<br />GENERAL ELECTRICAL NOTES
<br />3
<br />1. THIS CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONTRACTORS AND TRADES TO LOCATE HIS WORK TO AVOID CONFLICTS.
<br />2. THIS CONTRACTOR SHALL NOT UTILIZE "THRU TYPE OUTLET BOXES WHERE DEVICES ARE SHOWN BACK TO BACK IN SOUND
<br />INSULATED OR SOUND SECURE AREAS, TYPICAL.
<br />3. SMOKE DETECTORS FOR AIR HANDLING UNITS SHALL BE LOCATED IN AIR DUCTS OBSERVING ALL APPLICABLE CODES AND
<br />ORDINANCES. ELECTRICAL CONTRACTOR SHALL COORDINATE THE EXACT LOCATION AND REQUIREMENTS OF INSTALLATION WITH
<br />MECHANICAL CONTRACTOR PRIOR TO CUTTING DUCTWORK. LOCATE THE DETECTOR INDICATOR /RESET DEVICE IN AN ACCESSIBLE
<br />LOCATION AS DIRECTED BY THE ARCHITECT AND LABEL AS TO AREA AND ROOFTOP UNIT SERVED, TYPICAL.
<br />4. MOUNTING HEIGHTS GIVEN ARE TO TOP OF OUTLET BOX, UNLESS OTHERWISE NOTED. HEIGHTS MAY BE ADJUSTED TO MATCH
<br />MASONRY JOINTS, AND MUST COMPLY WITH NORTH CAROLINA STATE BUILDING CODE VOLUME 1 -C.
<br />5. ALL CONDUITS AND RACEWAYS ARE TO BE CONCEALED UNLESS OTHERWISE NOTED OR APPROVED BY THE DESIGNER.
<br />6. ALL CONDUITS, SLEEVES, INSERTS, OUTLET BOXES, AND OTHER ROUGH -IN MATERIALS SHALL BE INSTALLED AS BUILDING
<br />CONSTRUCTION PROGRESSES.
<br />7. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
<br />8. IN RECEIVING AND OTHER AREAS WHERE ITEMS SUCH AS EXIT SIGN, FIRE ALARM DEVICES, ETC., ARE SUBJECT TO DAMAGE, PROVIDE
<br />AND INSTALL GUARDS AS RECOMMENDED BY THE MANUFACTURER.
<br />9. THE SYMBOL " " DENOTED GROUNDING CONDUCTOR, TYPICAL UNLESS OTHERWISE NOTED, ALL CONDUITS SHALL BE 3/4" MINIMUM.
<br />10. ALL PANEL DIRECTORIES SHALL BE TYPED AS TO THE LOAD SERVED AND USING THE OWNER'S NUMBERING SYSTEM.
<br />11. ALL WIRING TROUGHS SHALL BE A MINIMUM OF 8" DEEP.
<br />12. ALL ELECTRICAL PANELS TO BE LABELED WITH PHENOLIC LABELS.
<br />GENERAL NOTES FOR ELECTRICAL DEMOLITION
<br />1. LIGHTING, POWER, DATA, INTERCOM, SECURITY - CONTRACTOR MAY REUSE EXISTING CONDUIT & WIRING TO THE EXTENT
<br />POSSIBLE IN PROVIDING A COMPLETE & OPERABLE SYSTEM. CONTRACTOR IS TO PROVIDE ALL LABOR & MATERIALS, INCLUDING
<br />BUT NOT LIMITED TO DEVICES, BOXES, CONDUIT, & WIRING FROM ALL DEVICES TO APPROPRIATE DISTRIBUTION /CONTROL
<br />PANEL IN ORDER TO PROVIDE A COMPLETE & OPERABLE SYSTEM. CONTRACTOR TO FIELD VERIFY ALL EXISTING QUANTITIES &
<br />LOCATIONS & COORDINATE CLOSELY WITH OWNER.
