DocuSign Envelope ID: AOD5DO06- 1BO4- 4F7B- 96D7- OF7A4E374317
<br />/1 1 1 2
<br />V
<br />3
<br />4
<br />LEGEND
<br />A CEILING SUPPLY DIFFUSER, TYPE AND CFM INDICATED
<br />275
<br />F CEILING RETURN GRILLE, TYPE AND CFM INDICATED
<br />450
<br />E CEILING EXHAUST GRILLE, TYPE AND CFM INDICATED
<br />95
<br />TYPE CEILING RETURN GRILLE, TYPE AND CFM INDICATED
<br />G"
<br />IU -5 CONCEALED DUCTED INDOOR UNIT
<br />IU 1 I CEILING CASSETTE INDOOR UNIT
<br />C CONDENSATE DRAIN PIPING
<br />R REFRIGERANT PIPING
<br />24X12 RECTANGULAR DUCT, WIDTH x DEPTH
<br />ROUND OR SPIRAL DUCT, DIAMETER
<br />DUCT BALANCE DAMPER
<br />DUCT TRANSITION
<br />DUCT TAKEOFF AT 45 DEGREES(TYPICAL)
<br />DUCT SQUARE ELBOW WITH TURNING VANES
<br />SD DUCT SMOKE DETECTOR (FURNISHED
<br />BY E.C. AND INSTALLED BY M.C.)
<br />UC UNDERCUT DOOR
<br />OT WALL MOUNTED THERMOSTAT / CONTROLLER
<br />FLEXIBL
<br />CONNECTION
<br />GENERAL MECHANICAL DUCTWORK NOTES
<br />CFM
<br />1. THE DRAWINGS SHOW THE LOCATION AND ARRANGEMENT OF PIPING, DUCTS, AND EQUIPMENT, TOGETHER
<br />50
<br />WITH DETAILS OF CONNECTIONS OF CERTAIN PRINCIPAL ITEMS. THE LAYOUT SHOWN SHALL BE FOLLOWED
<br />A
<br />AS CLOSELY AS CIRCUMSTANCES WILL PERMIT, BUT THIS CONTRACTOR SHALL REFER TO ARCHITECTURAL,
<br />50
<br />0 o STRUCTURAL, PLUMBING, AND ELECTRICAL DRAWINGS AND SHALL COOPERATE FULLY WITH OTHER
<br />50
<br />CONTRACTORS AND TRADES WHILE INSTALLING DUCTS, PIPING, AND OTHER EQUIPMENT BECAUSE OF CLOSE
<br />50
<br />=II I SPACE LIMITS. IN CASE OF CONFLICT, NOTIFY DESIGNER BEFORE PROCEEDING WITH INSTALLATION. REFER
<br />40
<br />TO ARCHITECTURAL DRAWINGS FOR EXACT BUILDING DIMENSIONS AND LOCATIONS OF PARTITION WALLS,
<br />40
<br />DOORS, CHASES, CASEWORK, ETC. DO NOT SCALE MECHANICAL DRAWINGS FOR SUCH DIMENSIONS.
<br />35
<br />IU -1 -09
<br />20
<br />Cn m 2. THIS CONTRACTOR SHALL PROVIDE AND INSTALL ALL OFFSETS, FITTINGS, AND ACCESSORIES THAT MAY BE
<br />40
<br />v REQUIRED FOR A COMPLETE AND PROPER INSTALLATION, OR RECOMMENDED BY THE EQUIPMENT
<br />WHETHER OR NOT THEY ARE SPECIFICALLY SHOWN OR SPECIFIED.
<br />20
<br />IU -1 -12
<br />IMANUFACTURER,
<br />IU -1 -13
<br />c� 3. DUCTWORK SIZES INDICATED ON DRAWINGS ARE FREE INSIDE DIMENSIONS.
<br />IU -1 -14
<br />4. MAXIMUM LENGTH OF FLEXIBLE DUCT IS SIX FEET (6).
<br />IU -1 -15
<br />ra
<br />IU -1 -16
<br />5. ALL VALVES, DAMPERS, CONTROLS, AND OTHER ITEMS REQUIRED FOR OPERATION OR MAINTENANCE ARE TO
<br />IU -1 -17
<br />BE ACCESSIBLE.
<br />I
<br />IU -1 -18
<br />20
<br />B
<br />6. ALL SLEEVES, OUTLET BOXES, AND OTHER ROUGH -INS FOR SUCH ITEMS AS FIRE DAMPERS, PIPE
<br />IU -1 -20
<br />PENETRATIONS, LOUVERS, AND CONTROL ITEMS SHALL BE INSTALLED AS THE BUILDING CONSTRUCTION
<br />IU -1 -21
<br />PROGRESSES. ALL FLOOR /ROOF /PLATFORM PENETRATIONS TO BE CAST IN PLACE SLEEVES.
<br />IU -1 -22
<br />7. PROVIDE AND INSTALL VOLUME CONTROL DAMPERS AT ALL SUPPLY MAIN AND BRANCH DUCT TAKE -OFFS.
