Orange County NC Website
:-: <br /> : . , <br /> n • <br /> i!:::: <br /> LE; 7. OWASA Easements-No grading. plantings, or encroachments are allowed <br /> t±' • within OWASA water or sewer easements. Propos.d .a50mrN* must <br /> n• have a vehicular access for OWASA maintenance vehicles with slopes <br /> bi not greater than 4 to 1. <br /> Repty:So Noted <br /> n . <br /> • <br /> (:.,.1 <br /> 8. Blocking & Rodding —retainer glands to be used on all mechanical joins <br /> . In addition to rodding and blocking. . . <br /> • <br /> Rep o Naiad <br /> H �. Dechlorination l quirerrren#s-Thy.ion c#or shatl be responsible for <br /> neutralization of chlorinated water at the point of discharge from the main <br /> being tested. This shall occur following chlorination to disinfect the main <br /> P • . or any other time when elevated levels of chlorine could potentially be <br /> t-o discharged into the environment by the contractor, At the time of <br /> f�:: disinfection and purity testing procedures are discussed with the OWASA <br /> Construction Inspector, the procedure for dechlorination will be covered. <br /> {,.. Absolutely no flcrnhing, disinfection or purity sampling is to take place <br /> 1,1 without prior approval of a sampling plan by the OWASA Inspector. <br /> VA <br /> Rep(y:So Noted <br /> .�� 10,Cross-Connection Control Ordinance-Backflow Prevention with be <br /> required in accordance with OWASA Cross Connection Control <br /> Li Ordirwnce and Manual. <br /> ne#fy: o Noted o�Noted <br /> i,',1 . <br /> tj 11.Remote Read-out Devlses-D DA andlor RPDA devices located Inside <br /> � Nptun.buildings must be equipped with T-'10 Remot. Read-out with <br /> �n Read-pad located outside the building in a location accessible by . <br /> OWASA personnel . <br /> Reply: Noted <br /> 1. ; 11 Fire Protection Systems-Pressure testit�g, chlorination, and purity tesling <br /> L shaH be completed before the instalFation of the DCDAIRPDA unit. <br /> (a Rep!}r: o Noted <br />