTORS, THROUGH #10 AWG, TO BE SOLID COPPER WITH TYPE THWN /THHN OR XHHW INSULATION UNLESS NOTED OTHERWISE. <br />ALL CONDUCTORS, #8 AWG AND LARGER, TO BE CLASS B STRANDED COPPER WITH TYPE THWN /THHN OR XHHW INSULATION UNLESS NOTED <br />OTHERWISE. <br />E <br />F <br />G <br />H <br />THE COLOR CODE FOR CONDUCTORS SHALL BE BLACK, RED, WHITE, ORANGE (120/24OV, 30, Y) <br />PROVIDE GREEN GROUNDING CONDUCTOR WITH ALL CIRCUITS. <br />P.V.C.CONDUIT SHALL NOT BE USED IN AREAS OF ASSEMBLY. <br />/_1a I V 10 " i7: 1 :y_l == O1T :19-1 0612 MT %y,a <br />ELECTRICAL CONTRACTOR SHALL PROVIDE & INSTALL SMOOTH PLASTIC DEVICE PLATES BRYANT 70000 SERIES LEVITON 85/86000 SERIES OR <br />APPROVED EQUAL. PLATES SHALL BE OF THE SAME COLOR AS THE DEVICE (REFER TO SYMBOL SCHEDULE). EXTERIOR MOUNTED BOXES <br />SHALL HAVE APPROVED WEATHERPROOF PLATES &/OR COVERS. ALL SURFACE INSTALLED BOXES SHALL HAVE STAMPED STEEL DEVICE <br />PLATES. <br />ALL DEVICE OUTLETS SHALL BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED. <br />BALLASTS SUPPLIED WITH RECESSED FLUORESCENT FIXTURES SHALL BE APPROVED BY UNDERWRITERS' LABORATORIES & SHALL BE, <br />ELECTRONIC, ENERGY SAVINGS, PREMIUM GRADE, PROPERLY APPLIED TO EACH INSTALLATION. BALLASTS SUPPLIED WITH SURFACE <br />MOUNTED FLUORESCENT FIXTURES SHALL BE, ELECTRONIC, ENERGY SAVINGS EXTRA LOW HEAT, SUPER PREMIUM TYPES. BALLASTS TO BE <br />AS MANUFACTURED BY ADVANCE, UNIVERSAL, JEFFERSON, OR APPROVED EQUAL. <br />1 I 2 I 3 I 4 I 5 <br />VA <br />AREA r'E ` ^' ^ °" <br />EXISTING BUILDING NOTES <br />1. WHERE INDICATED REMOVE ALL CONDUIT, WIRING, AND ELECTRICAL <br />EQUIPMENT, INCLUDING PREVIOUSLY ABANDONED, RENDERED <br />USELESS BY CONSTRUCTION. <br />2. EXISTING WIRING, DEVICES, ELECTRICAL PANELS, ETC., ARE SHOWN <br />LIGHTER AND DASHED. <br />3. EXISTING WIRING AND RACEWAYS TO BE REUSED WHERE POSSIBLE <br />OR PRACTICAL, AND EXISTING WIRING IS FOUND TO BE IN GOOD <br />CONDITION; REPLACE ANY EXISTING WIRING FOUND TO BE IN POOR <br />CONDITION. ALL NEW INSTALLATIONS SHALL USE NEW WIRE, TYPICAL. <br />4. ALL MATERIALS REMOVED AND NOT TO BE REUSED ARE TO BE <br />DISPOSED OF PER OWNER'S INSTRUCTIONS. <br />5. ALL FIXTURES ARE 120V UNLESS INDICATED OTHERWISE BY CIRCUIT <br />DESIGNATOR. <br />GENERAL NOTES FOR ELECTRICAL DEMOLITION <br />KEY PLAN <br />NOT TO SCALE <br />1. FIELD VERIFY ALL EXISTING CONDITIONS AND NOTIFY ARCHITECT OF ANY DISCREPANCIES ON DRAWINGS. <br />2. UNLESS OTHERWISE NOTED, THE OWNER RETAINS THE RIGHT TO RETAIN ALL ITEMS AND /OR MATERIALS IN GOOD <br />CONDITION FOLLOWING REMOVAL AND /OR DEMOLITION. OTHERWISE, THE CONSTRUCTION MANAGER SHALL <br />DISPOSE OF ALL OTHER ITEMS AND MATERIALS IN A LEGAL FASHION. <br />3. IF ANY ASBESTOS - CONTAINING MATERIAL IS SUSPECTED, G.C. SHALL STOP DEMOLITION