<br />IU -1 -23
<br />8. PROVIDE AND INSTALL DUCT ACCESS DOORS AT ALL SMOKE DAMPERS, FIRE DAMPERS, AND DUCT SMOKE
<br />IU -1 -24
<br />DETECTORS. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR DUCT SMOKE DETECTOR LOCATIONS.
<br />IU -1 -25
<br />N
<br />IU -1 -26
<br />9. THIS CONTRACTOR SHALL TAKE FIELD MEASUREMENTS BEFORE FABRICATING ANY DUCTS TO ENSURE THAT
<br />IU -1 -27
<br />10
<br />DUCT SIZES SHOWN WILL FIT INTO AVAILABLE SPACE. IN CASE OF CONFLICT, NOTIFY THE DESIGNER BEFORE
<br />PROCEEDING.
<br />_
<br />0
<br />i 10. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
<br />INSTRUCTIONS.
<br />=II
<br />11. COORDINATE LOCATIONS OF ALL FLOOR DRAINS WITH PLUMBING CONTRACTOR, PRIOR TO SLABS BEING
<br />POURED.
<br />C
<br />N o 12. COORDINATE EXACT LOCATION FOR ALL CEILING DIFFUSERS /GRILLES WITH ARCHITECTURAL REFLECTED
<br />�? CEILING PLAN AND ELECTRICAL CONTRACTOR'S LIGHTING LAYOUT.
<br />�m 13. ALL EMS SENSORS AND OTHER FIELD DEVICES MOUNTED ON WALLS TO BE PROTECTED FROM DAMAGE AS
<br />REQUIRED - INSTALL LEXAN COVERS, WIRE GUARDS, OR SIMILAR AS REQUIRED. COORDINATE CONDITIONS IN
<br />�t THE FIELD.
<br />�N
<br />14. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING TO THE GENERAL CONTRACTOR
<br />Io THE QUANTITY, SIZE AND LOCATIONS OF ALL ACCESS DOORS IN WALLS, DRYWALL CEILINGS, ETC. FOR
<br />ACCESS TO VALVES, BALANCE DAMPERS OR OTHER EQUIPMENT AS REQUIRED. COORDINATE THIS WORK
<br />WITH THE REFLECTED CEILING PLANS. ALL VALVES OR OTHER DEVICES LOCATED ABOVE THE CEILING SHALL
<br />BE LOCATED IN ACCESSIBLE CEILINGS WHEREVER POSSIBLE. VERIFY LOCATION OF ALL VALVES IN
<br />INACCESSIBLE CEILINGS OR CHASES WITH THE ARCHITECT PRIOR TO INSTALLATION.
<br />15. COORDINATE EXACT SIZE, LOCATION, APPURTENANCES, ETC. FOR ALL ROOF OPENINGS.
<br />_
<br />16. REFER TO MANUFACTURER'S DETAILS FOR PERMISSIBLE LOCATIONS AND METHODS FOR HANGING
<br />DUCTWORK FROM STRUCTURE. ALL DUCTWORK HANGERS TO BE WITHIN 6" OF PANEL POINTS OF JOISTS. DO
<br />D
<br />=� NOT WELD DUCT HANGERS /SUPPORTS TO STRUCTURE WITHOUT PRIOR APPROVAL FROM THE ENGINEER AND
<br />o
<br />GENERAL CONTRACTOR.
<br />17. COORDINATE EXACT SIZES REQUIRED FOR ALL OPENING FOR DUCTWORK AND PIPING WITH SPACE
<br />to REQUIREMENTS AND EXISTING CONDITIONS PRIOR TO FRAMING FOR THE PENETRATIONS.
<br />N
<br />�
<br />2
<br />■
<br />GENERAL MECHANICAL PIPING NOTES
<br />1. CONTRACTOR TO SLOPE ALL CONDENSATE DRAIN PIPING ABOVE CEILINGS, UNDER SLAB, AND BELOW GRADE
<br />-1/8" PER FOOT (MINIMUM).
<br />2. IN MECHANICAL ROOMS AND ON MECHANICAL PLATFORMS, ROUTE ALL A/H UNIT CONDENSATE DRAIN PIPING
<br />TO CLOSEST FLOOR OR HUB DRAIN UNLESS SHOWN OTHERWISE.
<br />3. REFER TO STRUCTURAL DRAWINGS AND DETAILS FOR PERMISSIBLE LOCATIONS AND METHODS FOR HANGING
<br />PIPING FROM STRUCTURE. ALL PIPE HANGERS TO BE WITHIN 6" OF PANEL POINTS OF JOISTS. DO NOT WELD
<br />E
<br />PIPE HANGERS /SUPPORTS TO STRUCTURE WITHOUT PRIOR APPROVAL FROM THE ENGINEER.