<br />2. E.C. TO TAKE CARE IN REMOVING, TAGGING, & STORING DEVICES DURING DEMO PHASE, & REPLACING DEVICES TO BE REUSED
<br />DURING NEW CONSTRUCTION PHASE. EXISTING CEILING MOUNTED DEVICES TO BE REINSTALLED AS CLOSE AS POSSIBLE TO
<br />ORIGINAL LOCATION. PROVIDE MATERIAL & LABOR FOR EXTENDING CONDUIT & WIRING, AS REQUIRED, FOR REINSTALLATION.
<br />ENSURE PROPER OPERATION AFTER CONSTRUCTION.
<br />3, WHERE RECEPTACLES ARE REMOVED, ELECTRICAL CONTRACTOR TO REMOVE EXISTING RECEPTACLE DEVICE, BOX, CONDUIT &
<br />WIRING BACK TO IT'S SOURCE. WHERE CIRCUIT FEEDING RECEPTACLE TO BE REMOVED ALSO FEEDS RECEPTACLES THAT ARE
<br />TO REMAIN, ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, WIRING & BOXES AS REQUIRED TO RE -FEED EXISTING
<br />RECEPTACLES, AS REQUIRED, FOR PROPER OPERATION.
<br />EXISTING BUILDING NOTES
<br />1. WHERE NOTED, REMOVE ALL CONDUIT, WIRING, & ELECTRICAL EQUIPMENT,
<br />INCLUDING PREVIOUSLY ABANDONED, RENDERED USELESS BY CONSTRUCTION.
<br />2. ALL MATERIALS REMOVED & NOT TO BE REUSED ARE TO BE DISPOSED OF PER
<br />OWNER'S INSTRUCTIONS.
<br />3. EXISTING WIRING & RACEWAYS TO BE REUSED WHERE POSSIBLE OR PRACTICAL, &
<br />EXISTING WIRING IS FOUND TO BE IN GOOD CONDITION; REPLACE ANY EXISTING
<br />WIRING FOUND TO BE IN POOR CONDITION. ALL NEW INSTALLATIONS SHALL USE NEW
<br />WIRE, TYPICAL.
<br />4. EXISTING WIRING, DEVICES, ELECTRICAL PANELS, ETC. ARE SHOWN LIGHTER &
<br />DASHED.
<br />4 1 5
<br />ELECTRICAL SPECIFICATIONS
<br />IT IS THE INTENT OF THESE SPECIFICATION FOR THE ELECTRICAL CONTRACTOR TO FURNISH A COMPLETE ELECTRICAL
<br />SYSTEM, FULLY ADJUSTED, & READY FOR USE.
<br />ALL ELECTRICAL WORK TO BE DONE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL
<br />CODE OBSERVING ALL STATE AND LOCAL CODES.
<br />ELECTRICAL CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS & PAY ALL SALES TAXES, UTILITY
<br />COMPANY CHARGES FOR SERVICE, PERMITS, FEES, & OTHER COSTS IN CONNECTION WITH HIS WORK.
<br />ELECTRICAL CONTRACTOR TO ENSURE THAT ALL MATERIAL & EQUIPMENT FURNISHED FOR THIS PROJECT SHALL BE U.L.
<br />LISTED.
<br />THE MATERIAL & EQUIPMENT HAS BEEN CAREFULLY SELECTED FOR THIS PROJECT & THE ELECTRICAL CONTRACTOR IS
<br />EXPECTED TO PROVIDE ALL ITEMS AS CLOSELY AS POSSIBLE TO THE SPECIFICATIONS & AS CALLED FOR ON THE DRAWINGS.
<br />ELECTRICAL CONTRACTOR SHALL SUBMIT THREE (3) SETS OF EQUIPMENT DATA SHOP DRAWINGS TO THE ENGINEER FOR ALL
<br />ITEMS TO BE FURNISHED & INSTALLED FOR APPROVAL.