AND CONTACT THE <br />OWNER'S REPRESENTATIVE IMMEDIATELY. THE OWNER SHALL CONTRACT WITH AN ASBESTOS ABATEMENT <br />CONTRACTOR UNDER A SEPARATE CONTRACT FOR THE REMOVAL OF ALL EXISTING ASBESTOS - CONTAINING <br />MATERIAL, SHOULD ANY BE ENCOUNTERED. <br />4. FOR WALL MOUNTED DEVICES: (TYPICALLY RECEPTACLES, DATA /TV OUTLETS & LIGHT SWITCHES) UNLESS <br />SPECIFICALLY IDENTIFIED BY DEMOLITION NOTE, WALL MOUNTED DEVICES ARE TO BE REMOVED. <br />5. FOR CEILING MOUNTED DEVICES: (TYPICALLY LIGHTING FIXTURES EXIT LIGHTS, WIRELESS TRANSMITTERS, <br />CAMERAS, SMOKE DETECTORS, SPEAKERS, ETC.) UNLESS NOTED OTHERWISE IN DEMOLITION NOTES, CEILING <br />DEVICES ARE TO BE REMOVED. <br />6. LIGHTING, POWER, & DATA - CONTRACTOR MAY REUSE EXISTING CONDUIT AND WIRING TO THE EXTENT POSSIBLE <br />IN PROVIDING A COMPLETE AND OPERABLE SYSTEM. CONTRACTOR IS TO PROVIDE ALL LABOR & MATERIALS, <br />INCLUDING BUT NOT LIMITED TO DEVICES, BOXES, CONDUIT, AND WIRING FROM ALL DEVICES TO APPROPRIATE <br />DISTRIBUTION /CONTROL PANEL IN ORDER TO PROVIDE A COMPLETE AND OPERABLE SYSTEM. CONTRACTOR TO <br />FIELD VERIFY ALL EXISTING QUANTITIES AND LOCATIONS & COORDINATE CLOSELY WITH OWNER. <br />7. E.C. TO TAKE CARE IN REMOVING, TAGGING, & STORING DEVICES DURING DEMO PHASE, & REPLACING DEVICES TO <br />BE REUSED DURING NEW CONSTRUCTION PHASE. EXISTING CEILING MOUNTED DEVICES TO BE REINSTALLED AS <br />CLOSE AS POSSIBLE TO ORIGINAL LOCATION. PROVIDE MATERIAL AND LABOR FOR EXTENDING CONDUIT & WIRING, <br />AS REQUIRED, FOR REINSTALLATION. ENSURE PROPER OPERATION AFTER CONSTRUCTION. <br />8. WHERE RECEPTACLES ARE REMOVED, ELECTRICAL CONTRACTOR TO REMOVE EXISTING RECEPTACLE DEVICE, <br />BOX, CONDUIT AND WIRING BACK TO IT'S SOURCE. WHERE CIRCUIT FEEDING RECEPTACLE TO BE REMOVED ALSO <br />FEEDS RECEPTACLES THAT ARE TO REMAIN, ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, WIRING AND <br />BOXES AS REQUIRED TO RE -FEED EXISTING RECEPTACLES, AS REQUIRED, FOR PROPER OPERATION. SEE <br />INSTALLATION DRAWINGS AND PANEL SCHEDULES FOR ADDITIONAL CIRCUITING INFORMATION. <br />9. WHERE LIGHTING FIXTURES AND ASSOCIATED SWITCHING ARE REMOVED, ELECTRICAL CONTRACTOR TO REMOVE <br />EXISTING FIXTURE, SWITCH, SWITCH BOX, CONDUIT AND WIRING BACK TO IT'S SOURCE. WHERE CIRCUIT FEEDING <br />FIXTURE(S) TO BE REMOVED ALSO FEEDS FIXTURE(S) THAT ARE TO REMAIN, ELECTRICAL CONTRACTOR SHALL <br />PROVIDE CONDUIT, WIRING AND BOXES AS REQUIRED TO RE -FEED EXISTING FIXTURE(S), AS REQUIRED, FOR <br />PROPER OPERATION. SEE INSTALLATION DRAWINGS AND PANEL SCHEDULES FOR ADDITIONAL CIRCUITING <br />INFORMATION. <br />10. WHERE JB'S, PULL BOXES, CONDUIT, OR OTHER ELECTRICAL DEVICES ARE FOUND WITH WIRING AND WITHOUT <br />COVERS, E.C. TO PROVIDE COVERS, AND /OR CAPS. WHERE JB'S, PULL BOXES, CONDUIT, OR OTHER ELECTRICAL <br />DEVICES ARE FOUND WITHOUT WIRING, E.C. TO REMOVE BACK TO SOURCE OR NEAREST POPULATED JUNCTION. <br />ELECTRICAL SYMBOL SCHEDULE <br />ALL SYMBOLS MAY NOT BE USED <br />SYMBOL DESCRIPTION MOUNTING <br />@ Exhaust fan See Mech'I. Dwgs. <br />@ Pump See Plumbing & Mech. Dwgs. <br />Motor See Mech'I. Dwgs. <br />0 Electrical panelboard, see panel schedule for description. 