<br />REFRIGERANT PIPING / POWER AND CONTROL WIRING NOTES:
<br />1. VRV SYSTEM PIPING AND ALL POWER / CONTROL WIRING AND CONDUIT NOT SHOWN ON THESE PLANS. EACH
<br />VRV HP MANUFACTURER HAS DIFFERENT PIPING REQUIREMENTS, CONTRACTOR TO COORDINATE WITH
<br />SPECIFIC EQUIPMENT MANUFACTURER / VENDOR IN REGARDS TO EXACT REFRIGERANT PIPING ROUTING,
<br />QUANTITY, AND SIZING, AS WELL AS ACCESSORIES (REFNET JOINTS, ELBOWS, HEADERS, BRANCH SELECTOR
<br />BOXES, EXPANSION LOOPS, ETC.) AS TO QUANTITIES AND LOCATIONS. EQUIPMENT MANUFACTURER /
<br />VENDOR TO FURNISH TO THE CONTRACTOR (PRIOR TO BIDDING) COMPLETE EQUIPMENT, REFRIGERANT
<br />PIPING, AND POWER / CONTROL WIRING AND CONDUIT LAYOUT DRAWINGS; COMPLETE SUBMITTALS OF ALL
<br />EQUIPMENT, ACCESSORIES, DEVICES, ETC.; COMPLETE LIST OF ALL REQUIRED MATERIALS (TAKE -OFFS) SUCH
<br />AS REFRIGERANT PIPING (AMOUNT AND SIZE), REFNET JOINTS, ELBOWS, HEADERS, BRANCH SELECTOR
<br />BOXES, ETC.. INFORMATION TO BE SUFFICIENT FOR CONTRACTOR TO PERFORM DETAILED TAKE -OFFS FOR
<br />BIDDING AND INSTALLATION. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
<br />PROVIDING A COMPLETE AND FUNCTIONAL SYSTEM. DRAWINGS TO SHOW LOCATIONS, PROPOSED ROUTING,
<br />F
<br />SIZES, FITTINGS, ACCESSORIES, ETC.. DRAWING PACKAGE TO BE FURNISHED AS PART OF SUBMITTAL
<br />PACKAGE (BY SUCCESSFUL VENDOR).
<br />2. THIS CONTRACTOR SHALL GENERALLY BE REQUIRED TO FURNISH AND INSTALL POWER WIRING / CONDUIT
<br />FOR INDOOR UNITS AND BRANCH SELECTOR BOXES (WHERE APPLICABLE). E.C. TO FURNISH A JUNCTION BOX
<br />WITH POWER WIRING FROM PANEL IN THE VICINITY OF EACH INDOOR FAN COIL UNIT. E.C. TO FURNISH A
<br />2 -POLE, FUSED DISCONNECT SWITCH (FUSED PER MFG'S RECOMMENDATIONS) AT EACH INDOOR FAN COIL
<br />UNIT AND BRANCH SELECTOR BOX. THIS CONTRACTOR TO FURNISH AND INSTALL POWER WIRING AND
<br />CONDUIT (SIZED PER NEC, ELECTRICAL DRAWINGS, AND MFG RECOMMENDATIONS) FROM EACH JUNCTION
<br />BOX TO EACH FAN COIL UNIT (AND, WHERE APPLICABLE, THE ASSOCIATED BRANCH SELECTOR BOX). M.C.
<br />CABLE MAY BE UTILIZED WHERE ALLOWED PER THE ELECTRICAL SPECIFICATIONS. ROUTE THROUGH
<br />DISCONNECT TO EQUIPMENT - BY THIS CONTRACTOR. SEE ELECTRICAL DRAWINGS AND MECHANICAL
<br />DETAILS.
<br />3. THIS CONTRACTOR TO FURNISH AND INSTALL ALL CONTROL CONDUIT, WIRING, CABLES (LOW VOLTAGE AND
<br />OTHERWISE).
<br />4. E.C. TO FURNISH AND INSTALL FUSED DISCONNECT SWITCHES FOR ALL INDOOR FAN COIL UNITS, BRANCH
<br />G
<br />SELECTOR BOXES, AND OUTDOOR UNITS. THIS CONTRACTOR TO SUPPLY FUSES (SIZED PER MFG'S
<br />RECOMMENDATIONS).
<br />5. THIS CONTRACTOR TO FURNISH AND INSTALL ALL REFRIGERANT PIPING, ALONG WITH ASSOCIATED FITTINGS,
<br />DEVICES, CONTROLS, ETC. FOR A COMPLETE SYSTEM PER THE VRV MANUFACTURER'S SUGGESTIONS.
<br />6. BASIS OF DESIGN IS DAIKIN.
<br />DEMOLITION NOTES
<br />1. ALL DEMOLITION WORK OF EXISTING HVAC SYSTEM TO BE BY OWNER, WITH THE EXCEPTION OF THE
<br />EXISTING CONDENSING UNITS ON THE ROOF. THIS CONTRACTOR TO BE RESPONSIBLE FOR REMOVING
<br />H
<br />EXISTING CONDENSING UNITS (WHILE CRANE IS AVAILABLE TO SET NEW OUTDOOR UNITS).
<br />2. M.C. TO REMOVE EXISTING WINDOW THAT WILL BE REPLACED WITH AN O/A INTAKE LOUVER.
