DocuSign Envelope ID: E9612703-F25B-492D-9C8C-EC3F9728ECE6 <br /> 3. Compressor overload protection. <br /> 4. Compressor over current protection. <br /> 5. IPM module protection. <br /> H. Electrical Requirements: <br /> 1. Units shall operate on single-phase, 60 Hz power at <br /> 208/230 v. <br /> 2. Unit electrical power shall be a single point connection. <br /> 3.All power and control wiring must be installed per NEC <br /> and all local electrical codes. <br /> 4.Units shall have multiple terminal blocks to connect to <br /> multiple indoor units. <br /> Indoor Units: <br /> 1.01 System Description <br /> Indoor, wall-mounted, direct expansion fan coils are matched with <br /> heat pump outdoor units. <br /> 1.02 Agency Listings <br /> Unit shall be rated per AHRI Standards 210/240 and listed in the <br /> AHRI directory as a matched system. <br /> 1.03 Delivery, Storage,And Handling <br /> Units shall be shipped in one piece and shall be stored and handled <br /> per manufacturer's recommendations. <br /> 1.04 Warranty (For Inclusion By Specifying <br /> Engineer) <br /> PART 2—PRODUCTS <br /> 2.01 Equipment <br /> A. General: <br /> Indoor, direct-expansion,wall-mounted fan coil. Unit shall be <br /> complete with cooling/heating coil, fan, fan motor,piping <br /> connectors, electrical controls,microprocessor control system, and <br /> integral temperature sensing. Unit shall be furnished with integral <br /> wall mounting bracket and mounting hardware. <br /> B. Unit Cabinet: <br /> Cabinet discharge and inlet grilles shall be attractively styled, <br /> high-impact polystyrene. Cabinet shall be fully insulated for <br /> improved thermal/acoustic performance. <br /> C. Fans: <br /> 1.Fan shall be tangential direct-drive blower type with air <br /> intake at the top of the unit and discharge at the bottom <br /> front. Automatic, motor-driven vertical air sweep shall be <br /> provided standard. <br /> 2. Air sweep operation shall be useable selectable. The vertical <br /> sweep may be adjusted(using the remote control) and the <br /> horizontal air direction maybe be set manually. <br /> 15H-22 <br />