6' -6" to top <br />Home run to panelboard. Arrowheads indicate number of <br />ELECTRICAL CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST TO THE OWNER, ANY LABOR, MATERIALS, SERVICES, <br />Required <br />AFF ..............ABOVE <br />APPARATUS, DRAWINGS, INCIDENTAL CONSTRUCTION WORK, ETC., IN ORDER TO COMPLY WITH ALL APPLICABLE LAWS, ORDINANCES, & <br />AHU ............. <br />AIR HANDLER UNIT <br />REGULATIONS, WHETHER OR NOT SHOWN ON DRAWINGS AND /OR SPECIFIED. NO CLAIM FOR EXTRAS WILL BE APPROVED WITHOUT PRIOR <br />Disconnect switch, 250 VAC Size as shown. Where <br />As <br />COORDINATION FOR CONFLICTS BY CONTRACTOR, & WRITTEN REQUEST & APPROVAL PRIOR TO PERFORMING WORK. <br />B <br />� <br />no <br />higher than <br />EWH .............ELECTRIC <br />ALL WORK & EQUIPMENT TO BE GUARANTEED BY CONTRACTOR FOR ONE (1) YEAR. <br />6' -6" <br />c <br />UPON COMPLETION OF ALL WORK & ALL TESTS, ELECTRICAL CONTRACTOR SHALL INSTRUCT THE OWNER OR HIS REPRESENTATIVE FULLY IN <br />Junction box as manufactured by RACO, Steel City, or <br />GWH .............GAS <br />THE OPERATIONS, ADJUSTMENTS, & MAINTENANCE OF EQUIPMENT FURNISHED. ELECTRICAL CONTRACTOR SHALL PROVIDE OWNER WITH <br />MC ............... <br />Universal. Size as applicable or required. <br />MAINTENANCE SCHEDULE FOR THE PRINCIPAL ITEMS OF EQUIPMENT FURNISHED. MANUFACTURER'S ADVERTISING LITERATURE OR <br />MOLDED CASE CIRCUIT BREAKER <br />AFF <br />CATALOGS WILL NOT BE ACCEPTABLE. <br />- - <br />- -- <br />AFG <br />Above finished grade <br />N <br />ALL MATERIALS AND EQUIPMENT TO BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS & GOOD RECOMMENDED PRACTICES. <br />AHU <br />Air Handler Unit <br />O <br />- -- <br />BFG <br />U <br />10D <br />ELECTRICAL CONTRACTOR SHALL GIVE FULL COOPERATION TO OTHER TRADES. WHERE THE WORK OF ELECTRICAL CONTRACTOR WILL BE <br />- -- <br />c� Im <br />INSTALLED IN CLOSE PROXIMITY TO, OR WILL INTERFERE WITH WORK OF OTHER TRADES, HE SHALL ASSIST IN WORKING OUT SPACE <br />- - <br />1� <br />CONDITIONS TO MAKE SATISFACTORY ADJUSTMENTS. IF ELECTRICAL CONTRACTOR INSTALLS HIS WORK BEFORE COORDINATING WITH <br />Fused Disconnet Switch <br />IN <br />OTHER TRADES, HE SHALL MAKE THE NECESSARY CHANGES IN HIS WORK TO CORRECT THE CONDITION WITHOUT EXTRA CHARGE. <br />M.C. <br />1° <br />- - <br />- -- <br />P.C. <br />THE DRAWINGS ARE DIAGRAMMATIC & INDICATE THE GENERAL ARRANGEMENTS OF SYSTEMS & WORK INCLUDED IN THE CONTRACT. THE <br />- - <br />- -- <br />DRAWINGS ARE NOT TO BE SCALED. <br />C <br />EXISTING INFORMATION SHOWN ON DRAWINGS TAKEN FROM OWNER FURNISHED AS BUILT DRAWINGS & LIMITED SITE SURVEY. <br />U <br />w <br />C) <br />0 <br />CONTRACTOR TO FIELD VERIFY ALL EXISTING EQUIPMENT, CIRCUITS, & WIRING. <br />NO <br />DATE <br />ISSUED FOR <br />1 <br />0 <br />2 <br />ELECTRICAL CONTRACTOR TO VERIFY EXACT LOCATION OF EQUIPMENT, ROUTING PIPE, ETC., & WORK CLOSELY WITH OTHER TRADES TO <br />3 <br />AVOID CONFLICTS. <br />4 <br />5 <br />6 <br />I <br />ELECTRICAL CONTRACTOR TO LOCATE & INSTALL ELECTRICAL CONTROL PANELS IN SUITABLE LOCATION WITH APPROPRIATE CLEARANCES & <br />OVERLOAD PROTECTION FOR ALL ITEMS REQUIRED. <br />7 <br />N ° <br />8 <br />U � <br />ELECTRICAL CONTRACTOR MAY COMBINE CONDUITS WHERE APPLICABLE, BUT MUST HOOK UP ITEMS TO PROPER CIRCUITS AS SHOWN. <br />ELECTRICAL SYMBOLS, <br />NOTES & SPECIFICATIONS <br />ISSUED FOR: <br />CONSTRUCTION <br />DRAWN BY: <br />JWC <br />DRAWING NO. <br />APPROVED BY: <br />THE OWNER, ARCHITECT & ELECTRICAL CONTRACTOR TO COORDINATE FOR PROPER CUTOUT HOLES, ALL STUB -UPS & JUNCTION BOXES, & <br />PROJECT #: <br />2018034 <br />TO VERIFY LOCATIONS. <br />WHERE ALUMINUM CONDUCTORS ARE UTILIZED THEY SHALL BE TERMINATED WITH BURNDY HY -PLUG, HYDRAULIC COMPRESSION <br />TERMINATORS. <br />D ALL CONDUCTORS, THROUGH #10 AWG, TO BE SOLID COPPER WITH TYPE THWN /THHN OR XHHW INSULATION UNLESS NOTED OTHERWISE. <br />ALL CONDUCTORS, #8 AWG AND LARGER, TO BE CLASS B STRANDED COPPER WITH TYPE THWN /THHN OR XHHW INSULATION UNLESS NOTED <br />OTHERWISE. <br />E <br />F <br />G <br />H <br />THE COLOR CODE FOR CONDUCTORS SHALL BE BLACK, RED, WHITE, ORANGE (120/24OV, 30, Y) <br />PROVIDE GREEN GROUNDING CONDUCTOR WITH ALL CIRCUITS. <br />P.V.C.CONDUIT SHALL NOT BE USED IN AREAS OF ASSEMBLY. <br />/_1a I V 10 " i7: 1 :y_l == O1T :19-1 0612 MT %y,a <br />ELECTRICAL CONTRACTOR SHALL PROVIDE & INSTALL SMOOTH PLASTIC DEVICE PLATES BRYANT 70000 SERIES LEVITON 85/86000 SERIES OR <br />APPROVED EQUAL. PLATES SHALL BE OF THE SAME COLOR AS THE DEVICE (REFER TO SYMBOL SCHEDULE). EXTERIOR MOUNTED BOXES <br />SHALL HAVE APPROVED WEATHERPROOF PLATES &/OR COVERS. ALL SURFACE INSTALLED BOXES SHALL HAVE STAMPED STEEL DEVICE <br />PLATES. <br />ALL DEVICE OUTLETS SHALL BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED. <br />BALLASTS SUPPLIED WITH RECESSED FLUORESCENT FIXTURES SHALL BE APPROVED BY UNDERWRITERS' LABORATORIES & SHALL BE, <br />ELECTRONIC, ENERGY SAVINGS, PREMIUM GRADE, PROPERLY APPLIED TO EACH INSTALLATION. BALLASTS SUPPLIED WITH SURFACE <br />MOUNTED FLUORESCENT FIXTURES SHALL BE, ELECTRONIC, ENERGY SAVINGS EXTRA LOW HEAT, SUPER