<br />3
<br />4
<br />LEGEND
<br />A CEILING SUPPLY DIFFUSER, TYPE AND CFM INDICATED
<br />275
<br />F CEILING RETURN GRILLE, TYPE AND CFM INDICATED
<br />450
<br />E CEILING EXHAUST GRILLE, TYPE AND CFM INDICATED
<br />95
<br />TYPE CEILING RETURN GRILLE, TYPE AND CFM INDICATED
<br />G"
<br />IU -5 CONCEALED DUCTED INDOOR UNIT
<br />IU 1 I CEILING CASSETTE INDOOR UNIT
<br />C CONDENSATE DRAIN PIPING
<br />R REFRIGERANT PIPING
<br />24X12 RECTANGULAR DUCT, WIDTH x DEPTH
<br />ROUND OR SPIRAL DUCT, DIAMETER
<br />DUCT BALANCE DAMPER
<br />DUCT TRANSITION
<br />DUCT TAKEOFF AT 45 DEGREES(TYPICAL)
<br />DUCT SQUARE ELBOW WITH TURNING VANES
<br />SD DUCT SMOKE DETECTOR (FURNISHED
<br />BY E.C. AND INSTALLED BY M.C.)
<br />UC UNDERCUT DOOR
<br />OT WALL MOUNTED THERMOSTAT / CONTROLLER
<br />FLEXIBL
<br />CONNECTION
<br />RETURN 1 01111!
<br />5
<br />FLEXIBLE
<br />CONNECTION
<br />3/4" COND. DRAIN AND
<br />AUXILIARY DRAIN PAN WITH 3/4" AUX. PAN DRAIN TO
<br />FLOAT SWITCH UNDER A/H OR P CONTR'S DRAIN
<br />OR PUMP.
<br />UNIT BY THIS CONTRACTOR
<br />OUTSIDE AIR SCHEDULE
<br />A/H UNIT MOUNTED IN
<br />HORIZONTAL POSITION
<br />CFM
<br />IU -1 -01
<br />50
<br />IU -1 -02
<br />50
<br />IU -1 -03
<br />50
<br />5
<br />FLEXIBLE
<br />CONNECTION
<br />3/4" COND. DRAIN AND
<br />AUXILIARY DRAIN PAN WITH 3/4" AUX. PAN DRAIN TO
<br />FLOAT SWITCH UNDER A/H OR P CONTR'S DRAIN
<br />OR PUMP.
<br />UNIT BY THIS CONTRACTOR
<br />OUTSIDE AIR SCHEDULE
<br />UNIT
<br />CFM
<br />IU -1 -01
<br />50
<br />IU -1 -02
<br />50
<br />IU -1 -03
<br />50
<br />IU -1 -04
<br />50
<br />IU -1 -05
<br />50
<br />IU -1 -06
<br />40
<br />IU -1 -07
<br />40
<br />IU -1 -08
<br />35
<br />IU -1 -09
<br />20
<br />IU -1 -10
<br />40
<br />IU -1 -11
<br />20
<br />IU -1 -12
<br />20
<br />IU -1 -13
<br />10
<br />IU -1 -14
<br />45
<br />IU -1 -15
<br />175
<br />IU -1 -16
<br />175
<br />IU -1 -17
<br />15
<br />IU -1 -18
<br />20
<br />IU -1 -19
<br />20
<br />IU -1 -20
<br />10
<br />IU -1 -21
<br />10
<br />IU -1 -22
<br />25
<br />IU -1 -23
<br />10
<br />IU -1 -24
<br />10
<br />IU -1 -25
<br />40
<br />IU -1 -26
<br />15
<br />IU -1 -27
<br />10
<br />TYPICAL A/H UNIT DETAIL
<br />1 1 2 1 3 1 4
<br />NOT TO SCALE
<br />5
<br />0
<br />7
<br />E-1
<br />MECHANICAL SUMMARY - MECHANICAL SYSTEMS, SERVICE SYSTEMS, AND EQUIPMENT
<br />THERMALZONE 4A
<br />WINTER DRY BULB 16 °F
<br />SUMMER DRY BULB 93 °F
<br />INTERIOR DESIGN CONDITIONS
<br />WINTER DRY BULB 70 °F
<br />SUMMER DRY BULB 75 °F
<br />RELATIVE HUMIDITY 50%
<br />BUILDING HEATING LOAD 179,000 BTUH
<br />BUILDING COOLING LOAD 20 TONS
<br />MECHANICAL SPACING CONDITIONING SYSTEM
<br />UNITARY
<br />DESCRIPTION OF UNIT
<br />HEATING EFFICIENCY REFER TO EQUIPMENT SCHEDULES FOR EFFICIENCIES
<br />COOLING EFFICIENCY
<br />SIZE CATEGORY OF UNIT
<br />BOILER
<br />TOTAL BOILER OUTPUT. IF OVERSIZED STATE REASON N/A
<br />CHILLER
<br />TOTAL CHILLER CAPACITY. IF OVERSIZED STATE REASON N / A
<br />LIST EQUIPMENT EFFICIENCIES I REFER TO EQUIPMENT SCHEDULES FOR EFFICIENCIES
<br />GRILLE & DIFFUSER SCHEDULE
<br />SYMBOL TYPE LOCATION MANUFACTURER SIZE CFM REMARKS
<br />MODEL
<br />A SUPPLY CEILING PRICE 10 "0 OFF -WHITE FINISH, SQUARE TO ROUND
<br />LAY -IN SCD 2424 400 TRANSITION AS REQUIRED
<br />B RETURN/ CEILING PRICE 6x6 100 OFF -WHITE FINISH
<br />EXHAUST LAY -IN PDDR 24x24
<br />C RETURN/ CEILING PRICE 8x8 220 OFF -WHITE FINISH
<br />EXHAUST LAY -IN PDDR 24x24
<br />RETURN/ CEILING PRICE 10x10
<br />D EXHAUST LAY -IN PDDR 350 OFF-WHITE FINISH
<br />24x24
<br />RETURN/ CEILING PRICE 16x16
<br />E EXHAUST LAY -IN PDDR 600 OFF-WHITE FINISH
<br />2 4x24
<br />NOTES:
<br />1. ALL GRILLES / DIFFUSERS SERVING LOCKERS, KITCHEN, TOILETS AND JAN. CLOSETS TO HAVE ALUMINUM CONSTRUCTION.