<br />ELECTRICAL CONTRACTOR SHALL INCLUDE IN THE WORK WITHOUT EXTRA COST TO THE OWNER ANY LABOR MATERIALS
<br />SERVICES, APPARATUS, DRAWINGS, INCIDENTAL CONSTRUCTION WORK, ETC., IN ORDER TO COMPLY WITH ALL APPLICABLE
<br />LAWS, ORDINANCES, & REGULATIONS, WHETHER. OR NOT SHOWN ON DRAWINGS AND /OR SPECIFIED. NO CLAIM FOR EXTRAS
<br />WILL BE APPROVED WITHOUT PRIOR COORDINATION FOR CONFLICTS BY CONTRACTOR, & WRITTEN REQUEST & APPROVAL
<br />PRIOR TO PERFORMING WORK.
<br />ALL WORK & EQUIPMENT TO BE GUARANTEED BY CONTRACTOR FOR ONE (1) YEAR.
<br />UPON COMPLETION OF ALL WORK & ALL TESTS, ELECTRICAL CONTRACTOR SHALL INSTRUCT THE OWNER OR HIS
<br />REPRESENTATIVE FULLY IN THE OPERATIONS, ADJUSTMENTS, & MAINTENANCE OF EQUIPMENT FURNISHED. ELECTRICAL
<br />CONTRACTOR SHALL PROVIDE OWNER WITH MAINTENANCE SCHEDULE FOR THE PRINCIPAL ITEMS OF EQUIPMENT
<br />FURNISHED. MANUFACTURER'S ADVERTISING LITERATURE OR CATALOGS WILL NOT BE ACCEPTABLE.
<br />ALL MATERIALS & EQUIPMENT TO BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS & GOOD RECOMMENDED PRACTICES.
<br />ELECTRICAL CONTRACTOR SHALL GIVE FULL COOPERATION TO OTHER TRADES. WHERE THE WORK OF ELECTRICAL
<br />CONTRACTOR WILL BE INSTALLED IN CLOSE PROXIMITY TO, OR WILL INTERFERE WITH WORK OF OTHER TRADES, HE SHALL
<br />ASSIST IN WORKING OUT SPACE CONDITIONS TO MAKE SATISFACTORY ADJUSTMENTS. IF ELECTRICAL CONTRACTOR
<br />INSTALLS HIS WORK BEFORE COORDINATING WITH OTHER. TRADES, HE SHALL MAKE THE NECESSARY CHANGES IN HIS WORK
<br />TO CORRECT THE CONDITION WITHOUT EXTRA CHARGE.
<br />THE DRAWINGS ARE DIAGRAMMATIC & INDICATE THE GENERAL ARRANGEMENTS OF SYSTEMS & WORK INCLUDED IN THE
<br />CONTRACT. THE DRAWINGS ARE NOT TO BE SCALED.
<br />ELECTRICAL CONTRACTOR TO VERIFY EXACT LOCATION OF EQUIPMENT, ROUTING PIPE, ETC., & WORK CLOSELY WITH OTHER
<br />TRADES TO AVOID CONFLICTS.
<br />ELECTRICAL CONTRACTOR TO LOCATE & INSTALL ELECTRICAL CONTROL PANELS IN SUITABLE LOCATION WITH APPROPRIATE
<br />CLEARANCES & OVERLOAD PROTECTION FOR ALL ITEMS REQUIRED.
<br />ELECTRICAL CONTRACTOR MAY COMBINE CONDUITS WHERE APPLICABLE, BUT MUST HOOK UP ITEMS TO PROPER CIRCUITS
<br />AS SHOWN.
<br />THE OWNER., ARCHITECT & ELECTRICAL CONTRACTOR TO COORDINATE FOR PROPER CUTOUT HOLES, ALL STUB -UPS &
<br />JUNCTION BOXES, & TO VERIFY LOCATIONS.
<br />ALL CONDUCTORS TO BE COPPER WITH TYPE THHW OR XHHW INSULATION UNLESS OTHERWISE NOTED.
<br />WHERE ALUMINUM CONDUCTORS ARE UTILIZED THEY SHALL BE TERMINATED WITH BURNDY HY -PLUG, HYDRAULIC
<br />COMPRESSION TERMINATORS.
<br />EXTERIOR MOUNTED BOXES SHALL HAVE APPROVED WEATHERPROOF PLATES &/OR COVERS.
<br />ALL SURFACE INSTALLED BOXES SHALL HAVE NYLON DEVICE PLATES.