PREMIUM TYPES. BALLASTS TO BE <br />AS MANUFACTURED BY ADVANCE, UNIVERSAL, JEFFERSON, OR APPROVED EQUAL. <br />1 I 2 I 3 I 4 I 5 <br />VA <br />AREA r'E ` ^' ^ °" <br />EXISTING BUILDING NOTES <br />1. WHERE INDICATED REMOVE ALL CONDUIT, WIRING, AND ELECTRICAL <br />EQUIPMENT, INCLUDING PREVIOUSLY ABANDONED, RENDERED <br />USELESS BY CONSTRUCTION. <br />2. EXISTING WIRING, DEVICES, ELECTRICAL PANELS, ETC., ARE SHOWN <br />LIGHTER AND DASHED. <br />3. EXISTING WIRING AND RACEWAYS TO BE REUSED WHERE POSSIBLE <br />OR PRACTICAL, AND EXISTING WIRING IS FOUND TO BE IN GOOD <br />CONDITION; REPLACE ANY EXISTING WIRING FOUND TO BE IN POOR <br />CONDITION. ALL NEW INSTALLATIONS SHALL USE NEW WIRE, TYPICAL. <br />4. ALL MATERIALS REMOVED AND NOT TO BE REUSED ARE TO BE <br />DISPOSED OF PER OWNER'S INSTRUCTIONS. <br />5. ALL FIXTURES ARE 120V UNLESS INDICATED OTHERWISE BY CIRCUIT <br />DESIGNATOR. <br />GENERAL NOTES FOR ELECTRICAL DEMOLITION <br />KEY PLAN <br />NOT TO SCALE <br />1. FIELD VERIFY ALL EXISTING CONDITIONS AND NOTIFY ARCHITECT OF ANY DISCREPANCIES ON DRAWINGS. <br />2. UNLESS OTHERWISE NOTED, THE OWNER RETAINS THE RIGHT TO RETAIN ALL ITEMS AND /OR MATERIALS IN GOOD <br />CONDITION FOLLOWING REMOVAL AND /OR DEMOLITION. OTHERWISE, THE CONSTRUCTION MANAGER SHALL <br />DISPOSE OF ALL OTHER ITEMS AND MATERIALS IN A LEGAL FASHION. <br />3. IF ANY ASBESTOS - CONTAINING MATERIAL IS SUSPECTED, G.C. SHALL STOP DEMOLITION AND CONTACT THE <br />OWNER'S REPRESENTATIVE IMMEDIATELY. THE OWNER SHALL CONTRACT WITH AN ASBESTOS ABATEMENT <br />CONTRACTOR UNDER A SEPARATE CONTRACT FOR THE REMOVAL OF ALL EXISTING ASBESTOS - CONTAINING <br />MATERIAL, SHOULD ANY BE ENCOUNTERED. <br />4. FOR WALL MOUNTED DEVICES: (TYPICALLY RECEPTACLES, DATA /TV OUTLETS & LIGHT SWITCHES) UNLESS <br />SPECIFICALLY IDENTIFIED BY DEMOLITION NOTE, WALL MOUNTED DEVICES ARE TO BE REMOVED. <br />5. FOR CEILING MOUNTED DEVICES: (TYPICALLY LIGHTING FIXTURES EXIT LIGHTS, WIRELESS TRANSMITTERS, <br />CAMERAS, SMOKE DETECTORS, SPEAKERS, ETC.) UNLESS NOTED OTHERWISE IN DEMOLITION NOTES, CEILING <br />DEVICES ARE TO BE REMOVED. <br />6. LIGHTING, POWER, & DATA - CONTRACTOR MAY REUSE EXISTING CONDUIT AND WIRING TO THE EXTENT POSSIBLE <br />IN PROVIDING A COMPLETE AND OPERABLE SYSTEM. CONTRACTOR IS TO PROVIDE ALL LABOR & MATERIALS, <br />INCLUDING BUT NOT LIMITED TO DEVICES, BOXES, CONDUIT, AND WIRING FROM ALL DEVICES TO APPROPRIATE <br />DISTRIBUTION /CONTROL PANEL IN ORDER TO PROVIDE A COMPLETE AND OPERABLE SYSTEM. CONTRACTOR TO <br />FIELD VERIFY ALL EXISTING QUANTITIES AND LOCATIONS & COORDINATE CLOSELY WITH OWNER. <br />7. E.C. TO TAKE CARE IN REMOVING, TAGGING, & STORING DEVICES DURING DEMO PHASE, & REPLACING DEVICES TO <br />BE REUSED DURING NEW CONSTRUCTION PHASE. EXISTING CEILING