<br />2. ALL GRILLE DESIGNATIONS MAY NOT BE UTILIZED ON THIS PROJECT.
<br />3. BASIS OF DESIGN - PRICE; EQUIVALENT PRODUCTS BY: CARNES, TITUS, AND KRUEGER.
<br />HOOD / LOUVER SCHEDULE
<br />SYMBOL TYPE LOCATION MANUFACTURER SIZE CFM REMARKS
<br />MODEL
<br />INTAKE WALL RUSKIN 48x72 1055 1, 2, 3, 4
<br />LOUVER ELF -375DX
<br />REMARKS:
<br />1. BIRD SCREEN
<br />2. BAKED ENAMEL FINISH - COLOR BY OWNER.
<br />3. COMPARABLE PRODUCTS BY ARROW, CESCO, AMERICAN WARMING & VENTILATING, EMPCO, & DOWCO
<br />4. COORDINATE DIMENSIONS WITH EXISTING WINDOW DIMENSIONS PRIOR TO ORDERING.
<br />FAN SCHEDULE
<br />FAN # TYPE LOCATION CFM S.P. RPM HP VOLT -PH. MFG. & MODEL SONES ROOF OPG. REMARKS
<br />EF -1 EXHAUST ROOF 450 .5" 1620 1/10 120 -1 GREENHECK 7.1 10.5x10.5 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />EF -2 EXHAUST ROOF 400 .5" 1620 1/10 120 -1 GREENHECK 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />0
<br />NOTE: BASIS OF DESIGN - GREENHECK; EQUIVALENT PRODUCTS BY CARNES, COOK, & PENN
<br />REMARKS:
<br />1. DISCONNECT SWITCH
<br />2. BACKDRAFT DAMPER
<br />3. PRE - FABRICATED ROOF CURB. COORDINATE WITH ROOF TYPE AND SLOPE.
<br />4. ON PROGRAM CONTROL WITH LOCAL AHU ZONE TO RUN WHEN BLDG. IS OCCUPIED.
<br />5. BIRD SCREEN
<br />7
<br />E-'
<br />A
<br />0
<br />C
<br />N
<br />C
<br />F
<br />G
<br />H
<br />WA AA
<br />R Kli
<br />=ENGINEERS
<br />Reece, Noland & McElrath, Inc.
<br />94 Main Street
<br />Canton, North Carolina 28716
<br />PHONE: 828 - 492 -0677
<br />FAX: 828 - 492 -1054
<br />MAIL @RNM - ENGINEERS. COM
<br />WWW.RNM- ENGINEERS.COM
<br />NC CERT. N0. C -0149
<br />(C 2018
<br />SEALS:
<br />m Z W J }} }}i]If7f1l
<br />o = ¢� CAR
<br />0 U W `1� ` oneoav /f,
<br />��JW
<br />ZNU O �.o7
<br />cno OW SEAL _
<br />- 0uiU-0
<br />O w
<br />?i u- ui m L i i --5 a
<br />Q N W f� , ° °�'ci;[n,4 K].
<br />= V)
<br />U)
<br />z
<br />O
<br />F_
<br />U
<br />Wz
<br />0
<br />W F_
<br />LL Q
<br />00.
<br />�
<br />Q _j Z
<br />W
<br />D
<br />0 Z o
<br />m W 0
<br />75 m
<br />F_ ::D J
<br />z
<br />W
<br />O c)
<br />U �
<br />W =
<br />V
<br />z
<br />U OW
<br />0
<br />REVISIONS /SU BM ISSIONS
<br />NO DATE ISSUED FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />6
<br />7
<br />8
<br />SHEET TITLE:
<br />MECHANICAL
<br />SUMMARY AND
<br />SCHEDULES
<br />ISSUED FOR:
<br />CONSTRUCTION
<br />DRAWN BY: DJM DRAWING NO.