<br />ALL DEVICE OUTLETS SHALL BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED.
<br />ALL FIXED ELECTRICAL EQUIPMENT INCLUDING RECEPTACLES SHALL BE LABELED WITH A REFERENCE TO THE CIRCUIT &
<br />PANEL OF ORIGIN. ALL PANELS SHALL BE LABELED WITH PANEL NAME & SOURCE OF SUPPLY. ALL PANEL DIRECTORIES SHALL
<br />USE ROOM IDENTIFICATIONS TO BE SUPPLIED BY THE OWNER, NOT THE ROOM NAMES & NUMBERS ON THE DRAWINGS.
<br />ALL LABELS REFERRING TO EMERGENCY POWER SHALL BE PER FACILITIES CURRENT COLOR CODE.
<br />CONDUIT, WIRING, & ELECTRICAL EQUIPMENT & DEVICES CAUSED TO BE ABANDONED OR RENDERED USELESS BY
<br />CONSTRUCTION SHALL BE REMOVED BACK TO THE SOURCE. IN ADDITION, CONDUIT, WIRING, ELECTRICAL EQUIPMENT &
<br />DEVICES DISCOVERED ABANDONED WITHIN THE LIMITS OF CONSTRUCTION SHALL BE REMOVED BACK TO THE SOURCE, EVEN
<br />IF THIS SHOULD INVOLVE REMOVAL OUTSIDE THE LIMITS OF CONSTRUCTION.
<br />SUPPLEMENTAL ELECTRICAL SPECIFICATIONS
<br />ALL PENETRATIONS OF RATED PARTITIONS, FLOOR SLABS BY EITHER NEW OR EXISTING CONDUITS SHALL BE FIRE CAULKED
<br />OR CLOSED BY APPROVED U.L. METHODS BY THE ELECTRICAL CONTRACTOR.
<br />ELECTRICAL CONTRACTOR TO MAINTAIN A COMPLETE SET OF CONSTRUCTION DOCUMENTS WITH AS -BUILT CONDITIONS &
<br />TURN OVER TO THE OWNER.
<br />ALL No. 10 & No. 12 CONDUCTORS FOR RECEPTACLES & LIGHTING CIRCUITS SHALL BE STRANDED COPPER.
<br />ALL TERMINATIONS SHALL BE NUMBERED AND LABELED.
<br />ALL CONDUCTORS SHALL BE MARKED WITH CIRCUIT NUMBER WHEN TERMINATING AT THE PANELBOARD.
<br />ALL 15A, 20A, & 30 AMPERE HOME RUN CONDUCTORS EXCEEDING 150' SHALL BE INCREASED ONE WIRE SIZE TO COMPENSATE
<br />FOR VOLTAGE DROP. ADJUST CONDUIT SIZE ACCORDINGLY.
<br />ALL CONDUIT COUPLINGS AND CONNECTORS SHALL BE "T &B" INSULATED THROAT COMPRESSION TYPE. NO "INDENTER" OR
<br />SET SCREW DEVICES WILL BE ALLOWED, TYPICAL.
<br />ALL PENETRATIONS THROUGH FLOOR SLAB OR RATED ASSEMBLIES SHALL BE APPROVED BY THE OWNER, ARCHITECT &
<br />STRUCTURAL ENGINEER PRIOR TO CUTTING OR BORING. ALL PENETRATIONS SHALL BE SLEEVED, FIRE CAULKED & FINISHED
<br />WITH COLLAR ON BOTH SIDES. ANY PENETRATION NOT COORDINATED WILL RESULT IN CONTRACTOR BEARING ALL COSTS
<br />ASSOCIATED WITH PATCHING, REPAIRING & REFINISHING AREA TO THE SATISFACTION OF THE OWNER & ENGINEER.
<br />ALL ELECTRICAL "TIE -INS" & "SHUT- DOWNS" SHALL BE COORDINATED WITH THE OWNER PRIOR TO COMMENCEMENT OF
<br />WORK. CONTRACTOR SHALL NOTIFY OWNER A MINIMUM OF 72 HOURS PRIOR TO ANY SUCH WORK.