MOUNTED DEVICES TO BE REINSTALLED AS <br />CLOSE AS POSSIBLE TO ORIGINAL LOCATION. PROVIDE MATERIAL AND LABOR FOR EXTENDING CONDUIT & WIRING, <br />AS REQUIRED, FOR REINSTALLATION. ENSURE PROPER OPERATION AFTER CONSTRUCTION. <br />8. WHERE RECEPTACLES ARE REMOVED, ELECTRICAL CONTRACTOR TO REMOVE EXISTING RECEPTACLE DEVICE, <br />BOX, CONDUIT AND WIRING BACK TO IT'S SOURCE. WHERE CIRCUIT FEEDING RECEPTACLE TO BE REMOVED ALSO <br />FEEDS RECEPTACLES THAT ARE TO REMAIN, ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, WIRING AND <br />BOXES AS REQUIRED TO RE -FEED EXISTING RECEPTACLES, AS REQUIRED, FOR PROPER OPERATION. SEE <br />INSTALLATION DRAWINGS AND PANEL SCHEDULES FOR ADDITIONAL CIRCUITING INFORMATION. <br />9. WHERE LIGHTING FIXTURES AND ASSOCIATED SWITCHING ARE REMOVED, ELECTRICAL CONTRACTOR TO REMOVE <br />EXISTING FIXTURE, SWITCH, SWITCH BOX, CONDUIT AND WIRING BACK TO IT'S SOURCE. WHERE CIRCUIT FEEDING <br />FIXTURE(S) TO BE REMOVED ALSO FEEDS FIXTURE(S) THAT ARE TO REMAIN, ELECTRICAL CONTRACTOR SHALL <br />PROVIDE CONDUIT, WIRING AND BOXES AS REQUIRED TO RE -FEED EXISTING FIXTURE(S), AS REQUIRED, FOR <br />PROPER OPERATION. SEE INSTALLATION DRAWINGS AND PANEL SCHEDULES FOR ADDITIONAL CIRCUITING <br />INFORMATION. <br />10. WHERE JB'S, PULL BOXES, CONDUIT, OR OTHER ELECTRICAL DEVICES ARE FOUND WITH WIRING AND WITHOUT <br />COVERS, E.C. TO PROVIDE COVERS, AND /OR CAPS. WHERE JB'S, PULL BOXES, CONDUIT, OR OTHER ELECTRICAL <br />DEVICES ARE FOUND WITHOUT WIRING, E.C. TO REMOVE BACK TO SOURCE OR NEAREST POPULATED JUNCTION. <br />ELECTRICAL SYMBOL SCHEDULE <br />ALL SYMBOLS MAY NOT BE USED <br />SYMBOL DESCRIPTION MOUNTING <br />@ Exhaust fan See Mech'I. Dwgs. <br />@ Pump See Plumbing & Mech. Dwgs. <br />Motor See Mech'I. Dwgs. <br />0 Electrical panelboard, see panel schedule for description. 6' -6" to top <br />6 I 7 <br />ABBREVIATIONS <br />ACT ..............ABOVE <br />Home run to panelboard. Arrowheads indicate number of <br />As <br />Required <br />AFF ..............ABOVE <br />circuits. <br />AHU ............. <br />AIR HANDLER UNIT <br />AFG ..............ABOVE FINISHED GRADE <br />Disconnect switch, 250 VAC Size as shown. Where <br />As <br />Required, <br />EC ................ELECTRICAL <br />exposed to weather shall be NEMA 3R. <br />no <br />higher than <br />EWH .............ELECTRIC <br />Shall be Square "D" safety switch or equal <br />6' -6" <br />AFF <br />GC ............... <br />Junction box as manufactured by RACO, Steel City, or <br />GWH .............GAS <br />WALL HEATER <br />MC ............... <br />Universal. Size as applicable or required. <br />MCCB ........... <br />MOLDED CASE CIRCUIT BREAKER <br />AFF <br />Above finished floor <br />- - <br />- -- <br />AFG <br />Above finished grade <br />- - <br />- -- <br />AHU <br />Air Handler Unit <br />- - <br />- -- <br />BFG <br />Below finished grade <br />- - <br />- -- <br />E.C. <br />Electrical Contractor <br />- - <br />- -- <br />FDS <br />Fused Disconnet Switch <br />----- <br />M.C. <br />Mechanical Contractor <br />- - <br />- -- <br />P.C. <br />Plumbing Contractor <br />- - <br />- -- <br />6 I 7 <br />ABBREVIATIONS <br />ACT ..............ABOVE <br />COUNTER TOP <br />ATS ..............AUTOMATIC <br />TRANSFER SWITCH <br />AFF ..............ABOVE <br />FINISHED FLOOR <br />AHU ............. <br />AIR HANDLER UNIT <br />AFG ..............ABOVE FINISHED GRADE <br />BCT ..............BELOW <br />COUNTER TOP <br />CLG ..............CEILING <br />EC ................ELECTRICAL <br />CONTRACTOR <br />EWC ............. <br />ELECTRIC WATER COOLER <br />EWH .............ELECTRIC <br />WALL HEATER <br />FDS ..............FUSED <br />DISCONNECT SWITCH <br />GC ............... <br />GENERAL CONTRACTOR <br />GWH .............GAS <br />WALL HEATER <br />MC ............... <br />MECHANICAL CONTRACTOR <br />MCCB ........... <br />MOLDED CASE CIRCUIT BREAKER <br />NFD ............. <br />NON —FUSED DISCONNECT SWITCH <br />PC ............... <br />PLUMBING CONTRACTOR <br />RTU ..............ROOFTOP <br />UNIT <br />UG ............... <br />UNDERGROUND <br />WCP .............WATER <br />CIRCULATION PUMP <br />XFMR........... <br />TRANSFORMER <br />8 <br />Q <br />0 <br />C <br />u <br />E <br />F <br />G <br />H <br />li <br />K 4 R AA <br />ENGINEERS <br />Reece, Noland & McElrath, Inc. <br />94 Main Street <br />Canton, North Carolina 28716 <br />PHONE: 828 - 492 -0677 <br />FAX: 828 - 492 -1054 <br />MAIL @RNM- ENGINEERS.COM <br />WWW.RNM- ENGINEERS.COM <br />NC CERT. N0. C -0149 <br />© 2018 <br />SEALS: <br />Ld <br />p� ZO W Q <br />� W <br />0 C_) w <br />` \ \UlIS[1t[1�J�� <br />��� CA/�C. <br />` \� .C94GCe <br />� w w <br />O�QUZ <br />O�'o� SS <br />z (n U O <br />cn O ow <br />—U=wz <br />ZZ �c <br />° <br />P o <br />C-D z� ~Nw <br />§i °° vi o w <br />� w W <br />(033_223 <br />QSyZi <br />✓r! aoaeoca <br />\� �� <br />Cf)��o� <br />= Cn <br />z <br />0 <br />0 <br />U <br />r <br />r I— z <br />Q Q:� <br />U <br />z::D <br />0 <br />C) <br />LU <br />o Q o <br />zJ <br />Q o <br />Q m <br />cr z <br />W J <br />0� <br />LU <br />W <br />U <br />w <br />C) <br />0 <br />REVISIONS /SUBMISSIONS <br />NO <br />DATE <br />ISSUED FOR <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 <br />7 <br />8 <br />SHEET TITLE: <br />ELECTRICAL SYMBOLS, <br />NOTES & SPECIFICATIONS <br />ISSUED FOR: <br />CONSTRUCTION <br />DRAWN BY: <br />JWC <br />DRAWING NO. <br />APPROVED BY: <br />JSD <br />PROJECT #: <br />2018034 <br />E1.0 <br />DATE: <br />05/24/2018 <br />OF 2 SHEETS <br />