<br />APPROVED BY: MRM
<br />PROJECT #:
<br />2017108 0 .1
<br />DATE:
<br />05/07/2018
<br />OF 8 SHEETS
<br />GRILLE & DIFFUSER SCHEDULE
<br />SYMBOL TYPE LOCATION MANUFACTURER SIZE CFM REMARKS
<br />MODEL
<br />A SUPPLY CEILING PRICE 10 "0 OFF -WHITE FINISH, SQUARE TO ROUND
<br />LAY -IN SCD 2424 400 TRANSITION AS REQUIRED
<br />B RETURN/ CEILING PRICE 6x6 100 OFF -WHITE FINISH
<br />EXHAUST LAY -IN PDDR 24x24
<br />C RETURN/ CEILING PRICE 8x8 220 OFF -WHITE FINISH
<br />EXHAUST LAY -IN PDDR 24x24
<br />RETURN/ CEILING PRICE 10x10
<br />D EXHAUST LAY -IN PDDR 350 OFF-WHITE FINISH
<br />24x24
<br />RETURN/ CEILING PRICE 16x16
<br />E EXHAUST LAY -IN PDDR 600 OFF-WHITE FINISH
<br />2 4x24
<br />NOTES:
<br />1. ALL GRILLES / DIFFUSERS SERVING LOCKERS, KITCHEN, TOILETS AND JAN. CLOSETS TO HAVE ALUMINUM CONSTRUCTION.
<br />2. ALL GRILLE DESIGNATIONS MAY NOT BE UTILIZED ON THIS PROJECT.
<br />3. BASIS OF DESIGN - PRICE; EQUIVALENT PRODUCTS BY: CARNES, TITUS, AND KRUEGER.
<br />HOOD / LOUVER SCHEDULE
<br />SYMBOL TYPE LOCATION MANUFACTURER SIZE CFM REMARKS
<br />MODEL
<br />INTAKE WALL RUSKIN 48x72 1055 1, 2, 3, 4
<br />LOUVER ELF -375DX
<br />REMARKS:
<br />1. BIRD SCREEN
<br />2. BAKED ENAMEL FINISH - COLOR BY OWNER.
<br />3. COMPARABLE PRODUCTS BY ARROW, CESCO, AMERICAN WARMING & VENTILATING, EMPCO, & DOWCO
<br />4. COORDINATE DIMENSIONS WITH EXISTING WINDOW DIMENSIONS PRIOR TO ORDERING.
<br />FAN SCHEDULE
<br />FAN # TYPE LOCATION CFM S.P. RPM HP VOLT -PH. MFG. & MODEL SONES ROOF OPG. REMARKS
<br />EF -1 EXHAUST ROOF 450 .5" 1620 1/10 120 -1 GREENHECK 7.1 10.5x10.5 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />EF -2 EXHAUST ROOF 400 .5" 1620 1/10 120 -1 GREENHECK 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />0
<br />NOTE: BASIS OF DESIGN - GREENHECK; EQUIVALENT PRODUCTS BY CARNES, COOK, & PENN
<br />REMARKS:
<br />1. DISCONNECT SWITCH
<br />2. BACKDRAFT DAMPER
<br />3. PRE - FABRICATED ROOF CURB. COORDINATE WITH ROOF TYPE AND SLOPE.
<br />4. ON PROGRAM CONTROL WITH LOCAL AHU ZONE TO RUN WHEN BLDG. IS OCCUPIED.
<br />5. BIRD SCREEN
<br />7
<br />E-'
<br />A
<br />0
<br />C
<br />N
<br />C
<br />F
<br />G
<br />H
<br />WA AA
<br />R Kli
<br />=ENGINEERS
<br />Reece, Noland & McElrath, Inc.
<br />94 Main Street
<br />Canton, North Carolina 28716
<br />PHONE: 828 - 492 -0677
<br />FAX: 828 - 492 -1054
<br />MAIL @RNM - ENGINEERS. COM
<br />WWW.RNM- ENGINEERS.COM
<br />NC CERT. N0. C -0149
<br />(C 2018
<br />SEALS:
<br />m Z W J }} }}i]If7f1l
<br />o = ¢� CAR
<br />0 U W `1� ` oneoav /f,
<br />��JW
<br />ZNU O �.o7
<br />cno OW SEAL _
<br />- 0uiU-0
<br />O w
<br />?i u- ui m L i i --5 a
<br />Q N W f� , ° °�'ci;[n,4 K].
<br />= V)
<br />U)
<br />z
<br />O
<br />F_
<br />U
<br />Wz
<br />0
<br />W F_
<br />LL Q
<br />00.
<br />�
<br />Q _j Z
<br />W
<br />D
<br />0 Z o
<br />m W 0
<br />75 m
<br />F_ ::D J
<br />z
<br />W
<br />O c)
<br />U �
<br />W =
<br />V
<br />z
<br />U OW
<br />0
<br />REVISIONS /SU BM ISSIONS
<br />NO DATE ISSUED FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />6
<br />7
<br />8
<br />SHEET TITLE:
<br />MECHANICAL
<br />SUMMARY AND
<br />SCHEDULES
<br />ISSUED FOR:
<br />CONSTRUCTION
<br />DRAWN BY: DJM DRAWING NO.