<br />ALL EXISTING EQUIPMENT, CONDUIT, WIRING, BOXES ETC. RENDERED UNUSED, SHALL BE REMOVED & DISPOSED OF AS
<br />DIRECTED BY THE OWNER.
<br />0
<br />7
<br />ELECTRICAL SYMBOL SCHEDULE
<br />Duct - Mounted Smoke Detector. Match existing. Connect to
<br />SD D existing Fire Alarm system.
<br />ABBREVIATIONS
<br />ACT ..............ABOVE
<br />NOTE: EXISTING DEVICES SHOWN LIGHTER AND WITH DASHED LINES.
<br />ATS ..............AUTOMATIC
<br />ALL SYMBOLS MAY NOT BE USED
<br />AFF ..............ABOVE
<br />FINISHED FLOOR
<br />SEE SPECIFICATIONS FOR A COMPLETE LISTING OF MFG'S
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />S
<br />Switch, single pole, 20 amp, commercial duty, Bryant #4901
<br />Leviton #1221 120/277
<br />4' -0" AFF t Top
<br />SEALS:
<br />or volt rated.
<br />or as noted
<br />EWC .............ELECTRIC
<br />Receptacle, industrial grade, duplex, Bryant #5252
<br />EWH .............ELECTRIC
<br />WALL HEATER
<br />Leviton #5252, 15 ampere rated, grounding type,
<br />1' -6" AFF
<br />GC ...............GENERAL
<br />2 pole, 3 wire, 125 volts.
<br />GWH .............GAS
<br />WALL HEATER
<br />Receptacle, same as above except mounting height.
<br />0' -6" ACT or
<br />as noted
<br />MCCB ...........
<br />Double Duplex Receptacle, (2) Bryant #5252 or
<br />1' -6" AFF
<br />-FUSED DISCONNECT SWITCH
<br />(2) Leviton #5252, 15 ampere rated, grounding type.
<br />unless noted
<br />RTU ..............ROOFTOP
<br />Receptacle, same as above except mounting height.
<br />0' -6" ACT or as noted
<br />UNDERGROUND
<br />Ground fault circuit interrupting receptacle, 15 amp,
<br />1' -6" AFF
<br />XFMR ...........
<br />feed -thru type, standard duty, Bryant #GFR52FT.
<br />®z O
<br />m ww o
<br />Receptacle, same as above except mounting height.
<br />0' -6" ACT or
<br />as noted
<br />VVP
<br />Receptacle, same as above with Weather Proof cover.
<br />V-6" n or
<br />as
<br />as noted
<br />0c)
<br />Receptacle, industrial grade, duplex, Bryant #5362
<br />:1&20A
<br />Leviton #5362, 20 ampere rated, grounding type,
<br />1'4' AFF
<br />2 pole, 3 wire, 125 volts.
<br />U OW
<br />-Cr-20A
<br />Receptacle, same as above except mounting height.
<br />0' -6" ACT or
<br />as noted
<br />30A
<br />Receptacle, Locking, 125 volt rated, 30 amp, 2 pole, 3 wire,
<br />1' -6" AFF
<br />Bryant #70530 -FR with mating plug and cord.
<br />as noted
<br />30A
<br />Receptacle, 250 volt rated, 30 amp, 3 pole, 4 wire,
<br />1' -6" AFF
<br />Bryant #9430 -FR with mating plug and cord.
<br />as noted
<br />New conduit/wiring
<br />- - - --
<br />Home run to panelboard. Arrowheads indicate number of
<br />As Required
<br />circuits.
<br />7
<br />Disconnect switch, 600V. Where exposed to weather shall
<br />As Required,
<br />be NEMA 3R. Square " T safety switch or equal.
<br />no higher than
<br />ELECTRICAL SYMBOLS,
<br />SPECIFICATIONS &
<br />6' -6" AFF
<br />■
<br />Junction box (JB) as manufactured by RACO, Steel City, or
<br />As required
<br />JWC
<br />Universal. Size as applicable or required.
