Orange County NC Website
19 <br /> Hot water pipes below the <br /> R8 sink are insulated or <br /> otherwise configured to <br /> protect against contact <br /> Other <br /> Safety or <br /> Access <br /> Concerns <br /> Restrooms(continued) Standard Met Notes and Possible Solutions <br /> (Yes/No/TBD/Other) <br /> Next to toilet, a side grab bar <br /> at least 42 inches long on the <br /> R9 side wall and mounted a <br /> maximum 12" from the back <br /> wall and 33"-36" from the <br /> floor <br /> Rear grab bar mounted 33"- <br /> 36" above the floor. If the <br /> toilet is not in a stall, the rear <br /> R10 wall grab bar must be at least <br /> 36" long with the end closer <br /> to the side wall mounted at <br /> least 12" from the centerline <br /> of the toilet <br /> Accessible stall is a minimum <br /> of 60" wide and 56" deep if <br /> wall-hung or 59" deep if <br /> R11 floor-mounted.This allows <br /> clear floor space for <br /> wheelchair turning radius. <br /> Door should swing out. <br /> If flush control is hand <br /> R12 operated, the operable part <br /> is located no higher than 48" <br /> above the floor <br /> R13 <br /> Stall is self-closing <br /> 18 <br />