<br />APPROVED BY: MRM
<br />PROJECT #:
<br />2017108 0 .1
<br />DATE:
<br />05/07/2018
<br />OF 8 SHEETS
<br />NOTES:
<br />1. ALL GRILLES / DIFFUSERS SERVING LOCKERS, KITCHEN, TOILETS AND JAN. CLOSETS TO HAVE ALUMINUM CONSTRUCTION.
<br />2. ALL GRILLE DESIGNATIONS MAY NOT BE UTILIZED ON THIS PROJECT.
<br />3. BASIS OF DESIGN - PRICE; EQUIVALENT PRODUCTS BY: CARNES, TITUS, AND KRUEGER.
<br />HOOD / LOUVER SCHEDULE
<br />SYMBOL TYPE LOCATION MANUFACTURER SIZE CFM REMARKS
<br />MODEL
<br />INTAKE WALL RUSKIN 48x72 1055 1, 2, 3, 4
<br />LOUVER ELF -375DX
<br />REMARKS:
<br />1. BIRD SCREEN
<br />2. BAKED ENAMEL FINISH - COLOR BY OWNER.
<br />3. COMPARABLE PRODUCTS BY ARROW, CESCO, AMERICAN WARMING & VENTILATING, EMPCO, & DOWCO
<br />4. COORDINATE DIMENSIONS WITH EXISTING WINDOW DIMENSIONS PRIOR TO ORDERING.
<br />FAN SCHEDULE
<br />FAN # TYPE LOCATION CFM S.P. RPM HP VOLT -PH. MFG. & MODEL SONES ROOF OPG. REMARKS
<br />EF -1 EXHAUST ROOF 450 .5" 1620 1/10 120 -1 GREENHECK 7.1 10.5x10.5 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />EF -2 EXHAUST ROOF 400 .5" 1620 1/10 120 -1 GREENHECK 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />0
<br />NOTE: BASIS OF DESIGN - GREENHECK; EQUIVALENT PRODUCTS BY CARNES, COOK, & PENN
<br />REMARKS:
<br />1. DISCONNECT SWITCH
<br />2. BACKDRAFT DAMPER
<br />3. PRE - FABRICATED ROOF CURB. COORDINATE WITH ROOF TYPE AND SLOPE.
<br />4. ON PROGRAM CONTROL WITH LOCAL AHU ZONE TO RUN WHEN BLDG. IS OCCUPIED.
<br />5. BIRD SCREEN
<br />7
<br />E-'
<br />A
<br />0
<br />C
<br />N
<br />C
<br />F
<br />G
<br />H
<br />WA AA
<br />R Kli
<br />=ENGINEERS
<br />Reece, Noland & McElrath, Inc.
<br />94 Main Street
<br />Canton, North Carolina 28716
<br />PHONE: 828 - 492 -0677
<br />FAX: 828 - 492 -1054
<br />MAIL @RNM - ENGINEERS. COM
<br />WWW.RNM- ENGINEERS.COM
<br />NC CERT. N0. C -0149
<br />(C 2018
<br />SEALS:
<br />m Z W J }} }}i]If7f1l
<br />o = ¢� CAR
<br />0 U W `1� ` oneoav /f,
<br />��JW
<br />ZNU O �.o7
<br />cno OW SEAL _
<br />- 0uiU-0
<br />O w
<br />?i u- ui m L i i --5 a
<br />Q N W f� , ° °�'ci;[n,4 K].
<br />= V)
<br />U)
<br />z
<br />O
<br />F_
<br />U
<br />Wz
<br />0
<br />W F_
<br />LL Q
<br />00.
<br />�
<br />Q _j Z
<br />W
<br />D
<br />0 Z o
<br />m W 0
<br />75 m
<br />F_ ::D J
<br />z
<br />W
<br />O c)
<br />U �
<br />W =
<br />V
<br />z
<br />U OW
<br />0
<br />REVISIONS /SU BM ISSIONS
<br />NO DATE ISSUED FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />6
<br />7
<br />8
<br />SHEET TITLE:
<br />MECHANICAL
<br />SUMMARY AND
<br />SCHEDULES
<br />ISSUED FOR:
<br />CONSTRUCTION
<br />DRAWN BY: DJM DRAWING NO.
<br />APPROVED BY: MRM
<br />PROJECT #:
<br />2017108 0 .1
<br />DATE:
<br />05/07/2018
<br />OF 8 SHEETS
<br />REMARKS:
<br />1. BIRD SCREEN
<br />2. BAKED ENAMEL FINISH - COLOR BY OWNER.
<br />3. COMPARABLE PRODUCTS BY ARROW, CESCO, AMERICAN WARMING & VENTILATING, EMPCO, & DOWCO
<br />4. COORDINATE DIMENSIONS WITH EXISTING WINDOW DIMENSIONS PRIOR TO ORDERING.
<br />FAN SCHEDULE
<br />FAN # TYPE LOCATION CFM S.P. RPM HP VOLT -PH. MFG. & MODEL SONES ROOF OPG. REMARKS
<br />EF -1 EXHAUST ROOF 450 .5" 1620 1/10 120 -1 GREENHECK 7.1 10.5x10.5 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />EF -2 EXHAUST ROOF 400 .5" 1620 1/10 120 -1 GREENHECK 1, 2, 3, 4, 5
<br />#G- 075 -VG
<br />0
<br />NOTE: BASIS OF DESIGN - GREENHECK; EQUIVALENT PRODUCTS BY CARNES, COOK, & PENN
<br />REMARKS:
<br />1. DISCONNECT SWITCH
<br />2. BACKDRAFT DAMPER
<br />3. PRE - FABRICATED ROOF CURB. COORDINATE WITH ROOF TYPE AND SLOPE.
