2 <br />   <br />1. What I read in this document was the Orange Alamance Water System (OAWS) was never  <br />designed or constructed for fire protection. My question to the engineer/OAWS, If that was the  <br />intent of the design, why would you install a fire hydrant on the system in the first place and  <br />subsequently install additional hydrants?  <br />2. Why didn’t the engineer reach out to the Fire Marshal for comment and review for fire  <br />protection needs in Orange County?  <br />3. NC Fire Code is specific and requires there to be an approved water supply capable of supplying  <br />the required fire flow for fire protection of buildings constructed or moved into within the  <br />jurisdiction. This requirement is applicable to the OAWS and any construction that expands from  <br />their water system is required to meet the fire flow requirements to protect those buildings. The  <br />insurance service office (ISO) is the grading/rating that fire departments categorize for their  <br />capability and resources. A majority of that grade is the water supply in the fire district and the  <br />capability of that department to meet fire flow requirements of structures within their  <br />jurisdiction. If this water system is “not designed” as indicated in the letter from Michael M.  <br />Hughes, P.E., I would like to know how that statement meets the intent of the code? My  <br />interpretation is that it does not and I would like to see a plan of action for infrastructure design  <br />to meet the intent of the code for purposes of fire protection. The link below has on page 3,  <br />code requirements for the water system to be maintained in an operative condition at all times  <br />and shall be repaired where defective, section 507.5.2. My understanding from the letter is that  <br />it doesn’t meet that code requirement and again, I’d like to see a plan of improvement.   <br />4. Permit drawings were mentioned as being submitted as indicated in paragraph 10. The Harts  <br />Mill water system is required per the fire code in chapter one (1) to be permitted, reviewed,  <br />approved and inspected from the Fire Marshal when there is an installation of a private fire  <br />service main. I haven’t seen any construction submittals from this project. The permitting takes  <br />place at the building inspections department, 131 W. Margaret Lane, Hillsborough, NC 27278.  <br />The review will be conducted utilizing NC Fire Code and applicable NFPA Standard, 24 and (NFPA  <br />1142 for the installation of the dry pipe for the static water source).   <br />5. Please have OAWS provide the Fire Marshal Division (attention Jason B. Shepherd, Fire Marshal)  <br />with documentation of the most recent water supply test of the water supply system as  <br />indicated in Section 507.4 of the NC Fire Code. See link page 3 for reference  <br />http://ecodes.biz/ecodes_support/free_resources/2012NorthCarolina/Fire/PDFs/Chapter%205 <br />%20‐%20Fire%20Service%20Features.pdf  <br />   <br />   <br />If there is any other question, follow up or future discussion regarding the OAWS, please include the fire  <br />marshal in those discussions.  <br />   <br />Thank you for the opportunity to comment on this subject.  <br />   <br />Jason  <br />   <br />   <br />Jason B. Shepherd  <br />Orange County Fire Marshal  <br />Orange County Emergency Services  <br />Fire Marshal Division  <br />510 Meadowlands Drive, Hillsborough NC 27278  <br />P.O. Box 8181, Hillsborough NC 27278  <br />Office (919) 245-6151  <br />Cellular (919) 257-8316  <br />Fax (919) 732-8137  <br />jshepherd@orangecountync.gov  <br />29