<br />APPROVED BY: I
<br />Fs-s
<br />Surge Suppresser
<br />Mnt, on Service
<br />E1.0
<br />See specifications.
<br />Distribution Eq.
<br />Electrical panelboard, see panel schedule for description.
<br />6-6" to top
<br />Duct - Mounted Smoke Detector. Match existing. Connect to
<br />SD D existing Fire Alarm system.
<br />ABBREVIATIONS
<br />ACT ..............ABOVE
<br />COUNTER TOP
<br />ATS ..............AUTOMATIC
<br />TRANSFER SWITCH
<br />AFF ..............ABOVE
<br />FINISHED FLOOR
<br />AHU .............AIR
<br />HANDLER UNIT
<br />AFG ..............ABOVE
<br />FINISHED GRADE
<br />BCT ..............BELOW
<br />COUNTER TOP
<br />CLG ..............CEILING
<br />SEALS:
<br />EC ................ELECTRICAL
<br />CONTRACTOR
<br />EWC .............ELECTRIC
<br />WATER COOLER
<br />EWH .............ELECTRIC
<br />WALL HEATER
<br />FDS ..............FUSED
<br />DISCONNECT SWITCH
<br />GC ...............GENERAL
<br />CONTRACTOR
<br />GWH .............GAS
<br />WALL HEATER
<br />MC ...............MECHANICAL
<br />CONTRACTOR
<br />MCCB ...........
<br />MOLDED CASE CIRCUIT BREAKER
<br />NFD .............NON
<br />-FUSED DISCONNECT SWITCH
<br />PC ...............
<br />PLUMBING CONTRACTOR
<br />RTU ..............ROOFTOP
<br />UNIT
<br />UG ...............
<br />UNDERGROUND
<br />WCP .............WATER
<br />CIRCULATION PUMP
<br />XFMR ...........
<br />TRANSFORMER
<br />f
<br />1 1 2 1 3 1 4 1 5 1 6 1 7 1 8
<br />11
<br />1.1
<br />C
<br />I
<br />E
<br />F
<br />G
<br />2
<br />RK14
<br />MILSICISILILUS
<br />Reece, Noland & McElrath, Inc.
<br />94 Main Street
<br />Canton, North Carolina 28716
<br />PHONE: 828 - 492 -0677
<br />FAX: 828 - 492 -1054
<br />MAIL@RNM- ENGMEERS.COM
<br />WW W.RNM- ENGINEERS.COM
<br />NC CERT. N0. C -0149
<br />(D 2018
<br />SEALS:
<br />M Z LZ J
<br />O of
<br />Z
<br />}lllil9lf+JJ
<br />��� °4 CA,RO, /�Ji
<br />oOf aUjz
<br />Z(nU�O
<br />cn 0 0 Uj
<br />— U W� U
<br />c� = z
<br />cnw
<br />_ EAL _
<br />v c —
<br />�y /fC'ry °
<br />QONOw
<br />Of M
<br />p
<br />rf�✓}
<br />J 0 v
<br />N v G` o
<br />❑ r�'�
<br />��Q_
<br />C/)
<br />Z
<br />O
<br />U
<br />W Z
<br />O
<br />W�
<br />LL
<br />U
<br />00,
<br />0 _ z
<br />LU
<br />r _
<br />D
<br />®z O
<br />m ww o
<br />G m
<br />J
<br />Z J
<br />z0
<br />LU
<br />0c)
<br />U �
<br />W =
<br />V
<br />Z
<br />U OW
<br />0
<br />W
<br />Q_
<br />REVISIONS /SUBMISSIONS
<br />NO
<br />DATE
<br />ISSUED FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />6
<br />7
<br />8
<br />SHEET TITLE:
<br />ELECTRICAL SYMBOLS,
<br />SPECIFICATIONS &
<br />NOTES
<br />ISSUED FOR:
<br />CONSTRUCTION
<br />DRAWN BY:
<br />JWC
<br />DRAWING NO.
<br />APPROVED BY: I
<br />JSD
<br />PROJECT #:
<br />2017108
<br />E1.0
<br />DATE:
<br />05/07/2018
<br />OF 2 SHEETS