<br />4. ON PROGRAM CONTROL WITH LOCAL AHU ZONE TO RUN WHEN BLDG. IS OCCUPIED.
<br />5. BIRD SCREEN
<br />7
<br />E-'
<br />A
<br />0
<br />C
<br />N
<br />C
<br />F
<br />G
<br />H
<br />WA AA
<br />R Kli
<br />=ENGINEERS
<br />Reece, Noland & McElrath, Inc.
<br />94 Main Street
<br />Canton, North Carolina 28716
<br />PHONE: 828 - 492 -0677
<br />FAX: 828 - 492 -1054
<br />MAIL @RNM - ENGINEERS. COM
<br />WWW.RNM- ENGINEERS.COM
<br />NC CERT. N0. C -0149
<br />(C 2018
<br />SEALS:
<br />m Z W J }} }}i]If7f1l
<br />o = ¢� CAR
<br />0 U W `1� ` oneoav /f,
<br />��JW
<br />ZNU O �.o7
<br />cno OW SEAL _
<br />- 0uiU-0
<br />O w
<br />?i u- ui m L i i --5 a
<br />Q N W f� , ° °�'ci;[n,4 K].
<br />= V)
<br />U)
<br />z
<br />O
<br />F_
<br />U
<br />Wz
<br />0
<br />W F_
<br />LL Q
<br />00.
<br />�
<br />Q _j Z
<br />W
<br />D
<br />0 Z o
<br />m W 0
<br />75 m
<br />F_ ::D J
<br />z
<br />W
<br />O c)
<br />U �
<br />W =
<br />V
<br />z
<br />U OW
<br />0
<br />REVISIONS /SU BM ISSIONS
<br />NO DATE ISSUED FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />6
<br />7
<br />8
<br />SHEET TITLE:
<br />MECHANICAL
<br />SUMMARY AND
<br />SCHEDULES
<br />ISSUED FOR:
<br />CONSTRUCTION
<br />DRAWN BY: DJM DRAWING NO.
<br />APPROVED BY: MRM
<br />PROJECT #:
<br />2017108 0 .1
<br />DATE:
<br />05/07/2018
<br />OF 8 SHEETS
<br />0
<br />NOTE: BASIS OF DESIGN - GREENHECK; EQUIVALENT PRODUCTS BY CARNES, COOK, & PENN
<br />REMARKS:
<br />1. DISCONNECT SWITCH
<br />2. BACKDRAFT DAMPER
<br />3. PRE - FABRICATED ROOF CURB. COORDINATE WITH ROOF TYPE AND SLOPE.
<br />4. ON PROGRAM CONTROL WITH LOCAL AHU ZONE TO RUN WHEN BLDG. IS OCCUPIED.
<br />5. BIRD SCREEN
<br />7
<br />E-'
<br />A
<br />0
<br />C
<br />N
<br />C
<br />F
<br />G
<br />H
<br />WA AA
<br />R Kli
<br />=ENGINEERS
<br />Reece, Noland & McElrath, Inc.
<br />94 Main Street
<br />Canton, North Carolina 28716
<br />PHONE: 828 - 492 -0677
<br />FAX: 828 - 492 -1054
<br />MAIL @RNM - ENGINEERS. COM
<br />WWW.RNM- ENGINEERS.COM
<br />NC CERT. N0. C -0149
<br />(C 2018
<br />SEALS:
<br />m Z W J }} }}i]If7f1l
<br />o = ¢� CAR
<br />0 U W `1� ` oneoav /f,
<br />��JW
<br />ZNU O �.o7
<br />cno OW SEAL _
<br />- 0uiU-0
<br />O w
<br />?i u- ui m L i i --5 a
<br />Q N W f� , ° °�'ci;[n,4 K].
<br />= V)
<br />U)
<br />z
<br />O
<br />F_
<br />U
<br />Wz
<br />0
<br />W F_
<br />LL Q
<br />00.
<br />�
<br />Q _j Z
<br />W
<br />D
<br />0 Z o
<br />m W 0
<br />75 m
<br />F_ ::D J
<br />z
<br />W
<br />O c)
<br />U �
<br />W =
<br />V
<br />z
<br />U OW
<br />0
<br />REVISIONS /SU BM ISSIONS
<br />NO DATE ISSUED FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />6
<br />7
<br />8
<br />SHEET TITLE:
<br />MECHANICAL
<br />SUMMARY AND
<br />SCHEDULES
<br />ISSUED FOR:
<br />CONSTRUCTION
<br />DRAWN BY: DJM DRAWING NO.
<br />APPROVED BY: MRM
<br />PROJECT #:
<br />2017108 0 .1
<br />DATE:
<br />05/07/2018
<br />OF 8 SHEETS